www.tridonic.com
2
Subject to change without notice. Information provided without guarantee.
Data sheet 09/22-EM080-23
Emergency lighting units
EM converterLED
Specific technical data
Type
1
Battery
technology
Rated
duration
Typ. λ (at 230
V, 50 Hz)
Typ. output
power
P emergency
Mains current in charging operation
Rated power in charging operation
Initial charge
Fast recharge
Trickle charge
3
Initial charge
Fast recharge
Trickle charge
3
EM converterLED BASIC
202A MH/LiFePO4 250V
NiMH
1 h
0.60C
2.3 W
17 mA
17 mA
17 / 12 mA
2.4 W
2.4 W
2.4 / 1.4 W
3 h
0.60C
2.3 W
18 mA
18 mA
18 / 12 mA
2.6 W
2.6 W
2.6 / 1.4 W
LiFePO4
1 h
0.60C
2.3 W
17 mA
17 mA
17 / 12 mA
2.1 W
2.1 W
2.1 / 1.4 W
3 h
0.60C
2.3 W
20 mA
20 mA
20 / 12 mA
2.9 W
2.9 W
2.9 / 1.4 W
EM converterLED BASIC
203 MH/LiFePO4 250V
NiMH
1h
0.60C
2.5 W
17 mA
17 mA
17 / 12 mA
2.4 W
2.4 W
2.4 / 1.4 W
3h
0.60C
2.5 W
19 mA
19 mA
19 / 12 mA
2.9 W
2.9 W
2.9 / 1.4 W
LiFePO
4
1h
0.60C
2.5 W
20 mA
20 mA
20 / 12 mA
2.8 W
2.8 W
2.8 / 1.4 W
3h
0.60C
2.5 W
25 mA
25 mA
25 / 12 mA
3.9 W
3.9 W
3.9 / 1.4 W
EM converterLED BASIC
204 MH/LiFePO4 250V
NiMH
1h
0.65C
3.5 W
18 mA
18 mA
18 / 12 mA
2.5 W
2.5 W
2.5 / 1.4 W
3h
0.65C
3.5 W
21 mA
21 mA
21 / 12 mA
3.2 W
3.2 W
3.2 / 1.4 W
LiFePO
4
1h
0.65C
3.5 W
20 mA
20 mA
20 / 12 mA
2.8 W
2.8 W
2.8 / 1.4 W
3h
0.65C
3.5 W
26 mA
26 mA
26 / 12 mA
3.9 W
3.9 W
3.9 / 1.4 W
EM converterLED BASIC
205 MH/LiFePO4 250V
NiMH
1h
0.65C
4.5 W
19 mA
19 mA
19 / 12 mA
2.7 W
2.7 W
2.7 / 1.4 W
3h
0.65C
4.5 W
22 mA
22 mA
22 / 12 mA
3.3 W
3.3 W
3.3 / 1.4 W
LiFePO
4
1h
0.65C
4.5 W
20 mA
20 mA
20 / 12 mA
2.8 W
2.8 W
2.8 / 1.4 W
3h
0.65C
4.5 W
26 mA
26 mA
26 / 12 mA
3.9 W
3.9 W
3.9 / 1.4 W
1
EM = Emergency
2
16 h battery charging time for 2 h emergency lighting function according to AS 2293.
3
In case of NiMH batteries: Intermittent charge is used. Value 1 is for 4 min. charge on / Value 2 is for 16 min. charge off. In case of LiFePO
4
batteries voltage dependent constant current charging is used.
4
12 h battery charging time for 2 h emergency lighting function when used with LiFePO
4
batteries.
EL
Technical data
Rated supply voltage
220 – 240 V
AC voltage range
198 – 264 V
Mains frequency
50 / 60 Hz
LED module forward voltage range
50 – 250 V
Output current
see chapter 5.3
Time to light
< 0.5 s from detection of emergency
event
Overvoltage protection
320 V (for 48 h)
U-OUT (including open- / short-circuit and
double load)
280 V
Max. open circuit voltage
280 V
Battery charging time
24 h
24
Ambient temperature range ta
-5 ... + 55 °C
Max. casing temperature tc
75 °C
Mains voltage changeover threshold
according to EN 60598-2-22
Mains surge capability (between L – N)
1 kV
Mains surge capability (between L/N – PE)
2 kV
Type of protection
IP20
Lifetime
up to 100,000 h
Guarantee (conditions at www.tridonic.com) 5 years
Dimensions LxWxH
179 x 30 x 21 mm
EM converterLED BASIC MH/LiFePO4 250 V
BASIC series
30
21
30
179
169.2
Duration
link 3 h
No
duration
link 1 h
Note: LED driver supplied with duration link in 3 hours position. Remove duration link for
1 hour duration. Duration link must be set before battery and mains connection.
Ordering data
Type
1
Article
number
Rated
duration
Packaging,
carton
Packaging,
pallet
Weight
per pc.
EM converterLED BASIC 202A MH/LiFePO4 250V 89800709
1/3 h
10 pc(s).
1,600 pc(s). 0.07 kg
EM converterLED BASIC 203 MH/LiFePO4 250V
89800592
1/3 h
10 pc(s).
1,600 pc(s). 0.07 kg
EM converterLED BASIC 204 MH/LiFePO4 250V
89800581
1/3 h
10 pc(s).
1,600 pc(s). 0.07 kg
EM converterLED BASIC 205 MH/LiFePO4 250V
89800582
1/3 h
10 pc(s).
1,600 pc(s). 0.07 kg
EMcLED Strain-relief set 240x43x30mm
A
CCES
-
SORIES
43
68
68
240
30
Permissible cable jacket diameter 2.2 – 9 mm
Ordering data
Type
Article
number
Packaging, carton Packaging, pallet Weight per pc.
EMcLED SR
28003813
10 pc(s).
1,260 pc(s).
0.08 kg