![TRIGA TR-B300-6 Скачать руководство пользователя страница 2](http://html.mh-extra.com/html/triga/tr-b300-6/tr-b300-6_installation-and-maintenance-instructions_1162361002.webp)
Triga™ is a trademark of TRIGA Life Safety Systems, LLC. System Sensor® is a registered trademark of Honeywell International, Inc.
FIGURE 5A. ACTIVATE TAMPER-RESIST FEATURE
PLASTIC LEVER
BREAK TAB AT DOTTED LINE BY
TWISTING TOWARD CENTER OF BASE
USE SMALL-BLADED SCREWDRIVER TO PUSH
PLASTIC LEVER IN DIRECTION OF ARROW
C0130-00
FIGURE 5B. DETECTOR REMOVAL
PLASTIC LEVER
BREAK TAB AT DOTTED LINE BY
TWISTING TOWARD CENTER OF BASE
USE SMALL-BLADED SCREWDRIVER TO PUSH
PLASTIC LEVER IN DIRECTION OF ARROW
C0130-00
FIGURE 6. CONNECTION TO REMOTE ANNUNCIATOR TERMINAL
STRIPPED WIRE
WIRE WITH SPADE LUG
C0116-00
TAMPER-RESIST FEATURE
NOTE: Do not use the tamper-resist feature if a removal tool will be used.
The detector base includes a tamper-resist feature that prevents removal of the
detector without using a small screwdriver or similar tool.
To activate this feature, use needle-nose pliers to break the tab on the detector
base as shown in Figure 5A. Then, install the detector.
To remove the detector from the base once the tamper-resist feature has been
activated, remove the decorative ring by rotating it in either direction and
pulling it away from the base. Then, insert a small screwdriver into the notch,
as indicated in Figure 5B, and press the plastic lever toward the mounting
surface before rotating the detector counterclockwise for removal.
The tamper-resist feature can be defeated by breaking and removing the plas-
tic lever from the base. However, this prevents the feature from being used
again.
REMOTE ANNUNCIATOR (TR-RA100Z)
Connect the remote annunciator between terminals 1 and 3 using the spade
lug terminal included. The spade lug terminal is connected to the base termi-
nal as shown in Figure 6.
It is not acceptable to have three stripped wires under the same wiring termi-
nal unless they are separated by a washer or equivalent means. The spade lug
supplied with the model TR-RA100Z is considered an equivalent means. See
Figure 3 for proper installation.
FIGURE 3. TYPICAL WIRING DIAGRAM FOR 2-WIRE LOOP
2
3
1
2
3
3
1
2
1
(–)
(+)
+
-
UL
LISTED COM
PA
TIBLE
CONTROL
P
ANEL
CAUTION: DO NOT LOOP WIRE
UNDER TERMINAL 1 OR 2.
BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
CLASS A OPTIONAL WIRING
REMOTE
ANNUNCIATOR
(–)
(+)
C0129-02
FIGURE 4. TERMINAL WIRE INSTALLATION
C0473-00
2
I56-6566TRG-001
©2021. 2/1/2021