Trinity Lx

 

 

Plumbing and Wiring Instructions                                     Water Heater Applications                                                                            

 

 

 

 

1.0  INTRODUCTION 

 

 

Water  Heater  Applications

  –  These  instructions  apply  to  plumbing  and  wiring  of 

Trinity  Lx200-800  units  operating  as  water  heaters  and  covers  instructions  that  are 

specific to water heater applications.  When these units are installed and operated as a boiler, and not used for 
direct fired potable or process water heating, refer to "Appendix B - Boiler Applications: Plumbing & Wiring 
Instructions".  See Table 1-1 for a list of Application Manuals. 

 

Terminology

  –  The  following  terms  in  the  instruction  manuals  are  used  to  differentiate  between  which 

instructions are common-to-both and which are appliance-specific. The term "

APPLIANCE

" applies to both 

kinds of applications (boiler and water heater) and is used when conveying instructions which are common-to-
both. The term "

BOILER

" or "

WATER HEATER

" is used when conveying instructions which are appliance-

specific or specific to one or the other, but not both. 

 

 

Table 1-1  Instruction Manuals 

Appliance 

Model No. 

Common-to-Both 

(Trinity Lx Series) 

Appliance-Specific 

(Application Based) 

Boiler 

Lx150-800 

Installation  
and Operation  
Instructions 

Appendix A -  
Controller and 
Touchscreen Display 
Instructions

 

Appendix B - 
Boiler Applications: 
Plumbing and  
Wiring Instructions 

n/a 

Water 
Heater 

Lx200-800 

Installation  
and Operation 
Instructions 

Appendix A - 
Controller and 
Touchscreen Display 
Instructions 

n/a 

Appendix C - Water 
Heating Applications:  
Plumbing and Wiring 
Instructions 

Notes 

1   

The conversion kit is required to convert the Appliance so it will safely operate with Propane Gas (Lx150-400).  

2   

Do not convert the Lx600-800 to Propane (LP). Operate with Natural Gas only.  

 

 

General Installation Requirements 

The  installation  of  your  NTI  Trinity  gas  water  heater  must  conform  to  the  requirements  of  this  manual,  your 
local  authority,  and  the  National  Fuel  Gas  Code  ANSI  Z223.1  and  or  CAN/CGA  B149  Installation  Codes. 
Where required by the Authority, the installation must conform to the standard for “Controls and Safety Devices 
for Automatically Fired Boilers ANSI/ASME CSD-1. 

 

This  document  pertains  to  the  correct  installation  and  operation  of  NTI  Trinity  water  heaters  models  Lx200, 
Lx300, Lx400, Lx500, Lx600, Lx700 and Lx800. The instructions detailed in this document supersede any and 
all previous instructions provided by NTI, written or otherwise. Each unit is provided with various manuals and 
a Natural to LP Conversion Kit for applicable models. See notes and list of Instruction Manuals in Table 1-1.  

 

Natural  Gas  Only

  -  The  Lx600-800  are  not  approved  for  operation  with  Propane  (LP 

Gas). Failure to comply with instructions will result in damage, serious injury or death.  

 

Be  Informed

  -  Read  and  understand  this  entire  document  prior  to  proceeding  with  the 

installation of the Trinity Lx water heater.  Failure to follow the instructions outlined in 

this document will result in property damage, serious injury or death. 

 

Service

 - Failure to have the water heater properly service and inspect on a regular basis 

by a qualified service technician may result in property damage, serious injury or death.

 

 

Water stored at temperatures between 68-113ºF is ideal for bacteria growth (see Table 1-
1);  therefore  consuming  water  from  a  Water  Heater  is  not  recommended.    Consuming 
water from a Water Heater may cause illness or death. 

 

Содержание Lx200-800

Страница 1: ... 18 HAZARD SYMBOLS AND DEFINITIONS Danger Sign Indicates a hazardous situation which if not avoided will result in serious injury or death Warning Sign Indicates a hazardous situation which if not avoided could result in serious injury or death Caution Sign plus Safety Alert Symbol Indicates a hazardous situation which if not avoided could result in minor or moderate injury Caution Sign without Sa...

Страница 2: ...t will safely operate with Propane Gas Lx150 400 2 Do not convert the Lx600 800 to Propane LP Operate with Natural Gas only General Installation Requirements The installation of your NTI Trinity gas water heater must conform to the requirements of this manual your local authority and the National Fuel Gas Code ANSI Z223 1 and or CAN CGA B149 Installation Codes Where required by the Authority the i...

Страница 3: ...ing diagram s for a typical installation Definitions of Potable Water Systems Each potable water system described below is meant to be used with a storage tank refer to Table 1 1 Water Potable Heating Only refers to an open potable water system dedicated to providing domestic hot water and is not intended for space heating Combination Space Heating refers to an open potable water system where the ...

Страница 4: ...llness or death High Risk Application Combination space heating systems can present a significantly higher risk of developing Legionella than dedicated domestic hot water systems especially during non heating seasons or low temperature water applications Using higher temperature tank water routinely maintaining your water system and having your water tested annually are considered good practice wh...

Страница 5: ...46o C 115o F shall be equipped with a thermostatic mixing valve on the hot water outlet to reduce potential scald hazards Clean aerators and nozzles on water fixtures on a regular basis to reduce scale build up Clean storage tanks and remove sediment Flush storage tanks and piping systems regularly for 10 30 minutes at high water temperatures depending on guidelines used to rid the system of sedim...

Страница 6: ...ater Heater Plumbing Pressure Relief Valve All Trinity Lx models dual certified as either a boiler or a water heater Lx200 800 have an additional factory supplied pressure relief valve For water heater installations use the higher pressure relief value along with the corresponding higher pressure gauge See Table 2 1 for pressure relief valve sizes The pressure relief valve must be installed at the...

Страница 7: ...Heater Piping Pressure Relief Valve discharge to floor drain Outlet To Water Heater and system plumbing Refer to piping diagrams Mandatory Safety Flow Switch Pressure Gauge Pressure Relief Valve Inlet Pressure Relief Valve discharge to floor drain Near Water Heater tees and fittings Safety Flow Switch Pressure Relief Valve Pressure Gauge Trimmable paddle Outlet Inlet ...

Страница 8: ...ger that requires a minimum rate of forced water circulation any time the burner is operating See Table 2 3 for minimum flow rates To ensure the minimum flow rate is attained the water heater must be installed with a safety flow switch see Figure 2 2 for suggested plumbing diagram A properly installed system will as a minimum include the major components in Table 2 3 Table 2 3 System Major Compone...

Страница 9: ...xpansion tank must be suitable for use with potable water and be sized in accordance with the water volume of the system as well as the firing rate of the appliance The expansion tank must be installed downstream of any backflow prevention device used to control system thermal expansion See examples in Figure 2 3 Ensure the expansion tank cannot become isolated from the water heater anytime the sy...

Страница 10: ...r heater application the thermostat aquastat in the storage tank is connected to the water heaters low voltage terminal strip and is used to trigger a DHW demand by completing the DHW to Sensor COM circuit See Table 3 2 for more details Figures 2 2 is an example of a plumbing configuration for stand alone water heaters using a single system circulator This schematic also illustrates an optional lo...

Страница 11: ...Water Heater Applications Plumbing and Wiring Instructions Trinity Lx 11 Figure 2 2 All Models Stand Alone Water Heater Plumbing Configuration ...

Страница 12: ...a water heater application at the Master boiler set the applicable sensor input to Unconfigured as follows Configure Sensor Configuration S10 J10 7 sensor S5 J8 11 sensor for Lx500 800 models Modbus Address assign a unique MB2 Modbus Address to each water heater in the cascade Access the MB2 Modbus Address setting via the System Identification Access menu as follows Configure System Identification...

Страница 13: ...ipe Size Pipe Size Pipe Size Pipe Size Pipe Size Pipe Size 2 2 2 1 2 3 3 4 4 4 3 2 1 2 3 4 4 4 4 4 4 3 4 4 4 4 5 5 5 3 4 4 4 5 5 5 6 4 4 4 5 5 5 5 7 4 4 5 5 5 6 6 8 4 4 5 5 5 6 6 All Water Heater piping in Multiple Water Heater Applications must be sized based on Table 2 5 in accordance with the number of units the piping supports All water heater circulators Pump B must be sized according to Tabl...

Страница 14: ...Trinity Lx Plumbing and Wiring Instructions Water Heater Applications 14 Figure 2 3 All Models Multiple Water Heater Lead Lag Plumbing Configuration ...

Страница 15: ...ses to protect 120VAC system components The fast acting fuses are located on the front of the control panel box and can be easily accessed from the outside of the control panel Lx200 400 Control Panel Fuse A Protects the blower spark generator and PUMP B output circuits Fuse B Protects PUMP A and C output circuits Lx500 800 Control Panel Fuse A Protects the 120VAC circuits within the appliance Pum...

Страница 16: ...h to break line voltage to the appliance PUMP A 2 Not used PUMP B 3 DHW Demand Output to the Water Heater Circulator powered during tank demand PUMP C 4 Not used L2 Neutral 5 120VAC Common Location for connecting neutral of the power supply and circulator 6 Ground 7 120VAC Ground Location for connecting ground of the power supply and circulator 8 No Conn 9 Factory Wiring This terminal is used only...

Страница 17: ...f the power supply Note most installation codes require the installation of a service switch to break line voltage to the appliance L2 Neutral 2 120VAC Common Location for connecting neutral of the power supply and circulator Ground 3 120VAC Ground Location for connecting ground of the power supply and circulator Non Powered Dry Contacts PUMP A 4 Not used 5 PUMP B 6 DHW Demand Dry Contact for Wate...

Страница 18: ... Tank Demand Input requiring closure of terminals 7 and 10 to initiate a demand for DHW Switch made via isolated end switch dry contact from the storage tank thermostat Aquastat Or optional Tank Sensor P N 84632 see Appendix A NOTICE Tank Sensor when operating in a cascade system the water heater controls do not support the use of a tank sensor a tank thermostat switch must be used OD SENSOR 8 Out...

Страница 19: ...at Or optional Tank Sensor P N 84632 see Appendix A OD SYS SENSOR 12 Outdoor Temperature Sensor Not applicable for Water Heater Applications System Water Temperature Not applicable for Water Heater Applications TOD 13 Time of Day Night Time Setback Input requiring closure of terminals 13 and 14 to initiate TOD setback setting Switch is made using an isolated end switch dry contact using a timer BA...

Страница 20: ...minals to any other terminal other than terminals 4 5 and or 6 LIM CH1 and CH2 LL via an isolated end switch dry contact Failure to follow these instructions may damage the unit Fuse 24VAC Trinity Lx150 400 models are equipped with a blade style 2 Amp fuse to protect the internal transformer located within the slide out control panel box Figure 3 2 All Models Lx150 400 shown Low Voltage Field Wiri...

Страница 21: ...Water Heater Applications Plumbing and Wiring Instructions Trinity Lx 21 NOTES ...

Страница 22: ...Trinity Lx Plumbing and Wiring Instructions Water Heater Applications 22 NOTES ...

Страница 23: ...NOTES ...

Страница 24: ...NY Thermal Inc 65 Drury Cove Road Saint John NB E2H 2Z8 Canada Technical Assistance 1 800 688 2575 Website www nythermal com Fax 1 506 432 1135 ...

Отзывы: