TR-B200SR-LF-WH/TR-B200SR-LF-IV TERMINALS
No. Function
1. Not Used
2. Positive (+) Comm. Line In and Out
3. Negative (-) Comm. Line In and Out
4. External Supply Positive (+)
5. External Supply Negative (-)
6. Sounder Base Interconnect
MOUNTING
Mount the TR-B200SR-LF-WH/TR-B200SR-LF-IV mounting plate directly to an
electrical box. The plate will mount directly to 4" square (with and without
plaster ring), 4" octagon, 3½" octagon, single gang or double gang junction
boxes.
1. Connect field wiring to terminals, as shown in Figure 1 and 2.
2. Attach the mounting plate to the junction box as shown in Figure 3.
3. To mount the sounder base, hook the tab on the sounder base to the groove
on the mounting plate.
4. Then, swing the sounder base into position to engage the pins on the
product with the terminals on the mounting plate.
5. Secure the sounder base by tightening the mounting screws.
6. Install a compatible smoke sensor as described in the installation manual
for the sensor.
CAUTION
Do not over tighten mounting plate screws; this may cause mounting plate
to flex.
FIGURE 3. MOUNTING
Location of jumper–
remove to enable
continuous tone
C0891-10
TAMPER RESISTANT FEATURE
NOTE: Do not use the tamper-resist feature if the removal tool is to be used.
This detector base includes a tamper-resist feature that prevents its removal
from the base without the use of a tool. To activate this feature, break the tab
from the detector base as shown in Figure 4A. Then, install the detector. To
remove the detector from the base once the tamper-resist feature has been
activated, insert a small-bladed screwdriver into the slot from the top and
press down on the lever (see Figure 4B). This allows the detector to be rotated
counterclockwise for removal. The tamper-resist feature can be defeated by
breaking and removing the plastic lever from the base. However, this prevents
the feature from being used again.
TESTING AND MAINTENANCE
Sensors and bases must be tested after installation and as an integral part of a
periodic maintenance program. Test the TR-B200SR-LF-WH/TR-B200SR-LF-IV
as follows:
NOTE: Before testing, notify the proper authorities that the smoke sensor
system is undergoing maintenance and, therefore, will be temporarily out of
service. Disable the system undergoing maintenance to prevent unwanted
alarms.
1. If configured as in Figure 5 and 6, reverse the polarity of the external 24VDC
supply. If configured as in Figure 6, turn on the Intelligent Relay Module.
All TR-B200SR-LF-WH/TR-B200SR-LF-IV bases on the loop should sound.
2. Latch the sensor LED on from the control panel. That individual sensor’s
TR-B200SR-LF-WH/TR-B200SR-LF-IV should sound.
When performing maintenance on connected smoke sensors, carefully note
the location and address of each removed sensor.
FIGURE 4A. ACTIVATING THE TAMPER-RESIST FEATURE
PLASTIC LEVER
BREAK TAB AT
DOTTED LINE BY
TWISTING TOWARD
CENTER OF BASE.