![Tripp Lite PDUMNH30HV Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/tripp-lite/pdumnh30hv/pdumnh30hv_quick-manual_1166234002.webp)
Supports HTTP, HTTPS, PowerAlert Network Management System, SMTP, SNMPv1, SNMPv2, Telnet, SSH, FTP, DHCP, BOOTP, NTP protocols
Fully compatible with FREE PowerAlert Network Management System / NMS Software
Included cord retention brackets keep vital network equipment plugged in and continuously powered
TAA Compliant Version Available - Order Tripp Lite PDUMNH30HVTAA
Specifications
OVERVIEW
PDU Type
Monitored
OUTPUT
Output Capacity Details
5kW (208V input), 5.8kW (240V input), 4.8kW (200V input); 30A maximum (agency de-rated to 24A continuous)
Frequency compatibility
50 / 60 Hz
Output nominal voltage
200-240V nominal, single phase
Overload protection
Outlets are arranged in two banks of 8 (6 C13, 2 C19 per bank); Each bank is protected by a separate 20A circuit
breaker
Outlet quantity / type
12 C13, 4 C19 outlets
Outlet Type
IEC-C13, IEC-C19
INPUT
PDU Input Voltage
200; 208; 240
Maximum Input Amps (A)
30
Maximum Input Amps (A) Details
Agency de-rated to 24A continuous
PDU Plug Type
NEMA L6-30P
Input cord length (ft.)
12
Input cord length (m)
3.65
Phase
Single-Phase
LEDS ALARMS & SWITCHES
Switches
n/a
Front panel LEDs
Two LEDs with toggle button identify which bank the visual current meter is reporting (bank 1, bank 2 or banks 1 &
2 combined)
PHYSICAL
Shipping Dimensions (HWD/in)
8 x 20.5 x 17
Shipping Dimensions (HWD/cm)
20.3 x 113 x 80.6
Shipping weight (lbs)
16.9
Shipping weight (kg)
7.6