OUTPUT
Output Capacity Details
5kW (208V input), 5.8kW (240V input), 4.8kW (200V input); 30A maximum (agency de-rated to 24A continuous)
Frequency compatibility
50 / 60 Hz
Output nominal voltage
200-240V nominal, single phase
Overload protection
Outlets are arranged in two 9 outlet load banks; each load bank is protected by a separate 20A circuit breaker
Outlet quantity / type
16 C13 and 2 C19 outlets
Outlet Type
IEC-C13, IEC-C19
INPUT
PDU Input Voltage
200; 208; 240
Maximum Input Amps (A)
30
Maximum Input Amps (A) Details
Agency de-rated to 24A continuous
PDU Plug Type
NEMA L6-30P
Input cord length (ft.)
12
Input cord length (m)
3.65
Phase
Single-Phase
LEDS ALARMS & SWITCHES
Switches
n/a
PHYSICAL
Shipping Dimensions (HWD/in)
8 x 20.5 x 17
Shipping Dimensions (HWD/cm)
20.3 x 52.1 x 43.2
Shipping weight (lbs)
16.9
Shipping weight (kg)
7.7
Unit Dimensions (HWD/in)
3.5 x 17.5 x 12.5
Unit Dimensions (HWD/cm)
8.8 x 44.4 x 31.8
Unit weight (lbs)
13.7
Unit weight (kg)
6.2
Material of construction
Steel
Style
Rackmount
Form factors supported
2U rackmount; mounting accessories included
PDU Form Factor
Horizontal (1U, 2U, etc)
ENVIRONMENTAL
2 / 4