Tripp Lite AG-0514 Series Скачать руководство пользователя страница 4

4

• The unit is for indoor use only.
• Do not place the unit near liquid or in an excessively damp environment.
• Do not place the unit directly in the sun or near a source of heat.
• Do not let liquid or foreign objects enter the unit.
• Ground the unit using a 2P+ ground socket.
• This equipment is not suitable for use in locations where children are likely to be present.
• The appliance is intended to be installed and operated by a skilled person (qualified electrical technician).

• 

CAUTION:

 Electrical shock risk due to the multiple supply connections. 

• Use tools with insulated handles.
• Do not touch the AC mains terminals or plug. Before working on the appliance, check for hazardous voltage 

between all AC mains terminals, both input plug and appliance inlet.

• When installing the unit, ensure the sum of the leakage currents of the unit and the devices it supplies does not 

exceed 3.5mA.

UPS Location Warnings

Temperature

Operating

0°C to 40°C (32°F to 104°F)

Storage

-20°C to 50°C (-4°F to 122°F)

Elevation

Operating

0 m to 3000 m (0 ft. to 9843 ft.): Normal Operation

Humidity

0% to 95% Relative Humidity, Non-Condensing

IP Rating

IP20

Inspection

Remove the unit from the shipping package and inspect it for damage that may have occurred during transport. Notify the 
carrier and your dealer if any damage is found.

Connect to the Wall Outlet

Plug the Bypass PDU main input cord to an unprotected AC outlet. This connection is labeled MAIN INPUT on the PDU. The 
MAIN POWER LED will illuminate when mains input is available.

Note:

 For models PDUBHV101U and PDUBHV201U, you may need to use your UPS system’s power cable to connect the Bypass PDU to 

the AC power source.

4. Installation

CAUTION!

 

Save these instructions. To safely operate this unit, read and follow all instructions carefully. Read 

this manual thoroughly before attempting to unpack, install or operate. Retain this manual for further 

reference.

3. Important Safety Warnings

Содержание AG-0514 Series

Страница 1: ...er AG 0515 PDUBHV101U Series Number AG 0516 PDUBHV201U Series Number AG 0517 PDUBHV20B Series Number AG 0518 PDUBHV20D Series Number AG 0519 WARRANTY REGISTRATION Register your product today and be au...

Страница 2: ...itting scheduled maintenance or UPS replacement without interruption of connected equipment The optional ECO Switching feature enables power savings by automatically powering off Controllable Output R...

Страница 3: ...MAL for standard protected UPS operation Set switch to BYPASS during UPS replacement 6 Mains AC Inlet Cord Connect AC input cord to any compatible mains power source This connection is labeled MAIN PO...

Страница 4: ...does not exceed 3 5mA UPS Location Warnings Temperature Operating 0 C to 40 C 32 F to 104 F Storage 20 C to 50 C 4 F to 122 F Elevation Operating 0 m to 3000 m 0 ft to 9843 ft Normal Operation Humidit...

Страница 5: ...When this switch is set to DISABLE all outlets will operate in an always on capacity In this configuration protected equipment can be connected to any outlet whether it is part of the Master or Contr...

Страница 6: ...nsfer to UPS Protection After maintenance service is complete ensure the UPS operation is normal Reconnect the UPS to the unit by following the steps in section 4 Installation Verify the Main Power LE...

Страница 7: ...Position Normal Bypass Normal Bypass Normal Bypass Normal Bypass Normal Bypass Normal Bypass Mains AC Input LED Green Green Off Off Green Green Off Off Green Green Off Off Bypass Mode LED Off Yellow...

Страница 8: ...ny interference received including interference that may cause undesired operation Note This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part...

Страница 9: ...ci n para Mantenimiento Modelos PDUB151U N mero de Serie AG 0514 PDUB201U N mero de Serie AG 0515 PDUBHV101U N mero de Serie AG 0516 PDUBHV201U N mero de Serie AG 0517 PDUBHV20B N mero de Serie AG 051...

Страница 10: ...rupo de Tomacorrientes Controlables cuando el dispositivo conectado al tomacorrientes maestro est apagado o entra en un modo de bajo consumo de energ a Instalaci n de la Unidad en Rack o Pared El m du...

Страница 11: ...UPS Coloque el switch en BYPASS durante el reemplazo del UPS 6 Entrada y Cable de CA de la Red P blica Conecte el cable de alimentaci n de CA a cualquier fuente compatible de alimentaci n de la red p...

Страница 12: ...n del UPS Temperatura Operaci n 0 C a 40 C 32 F a 104 F Almacenamien to 20 C a 50 C 4 F a 122 F Elevaci n Operaci n 0 m a 3000 m 0 pies a 9843 pies Operaci n Normal Humedad De 0 a 95 de Humedad Relat...

Страница 13: ...h est configurado para DESACTIVARSE todos los tomacorrientes funcionar n en una capacidad siempre encendida En esta configuraci n el equipo protegido puede conectarse a cualquier tomacorriente ya sea...

