background image

TRILUX GmbH & Co. KG

Postfach 1960 · D-59753 Arnsberg

Tel. +49 (0) 29 32.301-0

Fax +49 (0) 29 32.301-375

[email protected] ·  www.trilux.de

Mounting instructions

 

 

Mounting instructions 

 

SYMBOL I 450

 

 

 

Pole luminaire

 

230V ~ , 50Hz

 

 

  

IP 54

 

TRILUX GmbH+Co KG 

Postfach 1960 . D-59753 Arnsberg 

Tel.  +49 (0)2932.301-0 

Fax  +49 (0)2932.301-375 

[email protected]

     

www.trilux.de

 

 

Description 

 

 

 

 

 

ca. kg 

Symbol I 450/1x70HIE L···   

71,4 

Symbol I 450/1x100HIE L···

   

72,0 

Symbol I 450/1x150HIE L···

   

72,0 

Symbol I 450/1x70HSE-E L···

 

71,4 

Symbol I 450/1x150HSE L···

  

69,0 

Symbol I 450/2xTCL36 L···

   

72,4 

 

Symbol I 450-M2/1x70HIE

 

L··· 

84,2 

Symbol I 450-M2/1x100HIE

 

L··· 

84,2 

Symbol I 450-M2/1x150HIE

 

L··· 

84,2 

Symbol I 450-M2/1x70HSE-E

 

L··· 

84,2 

Symbol I 450-M2/1x150HSE

 

L··· 

82,8 

Symbol I 450-M2/2xTCL36

 

L··· 

86,2 

 

Lamp designation system in accordance with ZVEI 

Observe operating instructions of lamp manufacturer. 

 

 

Technical data 

Fixed flexible connection cable (pole cap) 

  max. 1 x 5G 4mm² 

Fixed flexible connection cable (head)   

           1 x 3G 1mm² 

                                                                               heat resistant t>130°C 

 

 

 

 

Saftety class 

 

 

 I 

Lighting point height  

 

4400 mm 

 

Luminaire made of  aluminium, cast aluminium, stainless steel, tempered 

safety glass, reflector made of pure aluminium.  

Pole made of hot-dip galvanized steel.  

 

 

Attention 

The  installation  and  assembly  have  to  be  performed  by  a  skilled 

electrician.  Installation  and  operation  have  to  comply  with  the 

national safety regulations.  

The enclosed 

General Instructions

 have to be absolutely observed. 

 

Luminaire is only allowed to be operated with its complete protective 

cover.  

Luminaire is also suitable for indoor areas (t

a

=25°C).  

Luminaire is suitable for looping-through connection only in combination 

with customer supplied cable box. 

 

 

Installation 

 

Pole 

Open access door (1) and fasten the customer-provided cable box to the 

C-channel (3). Lead fixed connection cable through cable entry of the pole 

up to access door area. The insertion depth of the pole (2) is 1000mm.  

 

Pole cap 

Lead customer-provided fixe flexible connection cable (l ~ 4.5 mts) from 

access door area up to terminal (4). Connect cable to terminal and secure 

with cable clip (5).  

Connect fixed flexible connection cable(s) for luminaire head(s) to 

terminal (4) of pole cap and fixate with cable clip(s) (7) (see figure). Attach 

push-on contact(s) to protection conductor(s) and connect to blade 

terminal (6).  

 

 

 

 

 

Note:  

The jackets of the connection cables have to be removed less 

than 30mm. The wires must be skinned max. 7 mm. Wires 

have to be tied up by the supplied cable fixers in a distance 

of 10-15mm to the terminal (see figure). 

 

 

Lead connection cable(s) down through the pole and feed through 

cable entry(ies) (9) using supplied cable gland(s). Mount pole cap 

on pole and secure with setscrew (10).

  

 

Cantilever 

Undo screws (25) and washers (26) to open connection part (13) 

of cantilever (14). Lead connection cable(s) through the 

cantilever. Align connection part of cantilever to the pole and 

tighten screws and washers with a torque of 8Nm. Secure with set 

screw.  

 

Luminaire head 

Undo fast-locks (24) and open cover (23). Undo screws (21) and 

washers (22). Take the electrical equipment (20) out of the 

housing (16).  

Feed connection cable(s) through cable gland(s) (15) into housing 

(max 300mm). Tighten cable gland with a torque of 6,25Nm. 

Connect housing with cantilever using screws (18) and washers 

(17). Tighten screws with a torque of 8Nm.  

Connect cable(s) to plug connector (19). Reassemble luminaire in 

reverse order. Insert lamp.

 

Close cover and rotate fast-locks 

clockwise to lock.  

 

 

Adjustment of reflector position 

The delivery position is wide beam. Unfasten screws (12) to 

change to the narrow beam position. Rotate the two reflectors 

inwards to the preassembled screws. Fix the reflector with screws 

in the new position.  

 

 

Insertion of lamp  -  Relamping 

Undo fast-locks (24) and open cover (23). Insert / replace lamp. 

Close the luminaire and and tighten fast-locks.  

 

03/09 Subject to technical alterations   

 

        10044802 

 

 

 

 

 

2 / 3 

IP 54 

Pole luminaire

230V ~,50Hz

10044802 / I 11  

2 / 3

Symbol I 450

Отзывы: