31
Performances
MODEL
Boiler Heating
Capacity MBH
Peak Flow
gal./ 10 min.
1st Hour Flow
Gal./Hour
Continuous Flow
Gal./ Hour
Circulator
Min. GPM
SMART 30
87
40
140
115
5
SMART 40
112
50
180
150
7
SMART 50
140
65
220
185
8
SMART 60
270
100
410
360
16
SMART 80
300
125
460
400
18
SMART 100
337
150
525
450
25
SMART 120
420
190
650
560
28
Conditions:
- 50ºF Domestic cold water inlet temperature
- 140ºF Domestic hot water outlet temperature
- 200ºF Boiler water supply temperature
MODEL
Boiler Heating
Capacity MBH
Peak Flow
gal./ 10 min.
1st Hour Flow
Gal./Hour
Continuous Flow
Gal./ Hour
Circulator
Min. GPM
SMART 30
115
60
235
210
8
SMART 40
130
70
270
240
9
SMART 50
180
95
370
330
12
SMART 60
320
145
635
590
21
SMART 80
340
165
690
630
24
SMART 100
380
185
775
700
26
SMART 120
445
235
915
820
30
Conditions:
- 50ºF Domestic cold water inlet temperature
- 115ºF Domestic hot water outlet temperature
- 200ºF Boiler water supply temperature