Tridonic BASIC Series Скачать руководство пользователя страница 4

www.tridonic.com

4

Subject to change without notice. Information provided without guarantee.

Data sheet 07/20-EM071-10

Emergency lighting units

EM converterLED

1. Standards

•  EN 61347-1
•  EN 61347-2-13
•  EN 61347-2-7
•  EN 55015
•  EN 61000-3-2
•  EN 61000-3-3
•  EN 61547
•  EN 60068-2-64
•  EN 60068-2-29
•  EN 60068-2-30
•  EN 62384
•  according to EN 50172
•  according to EN 60598-2-22

1.1 Glow-wire test

according to EN 61347-1 with increased temperature of 850 °C passed.

1.2 Insulation and electric strength testing of luminaires

Electronic LED-Drivers can be damaged by high voltage. This has to be consid-
ered during the routine testing of the luminaires in production.

According to IEC 60598-1 Annex Q (informative only!) or ENEC 303-Annex A, 
each luminaire should be submitted to an insulation test with 500 V

DC

 for 1 sec-

ond. This test voltage should be connected between the interconnected phase 
and neutral terminals and the earth terminal. The insulation resistance must be 
at least 2 MΩ.

As an alternative, IEC 60598-1 Annex Q describes a test of the electrical 
strength with 1,500 V

AC

 (or 1,414 x 1,500 V

DC

). To avoid damage to the electronic 

devices this test 

must not be conducted

.

2. Thermal details and life-time

2.1 Life-time

Average life-time 50,000 hours under rated conditions with a failure rate of 
less than 10 %. Average failure rate of 0.2 % per 1000 operating hours.

Expected life-time
EM converterLED BASIC 203 
NiCd/NiMH 90V

tc

65 °C

70 °C

75 °C

life-time

> 100,000 h 93,000 h

66,000 h

EM converterLED BASIC 204 
NiCd/NiMH 90V

tc

65 °C

70 °C

75 °C

life-time

> 100,000 h 79,000 h

55,000 h

3. Installation / Wiring

3.1 Wiring diagram

One or more LED modules with a total forward voltage of 40 to 97 V can be con-
nected to the EM converterLED 90V module. These LED module(s), marked with 
“Emergency” are operated in emergency mode from the associated battery. In 
normal mains mode all LED modules are operated by the LED Driver from the 
mains supply.

Use of the test switch: 
For checking the device function press the test switch for a minimum of 3 
seconds.

Meaning of marking 
Double or reinforced insulation for built-in electronic LED Drivers. The control 
gear relies upon the luminaire enclosure for protection against accidental contact 
with live parts.

The emergency lighting LED Driver is designed for a life-time stated above 
under reference conditions and with a failure probability of less than 10 %.

The relation of tc to ta temperature depends also on the luminaire design. 
If the measured tc temperature is approx. 5 K below tc max., ta tempera-
ture should be checked and eventually critical components (e.g. ELCAP) 
measured. Detailed information on request.

Содержание BASIC Series

Страница 1: ...ug duration link Compatible with all dimmable and non dimmable constant current LED Drivers see chapter 5 4 3 pole technology 2 pole LED module changeover and delayed power switching for the LED Driver Automatic shutdown of output if LED load is out of range Constant power output Maximum light output for all LED modules Electronic charge system Deep discharge protection Short circuit proof battery...

Страница 2: ...ng function according to AS 2293 EM converterLED BASIC NiCd NiMH 90 V BASIC series 30 21 30 179 169 2 Duration link 3 h No duration link 1 h Note LED Driver supplied with duration link in 3 hours position Remove duration link for 1 hour duration Duration link must be set before battery and mains connection Ordering data Type1 Article number Rated duration Number of cells Packaging carton Packaging...

Страница 3: ... 89800269 25 pc s 200 pc s 0 015 kg LED EM green HO 1 0 m CON 89800271 25 pc s 200 pc s 0 015 kg LED EM green 0 6 m CON 89800472 25 pc s 200 pc s 0 009 kg LED EM green HO 0 6 m CON 89800473 25 pc s 200 pc s 0 009 kg LED EM green 0 3 m CON 89800270 25 pc s 200 pc s 0 005 kg LED EM green HO 0 3 m CON 89800272 25 pc s 200 pc s 0 005 kg Product description For connection to the emergency lighting unit...

Страница 4: ...life time 50 000 hours under rated conditions with a failure rate of less than 10 Average failure rate of 0 2 per 1000 operating hours Expected life time EM converterLED BASIC 203 NiCd NiMH 90V tc 65 C 70 C 75 C life time 100 000 h 93 000 h 66 000 h EM converterLED BASIC 204 NiCd NiMH 90V tc 65 C 70 C 75 C life time 100 000 h 79 000 h 55 000 h 3 Installation Wiring 3 1 Wiring diagram One or more L...

Страница 5: ...LED Module Emergency Neutral P O Lout Lin N L L N Neutral Un Switched Line Test switch Indicator LED Switched Line in Switched Line out Control gear LED LED Control gear Battery Battery LED Module Emergency LED control gear max 150 W in operation EM ConverterLED BASIC EM converterLED BASIC with a standard LED Driver and series operation of LED modules Neutral P O Lout Lin N L L N Neutral Un Switch...

Страница 6: ...eration LED Module Emergency LED Module Switched Line in Switched Line out EM ConverterLED BASIC Two or more LED modules are operated in emergency mode All LED modules are operated in mains mode EM converterLED BASIC with a standard LED Driver and parallel operation of LED modules Neutral P O Lout Lin N L L N Neutral Un Switched Line Test switch Indicator LED Control gear LED LED Control gear Batt...

Страница 7: ...igh frequency content which should be considered for good EMC compliance LED leads should be separated from the mains connections and wiring for good EMC performance Maximum lead length on the LED terminals is 3 m For a good EMC performance keep the LED wiring as short as possible The secondary wires LED module should be routed in parallel to ensure good EMC performance Maximum lead length for the...

Страница 8: ...switch Mounting hole 7 0 mm diameter Lead length 0 55 m Plug connection Battery leads Quantity 1 red and 1 black Length 1 3 m Wire type 0 5 mm2 solid conductor Insulation rating 90 C Battery end termination Push on 4 8 mm receptacle to suit battery spade fitted with insulating cover Module end termination 8 0 mm stripped insulation Two piece batteries are supplied with a 200 mm lead with 4 8 mm re...

Страница 9: ...IC 204 NiCd NiMH 90V Article number 89800562 4 8 V battery voltage 850 960 mA battery discharge current tolerance VLED VLED 5 3 Typ LED current voltage characteristics The LED current in emergency mode is automatically adjusted by the EM converterLED module based on the total forward voltage of the LED modules con nected and the associated battery The start of the LED in emergency mode does not re...

Страница 10: ...llowed output voltage of the associated LED Driver applied to the EM converterLED output is 450V voltage withstand between adja cent contact of the single switching relay of the EM converterLED The max allowed LED load of the associated LED Driver is 150 W in operation The load must be an LED module Check compatibility with short function tests duration of several seconds 6 Functions 6 1 Duration ...

Страница 11: ...MH 4Ah 3A CON 89800441 stick 1 x 4 Accu NiMH 4Ah 4A CON 89800442 EM converterLED BASIC 1 3 h Type EM converterLED BASIC 203 NiCd NiMH 90V EM converterLED BASIC 204 NiCd NiMH 90V Article no 89800561 89800562 Cells 3 cells 4 cells Duration 1 h 3 h 1 h 3 h Battery charge time Initial charge 24 h Fast recharge 24 h Trickle charge continuously Charging current Initial charge 80 130 mA 170 220 mA 80 130...

Страница 12: ...years design life 5 C to 55 C Max short term temperature reduced life time 70 C Max number discharge cycles 12 cycles per year plus 4 cycles during comissioning Max storage time 12 months 7 4 Accu NiMH 2 2 Ah International designation HRMU 23 43 Battery voltage cell 1 2 V Cell type Cs Case temperature range to ensure 4 years design life 5 C to 50 C Max short term temperature reduced life time 70 C...

Отзывы: