Data sheet 03/20-EM042-21
Emergency lighting units
EM powerLED
Wiring
Mains (N, L, C/F, L link, S/L)
LED (LED +, LED –)
Batteries (Bat +, Bat –)
I set
Maximum lead length
LED
3 m
status indication LED
1 m
batteries
1 m
Wiring
Test switch
Indication LED
Max. lead insulation diameter
Battery
2.1 mm
Test switch
2.1 mm
Indicator LED
2.1 mm
Use one wire for each terminal connector only.
Use each strain relief channel for one cable only.
max.
∅
= 10 mm
min.
∅
= 6,3 mm
8.5 – 9.5 mm
0.2 – 0.5 mm² solid or fine-stranded
0.25 mm² fine-stranded with ferrule
8.5 – 9.5 mm
0.5 – 1.5 mm2 solid or fine-stranded
0.5 – 1.0 mm2 fine-stranded with ferrule
Installation instruction
Max. torque for the mounting screws: 0.5 Nm / M4.
3.3 Release of the wiring
Press down the “push button” and remove
the cable from front.
3.2 Wiring type and cross-section
3.4 Fixing conditions
Dry, acidfree, oilfree, fatfree. It is not allowed to exceed the maximum ambi-
ent temperature (ta) stated on the device. Minimum distances stated below
are recommendations and depend on the actual luminaire. Is not suitable for
fixing in corner.
>100 mm
Leuchte
Luminaire
>20 mm
>20 mm
3.5 Wiring guidelines
• The output to the LED is DC but has high frequency content, which should be
considered for good EMC compliance.
• LED leads should be separated from the mains connections and wiring for
good EMC performance.
• Maximum lead length on the LED terminals is 3 m. For a good EMC
performance keep the LED wiring as short as possible.
• The secondary wires (LED module) should be routed in parallel to ensure
good EMC performance.
• Maximum lead length for the Test switch and Indicator LED connection is 1 m.
The test switch and Indicator LED wiring should be separated from the LED
leads to prevent noise coupling.
• Battery leads are specified with 0.5 mm cross section and a length of 1.3 m.
• To avoid the damage of the control gear, the wiring must be protected against
short circuits to earth (sharp edged metal parts, metal cable clips, louver, etc.).
To ensure that a luminaire containing LED emergency units complies with
EN 55015 for radio frequency conducted interference in both normal and emer-
gency mode it is essential to follow good practice in the wiring layout.
Within the luminaire the switched and unswitched 50 Hz supply wiring must be
routed as short as possible and be kept as far away as possible from the LED
leads. Through wiring may affect the emc performance of the luminaire.
The length of LED leads must not be exceeded.
The output current depends on the forward voltage and the tolerance of the
LED modules.
4. Mechanical data
4.1 Housing properties
4.2 Mechanichal data accessories
LED status indicator
• Green
• Mounting hole 6.5 mm diameter, 1 – 1.6 mm thickness
• Lead length 0.3 m / 1.0 m
• Insulation rating: 90 °C
Test switch
• Mounting hole 7.0 mm diameter
• Lead length 0.55 m
Battery leads
• Quantity: 1 red and 1 black
• Length: 1.3 m
• Wire type: 0.5 mm
2
solid conductor
• Insulation rating: 90 °C
Battery end termination
Push on 4.8 mm receptacle to suit battery spade fitted with insulating cover
Module end termination
8.0 mm stripped insulation
Two-piece batteries are supplied with a 200 mm lead with 4.8 mm receptacle
at each end and insulting covers to connect the separate sticks together.
• Polycarbonat white/green
• Type of protection IP 20