Страница 14: ...del UPS Despu s de completar el servicio de mantenimiento aseg rese de que la operaci n del UPS sea normal Vuelva a conectar el UPS a la unidad siguiendo los pasos en la secci n 4 Instalaci n Verifiq...

Страница 15: ...vaci n Normal Derivaci n Normal Derivaci n Normal Derivaci n LED de Entrada de CA de la Red P blica Verde Verde Apagado Apagado Verde Verde Apagado Apagado Verde Verde Apagado Apagado LED de Modo en D...

Страница 16: ...N CASO TRIPP LITE ASUMIR RESPONSABILIDAD POR DA OS DIRECTOS INDIRECTOS ESPECIALES INCIDENTALES O EMERGENTES QUE SURJAN COMO RESULTADO DEL USO DE ESTE PRODUCTO INCLUSO SI SE ADVIERTE SOBRE LA POSIBILID...

Страница 17: ...r de d rivation de maintenance Mod les PDUB151U num ro de s rie AG 0514 PDUB201U num ro de s rie AG 0515 PDUBHV101U num ro de s rie AG 0516 PDUBHV201U num ro de s rie AG 0517 PDUBHV20B num ro de s rie...

Страница 18: ...utomatiquement hors tension les prises du groupe de prises de sortie contr lables lorsque le dispositif connect la prise ma tre est mis hors tension ou passe en mode faible consommation d nergie Monte...

Страница 19: ...tionnement prot g standard de l onduleur Configurer le commutateur BYPASS d rivation pendant le remplacement de l onduleur 6 Entr e cordon CA du secteur Raccorder le cordon d entr e CA une source d al...

Страница 20: ...acement de l onduleur Temp rature Fonctionnement 0 40 C 32 104 F Entreposage 20 50 C 4 122 F l vation Fonctionnement 0 3 000 m 0 9 843 pi fonctionnement normal Humidit 0 95 d humidit relative sans con...

Страница 21: ...de la charge ECO Lorsque ce commutateur est configur DISABLE d sactiver toutes les prises fonctionneront selon une capacit toujours disponible Dans cette configuration l quipement prot g peut tre con...

Страница 22: ...ur Une fois le service d entretien termin s assurer que l onduleur fonctionne normalement Reconnecter l onduleur l appareil en suivant les tapes de la section 4 Installation V rifier que le voyant DEL...

Страница 23: ...Vert Vert Off hors tension Off hors tension Vert Vert Off hors tension Off hors tension Vert Vert Off hors tension Off hors tension Voyant DEL du mode de d rivation Off hors tension Jaune Off hors ten...

Страница 24: ...ipp Lite ne pourra tre tenu responsable de co ts tels que perte de b n fices ou de recettes perte de mat riel impossibilit d utilisation du mat riel perte de logiciel perte de donn es frais de produit...

Страница 25: ...32 c o PDU PDUB151U AG 0514 PDUB201U AG 0515 PDUBHV101U AG 0516 PDUBHV201U AG 0517 PDUBHV20B AG 0518 PDUBHV20D AG 0519 1111W 35th Street Chicago IL 60609 USA tripplite com support 2020Tripp Lite Engli...

Страница 26: ...19 1 2 1 2 K PDUBHV101U PDUB151U PDUBHV201U PDUB201U PDUBHV20B PDUBHV20D B 2 8 C 1 D 5 3 4 6 A B 2 8 C 7 1 D 5 3 4 6 A 7 B 2 8 C 1 D 5 3 4 6 A B 2 8 C 1 D 5 3 4 6 A B 2 8 C 1 D 5 3 4 6 A B 2 8 C 1 D...

Страница 27: ...27 1 MASTER PDU 2 CONTROLLABLE GROUP PDU 3 TO UPS OUTPUT PDU 4 TO UPS INPUT PDU 5 NORMAL BYPASS 6 MAIN POWER PDU 7 8 ECO DISABLE ENABLE ECO A 6 B 2 C 1 D BYPASS 2 K...

Страница 28: ...28 2 3 5 0 40 C O 20 50 C 0 3000 0 95 IP IP20 PDU MAIN INPUT PDU MAIN POWER PDUBHV101U PDUBHV201U PDU 4 3...

Страница 29: ...29 1 4 To UPS Input PDU 2 PDU To UPS Output PDU PDUBHV101U PDUBHV201U ECO DISABLE ECO ENABLE 20 1 4...

Страница 30: ...30 4 Main Power NORMAL BYPASS Bypass Mode 4 Main Power BYPASS NORMAL ECO ECO Mode ECO ENABLE 20 Controllable Receptacle Group ECO Mode ECO DISABLE Controllable Receptacle Group...

Страница 31: ...31 ECO ECO Input Bypass Mode Controllable Receptacle Group Master 4...

Страница 32: ...zation RMA TRIPP LITE TRIPP LITE c TRIPP LIT a p TRIPP LITE OMME ECK E B e e e c e TRIPP LIT C C C C RI LI W Tripp Lite E o e o W Tripp Lite o c o ca H ripp Lite B c o e x 5 1111W 35th Street Chicago...

Отзывы: