Time Delay Relay Box Kit
for Prestige SOLO
2
Instructions:
1. Turn off the electrical power supply to the unit
at the service panel.
ELECTRICAL SHOCK HAZARD. For
your safety, disconnect electrical power sup-
ply to the unit before servicing or making
any electrical connections to avoid possible
electric shock hazard. Failure to do so can
cause severe personal injury or death.
2. Remove the front jacket panel from the Prestige
SOLO.
3. Remove the 120 volt power wiring from termi-
nals #1, #2, & #3 (SOLO 110) or L, N, & G
(SOLO 175 & 250).
4. Remove the cover from the Time Delay Relay
Box.
5. Mount the Time Delay Relay Box on a secure
surface near the boiler using the mounting
screws provided.
6. Connect the power supply wiring to the appro-
priate wire leads in the Time Delay Relay Box
as shown in Figure 1.
7. Connect field wiring to the appropriate wire
leads in the Time Delay Relay Box and to the
Prestige SOLO terminals #1, #2, & #3 (SOLO
110) or L, N, & G (SOLO 175 & 250) as shown
in Fig. 1.
8. Install the front jacket panel on the Prestige
SOLO and secure with mounting screws.
9. Install the cover on the Time Delay Relay Box
and restore power to the boiler.
10. Measure time from when power is restored until
the boiler actually powers up (LED numbers
will reappear on the display panel). The Time
Delay Relay Box has a delay-on-make timer
that delays powering of the boiler for 3 minutes
whenever power is lost to the boiler. Timing
should be approximately 3 minutes, but no
longer than 4 minutes. If the time delay is less
than 3 minutes or longer than 4 minutes, contact
Triangle Tube Tech Support at (856) 228-8881.
11. Cycle boiler per installation manual.
WARNING
L
N
To
Boiler
Relay
Honeywell R8222
Time Delay
Relay
120V
Incoming
Supply
2
4
3
1
3
1
Fig. 1: Time Delay Relay Box Wiring
2006-38 Time Delay Relay Box Kit
12/12/06