FIGURE 5A. ACTIVATE TAMPER-RESIST FEATURE

PLASTIC LEVER

BREAK TAB AT DOTTED LINE BY 

TWISTING TOWARD CENTER OF BASE

USE SMALL-BLADED SCREWDRIVER TO PUSH 

PLASTIC LEVER IN DIRECTION OF ARROW

C0130-00

FIGURE 5B. DETECTOR REMOVAL

PLASTIC LEVER

BREAK TAB AT DOTTED LINE BY

TWISTING TOWARD CENTER OF BASE

USE SMALL-BLADED SCREWDRIVER TO PUSH 

PLASTIC LEVER IN DIRECTION OF ARROW

C0130-00

FIGURE 6. CONNECTION TO REMOTE ANNUNCIATOR TERMINAL

STRIPPED WIRE

WIRE WITH SPADE LUG

C0116-00

TAMPER-RESIST FEATURE

NOTE: Do not use the tamper-resist feature if a removal tool will be used.

The detector base includes a tamper-resist feature that prevents removal of the 
detector without using a small screwdriver or similar tool.

To activate this feature, use needle-nose pliers to break the tab on the detector 
base as shown in Figure 5A. Then, install the detector. 

To remove the detector from the base once the tamper-resist feature has been 
activated, remove the decorative ring by rotating it in either direction and 
pulling it away from the base. Then, insert a small screwdriver into the notch, 
as indicated in Figure 5B, and press the plastic lever toward the mounting 
surface before rotating the detector counterclockwise for removal.

The tamper-resist feature can be defeated by breaking and removing the plas-
tic lever from the base. However, this prevents the feature from being used 
again.

REMOTE ANNUNCIATOR (TR-RA100Z)

Connect the remote annunciator between terminals 1 and 3 using the spade 
lug terminal included. The spade lug terminal is connected to the base termi-
nal as shown in Figure 6.

It is not acceptable to have three stripped wires under the same wiring termi-
nal unless they are separated by a washer or equivalent means. The spade lug 
supplied with the model TR-RA100Z is considered an equivalent means. See 
Figure 3 for proper installation.

FIGURE 3. TYPICAL WIRING DIAGRAM FOR 2-WIRE LOOP

2

3

1

2

3

3

1

2

1

(–)

(+)

+

-

UL

 LISTED COM

PA

TIBLE

CONTROL

 P

ANEL

CAUTION: DO NOT LOOP WIRE 

UNDER TERMINAL 1 OR 2.

BREAK WIRE RUN TO PROVIDE 

SUPERVISION OF CONNECTIONS.

CLASS A OPTIONAL WIRING

REMOTE 

ANNUNCIATOR

(–)
(+)

C0129-02

FIGURE 4. TERMINAL WIRE INSTALLATION