TriangleTube Prestige SOLO 299 Скачать руководство пользователя страница 4

Prestige SOLO 299/399 - ACVMax Boilers 

Natural to Propane Instructions  

4

2.0 Combustion Test and Adjustments

1.   The installer MUST perform a complete com-

bustion check to ensure the following combus-

tion levels in Tables 2 and 3 are met at high and

low input firing rates and the burner is operating

at optimum conditions.

Table 2: Recommended Propane Combustion Settings

The  combustion  testing  and  adjustments

must  be  performed  by  a  qualified  installer,

service agency or the gas supplier.  All com-

bustion  measurements  must  be  performed

with calibrated equipment to ensure proper

readings and accuracy.

Failure  to  perform  a  complete  combustion

test  at  both  high  and  low  input  rates  may

result in incomplete combustion and the pro-

duction  of  carbon  monoxide,  which  can

result in substantial property damage, seri-

ous injury, or death.

The combustion levels should be measured at

high firing rate.  If the combustion levels are

not within the range given in Table 2 for Low

Fire after adjusting High Fire, shut the boiler

down  and  contact  Triangle  Tube  Technical

Support  Department.    Failure  to  comply

with this requirement can result in substan-

tial  property  damage,  serious  injury,  or

death.

The gas valve outlet pressure is factory set to the

correct value and does not require field adjust-

ment or measurement.  Measurement or adjust-

ments  could  result  in  damage  to  the  gas  valve

and can result in substantial property damage,

serious injury, or death.

2. Press the round INSTALLER button.  See Fig.

4.

3.  Enter the installer access code “054” by using

the 

LEFT

and 

RIGHT

buttons to select a digit

and the 

UP

and 

DOWN

buttons to change the

digit.  Press the 

OK

button to enter the access

code.

4. Press  the 

RIGHT

button  to  highlight  the

Manual Operation icon

then press the 

OK

button.

5.   Press  the 

OK

button  while  the  FAN  icon  is

highlighted  to  manually  fire  the  burner  and

power the CH1 circulator (see Fig. 5)

WARNING

WARNING

WARNING

WARNING

DHW Demand

Target = 186°F

Installer Button

Fig. 4: ACVMax Navigation Buttons

Manual Operation

Released

Off

Off

Off

CH1

FAN

DHW

CH2

 

 

 

Fig. 5: ACVMax Manual Operation

PA 299

PA 399

Hi

gh

 Fi

re

CO2 Range

10.7 to 12.0% 10.4 to 11.4%

CO2 Target

11.0%

O2 Range

2.7 to 4.7%

3.7 to 5.2%

O2 Target

4.2%

Lo

w

 Fi

re

CO2 Range

0.5 to 0.6% 

Lower than

H.F. CO2

O2 Range

0.8 to 0.9% 

Higher than

H.F. O2

CO Max

150 ppm

Содержание Prestige SOLO 299

Страница 1: ...ting rating label DO NOT affix the new label over the existing rat ing label Add propane conversion labeling to the gas valve These instructions cover NG to LP conversion for ACVMax controlled Prestige Solo 299 399 boilers only Each kit is supplied with one orifice suitable for use with that particular boiler model NOTICE NOTICE WARNING WARNING Indicates a potentially hazardous situation which if ...

Страница 2: ...T 25 Torx head screws used to mount the gas supply piping to the bottom of the gas valve Do not discard the screws Remove the gas valve assembly from the gas piping See Fig 1 8 Remove the four 4 T 25 Torx head screws attaching the brass union collar to the top of the gas valve Do not discard the screws Remove the brass natural gas orifice from the underside of the brass union collar See Fig 2 9 In...

Страница 3: ...brass union and the gas supply piping Retighten the union just above the gas valve and install the four 4 T 25 Torx head screws to attach the gas supply pip ing to the gas valve 12 Reconnect the gas valve electrical connections as shown in Fig 3 13 Open the manual gas shut off valve Before placing the Prestige boiler back into operation check and test all gas connections for leaks Repair leaks if ...

Страница 4: ...ical Support Department Failure to comply with this requirement can result in substan tial property damage serious injury or death The gas valve outlet pressure is factory set to the correct value and does not require field adjust ment or measurement Measurement or adjust ments could result in damage to the gas valve and can result in substantial property damage serious injury or death 2 Press the...

Страница 5: ...ases Clockwise adjustment of the THROTTLE SCREW at High Fire 100 firing rate O2 increases and CO2 decreases 8 Once the combustion level is set at high fire manually place the boiler into low fire mode by pressing the LEFT button to adjust firing rate down to 1 low fire to verify low fire com bustion settings 9 If the combustion levels O2 CO2 during low fire are outside the recommended combus tion ...