Concrete specification
Semi dry concrete 25n grade with a ratio of 4.5 aggregate to 1 cement.
Important:
•
Standard concrete mixes should not be used, where sulphates or similarly aggressive
chemicals are present in the groundwater.
•
Lift height (rate of rise): Determine the lift height (m), or rate of rise (m/h) for the specific
type of concrete used to ensure that you do not exceed the design pressure (P max) of
15kN/m2 on the tank.
•
Vibration: The tank design assumes minimal compaction of the surrounding concrete.
Where necessary, this may be extended to include internal light vibration. Never use deep
reverberation which will substantially increase the pressure on the tank, possibly causing
failure.
•
Impact of concrete on discharge: Under no circumstances should concrete be discharged
directly onto the tank.
5.8
Topsoil requirements
Clean native top soil shall not contain rocks larger than 36mm in the largest dimension.
Note:
The use of geo textile barrier fabrics surrounding the primary backfill material is considered
good installation practice. The fabric must be chosen to allow the flow of water in and out
of the excavation but to prevent the movement of fine soil particles into the primary
backfill material.
Содержание Novo UK10
Страница 1: ...0 106 Rev 11 Dec 2017 Tricel Novo UK6 50 Wastewater Treatment Plants Engineering a green future...
Страница 4: ...3...
Страница 5: ...4...
Страница 10: ...9...
Страница 11: ...10...
Страница 26: ...25 5 11 1 Electrical Diagrams 5 11 1 1 Tricel Novo Gravity Outlet UK6 UK8 UK10 UK12 Control Panel No 209102...
Страница 27: ...26 UK18 UK24 Control Panel No 209116...
Страница 28: ...27 UK30 UK36 UK42 UK50 Control Panel No 209111...
Страница 29: ...28 5 11 1 2 Tricel Novo Pumped Outlet UK6 UK8 UK10 UK12 UK18 UK24 Control Panel No 209101...
Страница 30: ...29 UK30 UK36 UK42 UK50 Control Panel No 209112...
Страница 42: ...41 12 Terms conditions Subject to our standard terms and conditions which are available on request...
Страница 43: ...42...