background image

13

9. DC Input Terminals (All models):

The terminals’ lug screws secure the wires leading from

your external battery or battery system. Your battery or battery system must provide your
APS with proper DC voltage and your equipment with an adequate amp hour capacity. See
Battery Selection section, pg. 8 for more information.

10. AC Receptacles: IEC 320 (Corded models only):

These IEC receptacles allow you to 

connect equipment that would normally be plugged into a utility outlet. For other plug 
configurations, use an adapter that provides a connection to ground.

11. AC Input: IEC 320 (Corded models only):

This IEC receptacle should be connected to a

dedicated 15 Amp AC utility outlet via an adapter cord that provides a connection to ground.
A detachable IEC to 5-15 cord is provided for this purpose. DO NOT plug the cord into the
APS’s AC receptacles.

12. Hardwire AC Input/Output Terminal Strip (Hardwire models only):

Use the lug screws

on these terminals to secure hardwire connections for AC input and output. See pages 10 & 36
for wiring instructions.

13. Resettable Circuit Breakers (All models):

These circuit breakers protect your APS against

damage due to input or output overload. If a breaker trips, remove some of the load on the
APS to prevent overload, then wait 1 minute to allow components to cool before resetting
the circuit breaker.

14. Remote Module Connector (All models):

The front panel of all models has an RJ45

receptacle for use with the optional remote module. (Module is included with all VR 
models.) See the installation instructions packed with the remote module.

15. Load Sense Potentiometer (All models):

In order to save battery power, the APS’s inverter

automatically shuts off when no load is connected. When the unit detects a load, it 
automatically turns the inverter on. Users may choose the minimum load the APS will detect
by adjusting the Load Sense Potentiometer. Using a small tool, turn the potentiometer 
clockwise to lower the minimum load that will be detected, causing the inverter to turn on
for smaller loads. When the potentiometer is turned fully clockwise, the inverter will operate
even when there is no load. Turn the potentiometer counterclockwise to increase the minimum
load that will be detected, causing the inverter to stay off until the new minimum load is
reached. The factory setting for the potentiometer is fully clockwise, but in areas with 
frequent power interruptions, the potentiometer should be adjusted counterclockwise until
the inverter is only in operation when the APS’s load is in use. 

Switches, Indicator Lights & Other Features

continued

Other Features

200106010 230V APS Owners Manual.qxd  1/3/02  5:18 PM  Page 13

Содержание 93-2007 (200106010)

Страница 1: ...Instructions 4 Configuration Connection 5 Features 11 Maintenance and Service 14 PowerVerter is a registered trademark of Tripp Lite All rights reserved APS PowerVerter Alternative Power Sources 230V...

Страница 2: ...attery charge decreases Automatic Overload Protection If you overload your APS it will automatically protect itself and your valuable batteries from damage Fast Load Switching Your APS provides an uni...

Страница 3: ...osting or cutting the voltage to keep your equipment running through brownouts and overvoltages without draining battery power Load Sharing Select models only Select APS models can be set to limit the...

Страница 4: ...al battery connection Always observe proper polarity as batteries are connected Do not allow objects to contact the two DC input terminals Do not short or bridge these terminals together Serious injur...

Страница 5: ...To Battery Point DIP Switch 2 Group A Voltage Switch Position 264V Up 259V Down Select Low AC Voltage Switch To Battery Point DIP Switches 4 Group A 3 Group A Voltage Switch Postion 201V 4 Up 3 Up 182...

Страница 6: ...heir AC load and charger power within their circuit breakers rating This charger limiting function has four settings allowing you to choose less charger limiting for APS configurations with higher rat...

Страница 7: ...mit Battery Charger DIP Switch 4 Group B APSINT1524 only To prevent overheating smaller batteries the charger on this UPS system is initially set to deliver only a fraction of its maximum power rating...

Страница 8: ...Hour ratings of batteries are usually given for a 20 hour discharge rate Actual Amp Hour capacities are less when batteries are discharged at faster rates batteries discharged in 55 minutes provide o...

Страница 9: ...You must tighten your battery terminals to approximately 4 Newton meters of torque to create an efficient connection and prevent excessive heating Insufficiently tightening terminals could void your P...

Страница 10: ...ad your wires through strain reliefs and through the knockouts 3 Connect all input and output ground wires to the input output ground tie point 4 Connect the incoming hot wire to the input hot brown t...

Страница 11: ...has shut down due to overload or overheating See Diagrams 9a and 9b p 39 and 40 to locate the following switches indicator lights and other features 1 Operating Mode Switch All models This switch sele...

Страница 12: ...a severe overload or overheating If this happens turn Operating Mode Switch OFF Remove the overload and let the unit cool You may then turn the APS ON after it cools 7 CUT BOOST VRI models only These...

Страница 13: ...ove some of the load on the APS to prevent overload then wait 1 minute to allow components to cool before resetting the circuit breaker 14 Remote Module Connector All models The front panel of all mod...

Страница 14: ...Tripp Lite service center with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase This warranty does not...

Страница 15: ...e cabling APS charger failure Turn APS OFF Wait 1 minute and switch to AUTO REMOTE If automatic shutdown occurs call Tripp Lite Customer Service All APS Indicator Lights are This is normal if the APS...

Страница 16: ...gth 2 ft Acceptance Volts VDC Selectable 14 4 V 14 2 V Wet Gel Float Volts VDC w gel 13 3 V 13 6 V Input Voltage AC 230 V Input Current AC 3 3 A LINE VAC OPERATION Minimum Input AC Volts Selectable 14...

Страница 17: ...WIRED MODELS Cont APSINT2424 APSVRI3636 Weight 18 5 Kg 25 6 Kg INVERTER Continuous power 20 C 2400 W 3600 W Surge power 5 seconds 4800 W 7200 W Efficiency Full Load 89 88 Minimum DC Fuse Rating 220A 1...

Страница 18: ...ls 3 3 is the output neutral white 3 4 is the output hot black 3 5 is the input output ground tie point 3 6 is the input neutral blue and 3 7 is the input hot brown Refi rase a la secci n Conexiones E...

Страница 19: ...Inverter s Nominal Input Voltage See specs Refi rase a la secci n Conexi n de Bater as p gina 26 5 1 representa el fusible X El Voltaje Nominal de Entrada del Inversor del APS Vea las especificaciones...

Страница 20: ...Advanced 12VDC Vehicular Battery Connection See Pg 9 8 1 is the alternator 8 2 is a battery isolator 8 3 is the vehicle battery ground 8 4 is an auxiliary vehicle battery 8 5 is the vehicle battery 8...

Страница 21: ...Interruptores DIP Todos los modelos 3 Grupo B de Interruptores DIP Modelos selectos nicamente 4 LINE L nea Todos los modelos 5 INV Inversor Todos los modelos 6 LOAD Carga Conectada 8 BATTERY HI MED L...

Страница 22: ...Todos los modelos 2 Grupo A de Interruptores DIP Todos los modelos 3 Grupo B de Interruptores DIP Modelos selectos nicamente 4 LINE L nea Todos los modelos 5 INV Inversor Todos los modelos 6 LOAD Car...

Отзывы: