Manual sceneCOM S | 11-2019 | 1.0 | en
The sceneCOM S system
c
10 / 18
Max. output cable length
Recommended wire length depending on material, ambient temperature and cross section.
Material
Cross section
Max. cable length
25 °C
50 °C
75 °C
Copper
0.20 mm²
45 m
41 m
37 m
0.50 mm²
112 m
102 m
93 m
0.75 mm²
168 m
153 m
140 m
1.00 mm²
224 m
204 m
187 m
1.50 mm²
300 m
(1)
300 m
(1)
281 m
Aluminum
0.20 mm²
27 m
25 m
23 m
0.50 mm²
68 m
62 m
57 m
0.75 mm²
102 m
93 m
86 m
1.00 mm²
136 m
125 m
115 m
1.50 mm²
205 m
187 m
172 m
(1)
Cable lengths of more than 300 m are not recommended.
...