OVERVIEW
PDU Type
Metered
OUTPUT
Output Capacity Details
3.8kW total, 1.9kW per circuit (120V input); 4.0kW total, 2.0kW per circuit (127V input); 3.2kW total, 1.6kW per
circuit (100V input), 40A maximum total, 20A maximum per circuit (Agency de-rated to 32A continuous total, 16A
continuous per circuit)
Frequency compatibility
50 / 60 Hz
Output watts
4800
Output nominal voltage
100-127V nominal, single phase
Overload protection
Two 20A breakers
Outlet quantity / type
32 NEMA 5-15/20R
Outlet Type
NEMA 5-15R, NEMA 5-20R
INPUT
PDU Input Voltage
100; 120; 127
Maximum Input Amps (A)
40
Maximum Input Amps (A) Details
Each circuit supports 20A maximum (Agency de-rated to 16A continuous)
PDU Plug Type
NEMA 5-20P; NEMA L5-20P
Input cord length (ft.)
10
Input cord length (m)
3.05
Phase
Single-Phase
LEDS ALARMS & SWITCHES
Switches
Switchless design
Front panel LEDs
Dual digital current monitoring displays (1 color-coded ammeter for each circuit)
PHYSICAL
Shipping Dimensions (HWD/in)
5 x 71.50 x 2.25
Shipping Dimensions (HWD/cm)
12.7 x 181.61 x 5.72
Shipping weight (lbs)
9.2
Shipping weight (kg)
4.17
Unit Dimensions (HWD/in)
3 x 71.25 x 1.5
Unit Dimensions (HWD/cm)
7.62 x 180.98 x 3.81
Unit weight (lbs)
8.2
Unit weight (kg)
3.72
2 / 4