background image

DC system voltage
(VDC)

12

Battery recharge rate
(included batteries)

Less than 7.2 hours from 10% to 90%

Replacement battery
cartridge (internal UPS
battery replacement)

RBC52

 (quantity 2)

Battery Access

Battery access door allows hot-swap battery replacement without powering connected equipment off

Typical battery lifespan

3-6 years, depending on usage

VOLTAGE REGULATION

Voltage regulation
description

Line interactive UPS offers a single boost level of brownout correction to maintain usable, computer grade output

Undervoltage correction

Input voltages between 159 and 199 are boosted by 14%

Direct pass through

Input voltages between 200and 266V AC are passed through unchanged

LEDS ALARMS & SWITCHES

LED Indicators

4 LEDs indicate line power, battery power, overload and battery low/replace status

Alarms

Audible alarm indicates power failure conditions, silenceable via alarm cancel switch. Once cancelled, alarm will
resume when approximately 2 minutes of battery operation remain (assuming full load)

Switches

Yes, includes 2 front panel mounted push-button switches for system enable, self-test and alarm cancel functions

SURGE / NOISE SUPPRESSION

EMI / RFI AC noise
suppression

Yes

AC suppression
response time

Instantaneous

Dataline suppression

2-Line Tel/DSL

PHYSICAL

Installation form
factors supported with
included accessories

Tower

Installation form
factors supported with
optional accessories

Wallmount (UPSWM - tower mounting kit)

UPS / Power Module
dimensions in primary
form factor (height x
width x depth / inches)

10.6 x 5.2 x 7.4

UPS / Power Module
dimensions in primary
form factor (height x
width x depth / cm)

26.9 x 13.1 x 18.8

UPS / Power Module
weight (lbs)

25.4

UPS / Power Module
weight (kg)

11.5

UPS Shipping
dimensions (height x
width x depth / inches)

14.1 x 10.4 x 8.2

Отзывы: