Time Delay Relay Box Kit

for Prestige SOLO

2

Instructions:

1. Turn off the electrical power supply to the unit

at the service panel.

ELECTRICAL SHOCK HAZARD. For

your safety, disconnect electrical power sup-

ply to the unit before servicing or making

any electrical connections to avoid possible

electric shock hazard.  Failure to do so can

cause severe personal injury or death.

2. Remove the front jacket panel from the Prestige

SOLO.

3. Remove the 120 volt power wiring from termi-

nals #1, #2, & #3 (SOLO 110) or L, N, & G
(SOLO 175 & 250).

4. Remove the cover from the Time Delay Relay

Box.

5. Mount the Time Delay Relay Box on a secure

surface near the boiler using the mounting
screws provided.

6. Connect the power supply wiring to the appro-

priate wire leads in the Time Delay Relay Box
as shown in Figure 1.

7. Connect field wiring to the appropriate wire

leads in the Time Delay Relay Box and to the
Prestige SOLO terminals #1, #2, & #3 (SOLO
110) or L, N, & G (SOLO 175 & 250) as shown
in Fig. 1.

8. Install the front jacket panel on the Prestige

SOLO and secure with mounting screws.

9. Install the cover on the Time Delay Relay Box

and restore power to the boiler.

10. Measure time from when power is restored until

the boiler actually powers up (LED  numbers
will reappear on the display panel).  The Time
Delay Relay Box has a delay-on-make timer
that delays powering of the boiler for 3 minutes
whenever power is lost to the boiler.  Timing
should be approximately 3 minutes, but no
longer than 4 minutes.  If the time delay is less
than 3 minutes or longer than 4 minutes, contact
Triangle Tube Tech Support at (856) 228-8881.

11. Cycle boiler per installation manual.

WARNING

L

N

To

Boiler

Relay

Honeywell R8222

Time Delay

Relay

120V

Incoming

Supply

2

4

3

1

3

1

Fig. 1:  Time Delay Relay Box Wiring

2006-38 Time Delay Relay Box Kit