background image

Voltage regulation
description

Automatic voltage regulation (AVR) circuits maintain clean, regulated computer-grade 120V nominal output,
without using battery power, during brownouts to 83V and overvoltages to 147V (120V) / 159V to 282V (230V)

Overvoltage correction

Overvoltages from 125V to 147 V (120V) and from 240V to 282V (230V) are reduced by 12%

Undervoltage
correction

A voltage boost of 14% applies when input voltage is between 83 and 104 (120V), 159V and 199V (230V)

LEDS ALARMS & SWITCHES

LED Indicators

5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status

Alarms

Audible alarm with 15 sec. delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front
panel alarm cancel button. Once silenced, alarm will re-sound when approximately 2 min. runtime remain.

Switches

Includes 2 front panel switches - one main on/off power switch and one dual function "alarm cancel" / "self test"
button

SURGE / NOISE SUPPRESSION

UPS AC suppression
joule rating

570 joules

EMI / RFI AC noise
suppression

Yes

PHYSICAL

Installation form
factors supported with
included accessories

Tower

Primary form factor

Tower

UPS / Power Module
dimensions in primary
form factor (height x
width x depth / inches)

10.2 x 9 x 12.5

UPS / Power Module
dimensions in primary
form factor (height x
width x depth / cm)

26 x 22.9 x 31.8

UPS / Power Module
weight (lbs)

51

UPS / Power Module
weight (kg)

23.2

UPS Shipping
dimensions (height x
width x depth / inches)

15.2 x 17.8 x 14.2

UPS Shipping
dimensions (height x
width x depth / cm)

38.7 x 45.1 x 36.2

UPS housing material

Steel

Cooling method

Fan

ENVIRONMENTAL

Operating
Temperature Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage Temperature
Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0 to 95%, non-condensing

Отзывы: