Mounting (Optional*)

(See Diagram 2, p. 32).

User must supply all fasteners and brackets and verify their suitability for use with the intended
mounting surface. Turn your APS PowerVerter and connected equipment OFF before mounting.

• Install two 8 mm (1/4 in.) fasteners (A) into a rigid horizontal surface using the measurements

in the diagram. Leave the heads of fasteners raised slightly above the surface in order to
engage the slots in the APS’s feet.

• Slide PowerVerter forward to fully engage the fasteners in the APS’s feet. Install two 8 mm

(1/4 in.) fasteners (B) into the surface, through the slots in the APS’s two unsecured feet.
Tighten the screws to secure the APS in position.

* Horizontal mounting should be used for all vehicular applications. Due to their size and weight, all APS PowerVerter

systems in vehicles should be mounted on a rigid horizontal (not vertical) surface, mounting plate or bracket before
battery connection. 

Battery Connection (Standard)

1. Connect your APS’s positive DC Terminal directly to a fuse.

UL recommends that you install a recognized UL component fuse block and fuse within 18 inches
of the battery. The fuse's rating must equal or exceed the Minimum DC Fuse Rating listed in your
APS model's specifications on pages 14 or 15.

2. Choose a battery configuration appropriate to your batteries.

•  Single Battery Connection:

Refer to Diagram 4, page 33. When using a single battery, its

voltage must be equal to the voltage of your APS's Inverter Nominal Input Voltage (see
specs).

•  Parallel Battery Connection:

Refer to Diagram 5, page 33. When using multiple batteries in

parallel, each battery's voltage must be equal to the voltage of your APS's Inverter Nominal
Input Voltage (see specs).

• Series Battery Connection:

Refer to Diagram 6, page 33. When using multiple batteries in

series, all batteries must be equal in voltage and amp hour capacity, and the sum of their 
voltages must be equal to the voltage of your APS's Inverter Nominal Input Voltage (see
specs).

3. Use 2/0 gauge wire ONLY to make external battery connections.

Tighten battery terminals to a torque of 4 N-m.

WARNING! Failure to follow these instructions can lead 

to product failure due to excessive heating!

Battery connection cable lengths should be short as possible, and must not exceed the
Maximum Cable Length listed under Specifications, page 14. Shorter and heavier gauge cabling
limits DC voltage drop and allows for maximum transfer of current.* You 

must 

tighten your battery

terminals to approximately 4 Newton-meters of torque to create an efficient connection and prevent
excessive heating. Insufficiently tightening terminals could void your PowerVerter's warranty.

*APS models are capable of delivering a much higher wattage output for brief periods of time. Wiring should be configured to
handle this brief high-current draw. Though your APS is a high-efficiency converter of electricity, its rated output capacity is limited
by the length and gauge of the wires running from the battery to the APS

.

Battery Connection (DC Vehicular)

APS systems may be permanently mounted in a car, truck or boat and connected to draw power
from the vehicle's battery.

Note: An APS can ONLY be connected to vehicle batteries with

voltage that matches the APS's Nominal DC Input—12V vehicle batteries to 12V Nominal DC
Input APS systems, etc. (See Specifications).

There are two main ways to make this sort of

200103046 120V APS MV-cabinetEn-Sp 93-1911.qxd  7/2/01  10:18 AM  Page 8

Содержание PowerVerter 93-1911

Страница 1: ...w tripplite com Configuration Connection p 5 10 Features p 10 11 Warranty p 12 Troubleshooting p 13 Safety p 4 Introduction p 2 3 Maintenance Service p 12 Specifications p 14 15 Owner s Manual APS PowerVerter Alternative Power Sources 120V 60 Hz Voltage and Frequency Controlled Peak Power High Efficiency Español pg 16 ...

Страница 2: ...ttery charge decreases Automatic Overload Protection If you overload your APS it will automatically protect itself and your valuable batteries from damage Fast Load Switching Your APS provides an uninterruptible power supply If AC power goes down your APS will switch over to providing battery backup power in 6 milliseconds or less so that your equipment will operate with no interruption Multi Func...

Страница 3: ...oltage Regulation Select models only VR APS models regulate incoming AC power by automatically boosting or cutting the voltage to keep your equipment running through brownouts and overvoltages without draining battery power Load Sharing Select models only Select APS models can be set to limit their own charging functions so they can charge their batteries at the quickest rate possible without over...

Страница 4: ...lways observe proper polarity as bat teries are connected Do not allow objects to contact the two DC input terminals Do not short or bridge these terminals together Serious injury to property or person could result Equipment Connection Warnings Do not use Tripp Lite APS Systems in life support applications where a malfunction or failure of a Tripp Lite APS System could cause failure or significant...

Страница 5: ...when your APS s High AC Voltage Point DIP Switch 2 is set to 135V and its Low AC Voltage Point DIP Switches 3 and 4 are set to 95V However if your APS frequently switches to battery power due to momentary high low line voltage swings that would have little effect on equipment operation you may wish to adjust these settings By raising the High AC Voltage Switch to Battery point and or lowering the ...

Страница 6: ...ROCEDURE 1 Move to Equalize DOWN position for three seconds 2 Move to Reset UP position and leave it there CAUTION Battery charge equalization should only be performed in strict accordance with the battery manufacturer s instructions and specifications CAUTION Do not leave DIP switch 3 in the down position after beginning process Battery Charge Switch Position Reset Up Equalize Down Factory defaul...

Страница 7: ...r an extended period of time See APS Configuration page 5 for more information Selecting Battery Amp Hour Capacity Step 1 Add the Wattage Ratings of your connected equipment to determine the Total Wattage Required Step 2 Divide the Total Wattage Required from Step 1 by the battery voltage to determine the DC Amperes Required Step 3 Multiply the DC Amperes Required from Step 2 by the number of hour...

Страница 8: ...parallel each battery s voltage must be equal to the voltage of your APS s Inverter Nominal Input Voltage see specs Series Battery Connection Refer to Diagram 6 page 33 When using multiple batteries in series all batteries must be equal in voltage and amp hour capacity and the sum of their voltages must be equal to the voltage of your APS s Inverter Nominal Input Voltage see specs 3 Use 2 0 gauge ...

Страница 9: ...n Hardwired Electrical Connections All hardwire models See Diagram 3 p 32 Consult a qualified electrician and follow all applicable electrical codes and requirements HARDWIRE PROCEDURE 1 Remove screws and cover plate from your APS s Hardwire AC electrical box Remove the knockout covers closest to the desired electrical source and to your equipment 2 Thread your wires through strain reliefs and thr...

Страница 10: ...attery charging See Configuration pg 7 to select the optimum settings for these switches Indicator Lights 4 LINE All models This green light will turn continuously ON whenever connected equipment is receiving utility supplied AC power and your APS is set to AUTO REMOTE meaning that it will provide battery backup if utility power fails It will flash intermittently when connected equipment is receiv...

Страница 11: ...g the cord into the APS s AC receptacles 12 Hardwire AC Input Output Terminal Strip Hardwire models only Use the lug screws on these terminals to secure hardwire connections for AC input and output See pages 9 32 for wiring instructions 13 Resettable Circuit Breakers All models These circuit breakers protect your APS against damage due to input or output overload If a breaker trips remove some of ...

Страница 12: ...EIN TRIPP LITE MAKES NO WARRANTIES EXPRESS OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Some states do not permit limitation or exclusion of implied warranties therefore the aforesaid limitation s or exclusion s may not apply to the purchaser EXCEPT AS PROVIDED ABOVE IN NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT INDIRECT SPECIAL INCIDENTAL OR CONSEQUEN...

Страница 13: ...ace cabling APS charger failure Turn APS OFF Wait 1 minute and switch to AUTO REMOTE If automatic shutdown occurs call Tripp Lite Customer Service All APS Indicator Lights are This is normal if the APS is set OFF AC input absent to CHARGE ONLY All APS Indicator Lights are Excessive battery discharge Use an auxiliary charger to raise OFF AC input is present or battery voltage Check external battery...

Страница 14: ...30 A 15 A Maximum Cable Length 2 ft 7 ft Acceptance Volts VDC Selectable Selectable 14 4 V 14 2 V Wet Gel 28 8 V 28 4 V Wet Gel Float Volts VDC w gel 13 3 V 13 6 V 26 6 V 27 2 V Input Voltage AC 120 V 120 V Input Current AC 8 A 8 A LINE VAC OPERATION Minimum Input AC Volts Selectable 75 85 95 or 105 VAC Selectable 75 85 95 or 105 VAC Maximum Input AC Volts Continuous Charger at Maximum Selectable ...

Страница 15: ...nuous 16 7 A 20 A Automatic Transfer Time 4 6 ms 4 6 ms HARDWIRED MODELS Cont APS 2448 APS3636VR Weight 38 0 lbs 56 9 lbs INVERTER Continuous power 20 C 2400 W 3600 W Surge power 5 seconds 4800 W 7200 W Efficiency Full Load 90 89 Minimum DC Fuse Rating 300A 300A DC Input Current Nominal V DC Full Load 56 A 114 A No Load 1 5 A 1 7 A Nominal Input Volts 48 VDC 36 VDC DC Input Voltage Range 40 60 VDC...

Страница 16: ... white 3 4 is the output hot black 3 5 is the ground green 3 6 is the input neutral blue and 3 7 is the input hot brown Refiérase a la sección Conexiones Eléctricas Directas al Circuito página 24 3 1 representa la cubierta 3 2 representa la barra de terminales de 5 posiciones 3 3 representa la terminal neutra de salida blanca 3 4 representa la terminal positiva de salida negra 3 5 representa la te...

Страница 17: ...attery Connection Pg 8 5 1 is the fuse X Your APS s Inverter s Nominal Input Voltage See specs Refiérase a la sección Conexión de Baterías página 23 5 1 representa el fusible X El Voltaje Nominal de Entrada del Inversor del APS Vea las especificaciones See Battery Connection Pg 8 6 1 is the fuse X Your APS s Inverter s Nominal Input Voltage See specs Refiérase a la sección Conexión de Baterías pág...

Страница 18: ...esenta la batería del vehículo 7 4 representa el fusible Advanced 12VDC Vehicular Battery Connection See Pg 8 8 1 is the alternator 8 2 is a battery isolator 8 3 is the vehicle battery ground 8 4 is an auxiliary vehicle battery 8 5 is the vehicle battery 8 6 is the fuse Conexión Avanzada de Baterías de 12V de CD en Vehículos Vea página 23 8 1 representa el alternador 8 2 representa el aislador de ...

Страница 19: ...mente 13 Interruptores de Circuito con Restablecimiento 14 Conector para el Módulo de Control Remoto Todos los modelos 15 Potenciómetro Sensor de Carga Conectada Todos los modelos 9 3 15 6 1 13 5 4 14 8 2 12 9 11 13 15 1 6 5 4 14 8 2 10 9 7 1 Operating Mode Switch All models 2 DIP Switch Group A All models 3 DIP Switch Group B Select models only 4 LINE All models 5 INV Inverting all models 6 LOAD ...

Страница 20: ...36 93 1911 200103046 1111 W 35th Street Chicago IL 60609 USA Customer Support 773 869 1234 www tripplite com ...

Отзывы: