www.tridonic.com
6
Subject to change without notice. Information provided without guarantee.
Data sheet 11/21-LC888-6
LED Driver
Linear fixed output
6.1 Insulation and electric strength testing of luminaires
Electronic devices can be damaged by high voltage. This has to be considered
during the routine testing of the luminaires in production.
According to IEC 60598-1 Annex Q (informative only!) or ENEC 303-Annex A,
each luminaire should be submitted to an insulation test with 500 V
DC
for
1 second. This test voltage should be connected between the interconnected
phase and neutral terminals and the earth terminal.
The insulation resistance must be at least 2 MΩ.
As an alternative, IEC 60598-1 Annex Q describes a test of the electrical
strength with 1500 V
AC
(or 1.414 x 1500 V
DC
). To avoid damage to the electronic
devices this test must not be conducted.
6.3 Additional information
Additional technical information at www.tridonic.com
→
Technical Data
Life-time declarations are informative and represent no warranty claim.
No warranty if device was opened.
6.2 Conditions of use and storage
Humidity:
5 % up to max. 85 %,
not condensed
(max. 56 days/year at 85 %)
Storage temperature:
-40 °C up to max. +80 °C
The devices have to be within the specified temperature range (ta) before
they can be operated.
The LED Driver is declared as inbuilt LED controlgear, meaning it is intended
to be used within a luminaire enclosure.
If the product is used outside a luminaire, the installation must provide
suitable protection for people and environment (e.g. in illuminated ceilings).
Automatic circuit
breaker type
C10
C13
C16
C20
B10
B13
B16
B20
Inrush current
Installation Ø
1.5 mm
2
1.5 mm
2
1.5 mm
2
2.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
2.5 mm
2
I
max
Time
LC 35/200-350/121 stepDIM lp SNC
36
47
58
73
36
47
58
73
12 A
80 µs
THD
3.
5.
7.
9.
11.
LC 35/200-350/121 stepDIM lp SNC
< 10
< 7
< 5
< 5
< 5
< 3
Acc. to 6100-3-2. Harmonics < 5 mA or < 0.6 % (whatever is greater) of the input current are
not considered for calculation of THD.
4.7 Harmonic distortion in the mains supply (at 230 V / 50 Hz and full load)
in %
5. Functions
6. Miscellaneous
5.1 Short-circuit behaviour
In case of a short circuit on the output side (LED) the LED Driver switches off.
After elimination of the short-circuit fault the LED Driver will recover
automatically.
5.2 No-load operation
The LED Driver works in burst working mode to provide a constant output
voltage regulation which allows the application to be able to work safely when
LED string opens due to a failure.
4.6 Maximum loading of automatic circuit breakers in relation to inrush current
These are max. values calculated out of continuous current running the device on full load. There is no limitation due to in-rush current.
If load is smaller than full load for calculation only continuous current has to be considered.
Motion Sensor
Product description
5.3 Overload protection
If the maximum load is exceeded by a defined internal limit, the LED Driver
will protect itself and LED may flicker. After elimination of the overload, the
nominal operation is restored automatically.