1
Torque Specifications
SU50K3/3PM, SU50K3/3INTPM:
• 150A Terminal Blocks: 61 kgf-cm (4.4 ft-lb)
• 200A Terminal Blocks: 102 kgf-cm (7.4 ft-lb)
SU80K3/3PM, SU80K3/3INTPM, SU100K3/3PM,
SU100K3/3INTPM, SU120K3/3PM:
• 200A Terminal Blocks: 102 kgf-cm (7.4 ft-lb)
• Bus Bar (w/M8 screw): 110 kgf-cm (8.0 ft-lb)
SU120K3/3INTPM:
• Bus Bar (w/M8 screw): 110 kgf-cm (8.0 ft-lb)
• 200A Terminal Blocks (w/M10 screw): 102 kgf-cm (7.4 ft-lb)
SU160K3/3PM, SU160K3/3INTPM, SU200K3/3PM,
SU200K3/3INTPM:
• Bus Bar (w/M8 screw): 110 kgf-cm (8.0 ft-lb)
Recommended Cable Sizes
UPS Power Module
SU50K SU80K SU100K
SU120K
SU160K SU200K
SU50K
SU80K
SU100K
SU120K SU160K
SU200K
Model
3/3PM
3/3PM
3/3PM
3/3PM
3/3PM
3/3PM
3/3INTPM
3/3INTPM
3/3INTPM
3/3INTPM 3/3INTPM
3/3INTPM
UPS System Capacity (kVA)
50
80
100
120
160
200
50
80
100
120
160
200
Input Circuit Breaker (A)
100
150
175
225
300
350
125
200
225
300
350
500
Input Cable (AWG)
2
1/0
3/0
4/0
250
Kcmil*
400
Kcmil*
1
3/0
3/0
4/0
250
Kcmil*
500
Kcmil*
Input Cable (mm
2
)
22
50
70
95
120
185
38
70
125
125
185
80 x 2
Reserve Input Circuit Breaker (A) 75
125
150
175
250
300
100
150
200
225
300
400
Reserve Input Cable (AWG)
6
2
1
1/0
3/0
250
Kcmil*
4
1
3/0
4/0
250
Kcmil*
500
Kcmil*
Reserve Input Cable (mm
2
)
10
25
35
50
70
120
22
38
80
100
38 x 2
80 x 2
Output Circuit Breaker (A)
75
125
150
175
250
300
100
150
200
225
300
400
Output Cable (AWG)
6
2
1
1/0
3/0
250
Kcmil*
4
1
3/0
4/0
250
Kcmil*
500
Kcmil*
Output Cable (mm
2
)
10
25
35
50
70
120
22
38
80
100
38 x 2
80 x 2
See Battery Module Owner's Manual or Contact Tripp Lite for Battery Module Cable Size Information. *Kcmil=MCM
1111 W. 35th Street
Chicago, IL 60609 USA
(773) 869-1234 • www.tripplite.com
Copyright © 2007 Tripp Lite. All rights reserved. The policy of Tripp Lite is one of continuous improvement. Specifications and diagrams are subject to change without notice.
3-Phase UPS Specifications
Addendum—50kVA & Above
Español
7
Floor Weight Loading Table
UPS Power Module
SU50K
SU80K
SU100K SU120K
SU160K
SU200K
SU50K
SU80K
SU100K SU120K
SU160K SU200K
Model
3/3PM
3/3PM
3/3PM
3/3PM
3/3PM
3/3PM
3/3INTPM
3/3INTPM
3/3INTPM 3/3INTPM
3/3INTPM 3/3INTPM
UPS System Capacity (kVA)
50
80
100
120
160
200
50
80
100
120
160
200
Weight (lb)
1276
1540
2040
2280
2550
2760
1012
1155
1543
1642
2315
2392
Weight (kg)
580
700
1020
1140
1275
1380
460
525
700
745
1050
1085
Weight Loading (lb/in
2
)
1.716
1.495
1.32
1.48
1.65
1.79
1.361
1.554
1.50
1.60
1.50
1.55
Weight Loading (kg/m
2
)
1208
1054
1024
1145
1280
1386
958
1094
1054
1122
1054
1089
See Battery Module Owner's Manual or Contact Tripp Lite for Battery Module Weight Loading Information.