12
PRELIMINARY: TR-FFT Fire Fighter’s Telephone Manual — LS10309-001TR-E:A 04/28/2021
Section 3: Installation
3.1 Mounting the Cabinet
Read the Environmental Specifications in Section 2.1 before you mount the TR-FFT cabinet. This will ensure that you select a
suitable location.
The TR-FFT cabinet can be surface or flush-mounted. Do NOT flush-mount in a wall designed as a fire break.
3.1.1 Surface Mounting
The Cabinet can be mounted on the wall surface. To secure the cabinet to the wall, use the mounting holes in the back of the
cabinet (see Figure 3.1 on page 12).
1. Insert two screws level with each other, spacing 14" (.36cm) apart for the top cabinet key-shaped holes. See Figure 3.1 on
2. Hang the cabinet onto the two screws. Tighten the screws.
3. Insert the two screws into the two bottom mounting holes and tighten the screws to secure them to the cabinet.
Figure 3.1 Cabinet Mounting Holes
3.1.2 Flush Mounting
This Section describes how to flush-mount the cabinet into a wall. To recess mount the cabinet, you will need to have the
optional Trim Ring P/N VIP-TR (ordered separately).
To recess mount the cabinet, refer to the following these steps.
1. Remove the cabinet door and the dead front panel.
2. Cut a recess hole 20-1/4” W x 26-3/4” H (51.44 cm W x 67.95 cm H). There should be 1.5" to 1.75" (3.8cm to 4.45cm) of
cabinet space extending from the wall.
This space should be measured from either the top edge or bottom edge to the exterior side of the sheet rock. (See Figure
3.2).
3. To mount the cabinet to the wall studs, insert a screw through the cabinet’s side mounting holes into the wall stud.
Bottom Mounting Holes
20" (6.09m)
26-½”
Key Shaped Holes
8.05m
NOTE:
Do not insert the cabinet deeper than recommended in Step 2. If the cabinet is mounted to deep, you will not be able
to re-attach the door assembly.