As many momentary switches as required
can be wired in parallel.
*
L
N
modularDIM Basic
*
*
*
*
L N COM ALL I II III
D1 D2 D1 D2 D1 D2 X1 X2 COM PD I PD II PD III
groups
I II III iX
COM S1 L1 S2 L2 S3 L3 S4 L4
scenes
Sx ... momentary switches
Lx ... scene indication
modularDIM SC
iX
X1 X2
modularDIM LC
Sensor DAYLIGHT
**
PD1 PD2 PD3 com
PD PD PD
L1 L2 L3 N
N L L' N L L' N L L'
ALL I II III
iX ... intelligent extension
DAYLIGHT function
ON/OFF
2
PCA
6 D1 / DA
D2 / DA
3
4
7
max. 100 PCA/TE one4all/PCD/LCA
III
max. 100 PCA/TE one4all/PCD/LCA
II
max. 100 PCA/TE one4all/PCD/LCA
I
The light sensor „Sensor DAYLIGHT“ is to be installed with free view direction window (consider mounting instruction).
max. wire lengths:
• DSI: max. 250
m
• Momentary switch: max. 100
m
• Scene indication: max. 100
m
• iX: max. 10
m
• Sensor
DAYLIGHT: max. 100 m
•
DAYLIGHT function ON/OFF: max. 100 m
• PD: max. 100
m
L N
**
D1 / DA
D2 / DA
L
N
LCA
D1 / DA
D2 / DA
L
N
PCD
2
PCA
6 D1 / DA
D2 / DA
3
4
7
D1 / DA
D2 / DA
L
N
LCA
D1 / DA
D2 / DA
L
N
PCD
2
PCA
6 D1 / DA
D2 / DA
3
4
7
D1 / DA
D2 / DA
L
N
TE
one4all
D1 / DA
D2 / DA
L
N
PCD
modularDIM DM
channel
selector
iX
X2
AUTO
S1
S2
S1
S2
X1
MAN
Installation instructions
• To enable several operating points to be used, several keys or switches are connected in parallel.
• The maximum operating length of all keys, as well as the light sensor, may not be more than a max. length of 100 m.
• The DSI signal is transmitted by a functional extra low voltage (not safety extra low voltage). Use installation material that is designed for mains
voltage installations (230 V 50 Hz) therefore.
• The inputs and outputs for the keys, daylight sensor and for the iX interface meet the requirements for safety low voltage.
Important note: if one of the safety low voltage inputs/outputs is not wired in accordance with the relevant requirements, the other inputs
outputs should also be wired with installation material designed for mains voltage installation (230 V 50 Hz).
• The key inputs comply with the requirements of safety low voltages. Any kind of key can be used.
Data sheet 08/14-CO061-3 We reserve the right to make technical changes without prior notice.