Prestige Trimax 175

Ignition Kit - Installation Instructions

1.1.  Applicability

Prestige boilers with “PT”-prefixed serial number, as 

indicated on data plate. 

Kit Part Number

Model

PTRKIT302

PT 175

Table 1 - PT Ignition Kit Numbers

1.2.  Purpose

This kit (see 

Fig. 3 

for details) replaces the existing TriMax 

control module, the igniter and wiring, the internal 

venting tube and the heat exchanger insulation.

1.3.  Initial tasks

Confirm the replacement kit is appropriate for the boiler 
to be worked on (see 

Table 1).

 

Write down all the appliance settings, including the 

cascade settings (if the boiler is in a cascade) for reference 

before bringing any change to the appliance. A reference 

table is provided on the last page of this document. 

1.4.  Boiler preparation

1.4.1  Required Tools and Material

•  Screwdriver, flat head

•  Screwdriver, cross head

•  10 mm socket/wrench

•  Wrench, Torx 20

•  Flue gas analyzer

1.4.2  Preparation Procedure

1.  Turn the boiler off by pressing the on/off power 

switch.

2.  Allow boiler to cool down.
3.  Disconnect electrical power at the external electric box

• 

Avoid electrical shock by disconnecting the 

electrical supply prior to performing any operation 

on the internal parts of the boiler. 

 

DANGER

 

DANGER

• 

Before any operation on the internal components 

of the appliance, allow the appliance to cool 

down to room temperature. Some components 

can be very hot.

• 

Failure to comply will result in substantial property 

damage, serious injury, or death.

4.  Shut off the gas supply to the boiler at the main manual 

shut off valve.

5.  Remove boiler front panel as follows:

•  Remove the thumb screw along the upper 

edge of the unit.

•  Lift the panel up and tilt back slightly to remove 

the front panel. 

6.  Slide left and right tabs of control panel inward and 

lower control panel. See 

Fig. 1

.

Œ

Œ



Fig. 1 -  Opening and Lowering the Control Panel

Retaining tabs

Fig. 2 -  Opening the Retaining Tabs

Revision Date: 5/4/2020

2020-32 Prestige Trimax 175 Ignition Kit

Содержание Prestige Trimax 175

Страница 1: ...x 20 Flue gas analyzer 1 4 2 Preparation Procedure 1 Turn the boiler off by pressing the on off power switch 2 Allow boiler to cool down 3 Disconnect electrical power at the external electric box Avoi...

Страница 2: ...W Bk V Fig 3 Prestige Solo Excellence Ignition Kit Item Description Qty 1 Igniter 1 Screws igniter 2 Gasket igniter 1 Bracket spark generator not illustrated 1 2 Spark generator 1 3 Wiring spark gene...

Страница 3: ...r intake 3 from venturi Retain for reinstallation Before disconnecting any wire connections mark and label all connections and location of the connections 2 Open top access panels by removing top acce...

Страница 4: ...Required 0 221 5 6mm Table 2 Orifice Sizes 1 5 4 Removing the Burner and Insulation 1 Remove heat exchanger bracket located at the back of the heat exchanger Discard bracket 2 Remove burner plate nut...

Страница 5: ...nnection 1 5 9 Checking the Combustion Settings 1 Turn boiler on 2 Allow the appliance to stabilize and insert the gas an alyzer probe in the top vent adapter measuring port 3 Check combustion values...

Страница 6: ...s 1 5 10 Return to Service 1 Reinstall the air intake on the venturi 2 Close top access panel as required 3 Check that all wiring connections are secure 4 Check that the gas connection is tight 5 Supp...

Страница 7: ...llence PCB Wiring POSTMOD Gr Br W Bk V F00 F01 V To left side casing grounding tabs Connect to uncon nected Molex connector in exist ing boiler wiring DO NOT reconnect original boiler wiring Molex con...

Страница 8: ...68 F 20 C 188 F 87 C CH1 Minimum Setpoint 120 F 49 C 60 F 15 C 188 F 87 C Reset Curve Coldest Day 0 F 18 C 30 F 34 C 50 F 10 C Reset Curve Warmest Day 64 F 18 C 60 F 15 C 78 F 25 C CH2 Circuit Enable...

Отзывы: