Prestige SOLO 399 Boiler

Natural to Propane Instructions

6

creating a DHW call which will enable the DHW
circulator.

5.  Press the 

RIGHT

button to adjust the firing rate

to 100% (high fire).  Hold down the  

RIGHT

but-

ton to rapidly increase the firing rate.

6.   If the combustion levels during high fire are out-

side  the  recommended  combustion  settings  in
Table 2, adjust the THROTTLE SCREW (see Fig.
3) using a flat-blade screwdriver.

The throttle screw is highly sensitive and requires
the use of a combustion analyzer for adjustment.
An adjustment as small as an 1/8 of a turn can pro-
duce a large change in combustion levels.

7.   Once the combustion level is set at high fire, man-

ually place the boiler into low fire mode by press-
ing the 

LEFT

button to adjust firing rate down to

0% (low fire).

8.   If the combustion level (O2 or CO2) during low

fire is not /-0.2 of the combustion level
measured  at  high  fire,  remove  the  offset  cover
screw  and  adjust  the  plastic  OFFSET  SCREW
(see Fig. 3) using a T-40 Torx wrench as follows:

Counter-clockwise  adjustment  of  OFFSET
SCREW at Low Fire (0% firing rate):

            O2 increases and CO2 decreases

Clockwise  adjustment    of  OFFSET  SCREW at
Low Fire (0% firing rate):

            O2 decreases and CO2 increases

9.   Press the OK button while the fan icon is high-

lighted to shutdown the burner.

10. Press the 

LEFT

or 

RIGHT

button to highlight

the home screen icon

to exit the service mode.

 

   

 

 

   

 

 

   

 

 

   

 

 

  

 

 

  

 

 

  

 

 

  

  

 

 

WARNING

2012-33 Prestige Solo 399 Natural to LP Instructions

Revised Date: 6/5/12