PRESTIGE SOLO & EXCELLENCE IGNITION KIT - INSTALLATION INSTRUCTIONS

1.3.  Initial task

Write down all the appliance settings and the chosen 

configuration for reference before bringing any change 

to the appliance. A reference table is provided on the 

last page of this document. 

1.4.  Boiler preparation

1.4.1  Required Tools and Material

• 

Flathead and Phillips Screwdriver

• 

Torx 20  Wrench

1.4.2  Combustion Chamber Insulation

1.  The  Ignition kit is shipped with a new combustion 

chamber 2in1 insulation/gasket. This may need to 

be installed with the new ignition kit. Boilers with 

serial number before those listed in the table below 

need to be replaced.

Model

Serial Number

PA80

PA132660

PA110

PA131779

PA155

PA13163

PA175

PA127120

PA250

PA137281

PA299

PA127280

PA399

PA128691

PA Excellence

PA131819

2.  If the Prestige serial number is after the listed num-

ber above, no change is required to the insulation/

gasket.

3.  Refer to the installation manual for installation pro-

cedure.

1.4.3  Procedure

4.  Turn the boiler off by pressing the power switch
5.  Disconnect electrical power at the external electric box

• 

Avoid electrical shock by disconnecting the 

electrical supply prior to performing any operation 

on the internal parts of the boiler. 

• 

Before any operation on the internal components 

of the appliance, allow the appliance to cool 

down to room temperature. Some components 

can be very hot.

• 

Failure to comply will result in substantial property 

damage, serious injury, or death.

 

DANGER

6.  Shut off the gas supply to the boiler at the main manual 

shut off valve.

7.  Remove boiler front panel to access the electronic 

board and the burner (See 

Fig. 2)

x 3

Fig. 2 - Prestige Solo & Excellence - Front Panel Removal

8.  Disconnect the black ignition cable from the front 

of the electronic box.

9.  Open the front cover of the electronic box (See 

Fig. 3)

Discard the cover.

1

2

Fig. 3 - Prestige Solo & Excellence - Removal of Control Box  

Front Cover

10.  Disconnect the igniter wiring from the igniter. Discard. 
11.  Using the Torx wrench, release two screws and 

remove the igniter and gasket from the burner 

mounting plate. Discard all.

If the gasket is stuck on the igniter support, use 

a flat head tool and release it carefully from the 

surface. Be careful not to scratch the surface.

NOTICE

Содержание Prestige PA 299 V1

Страница 1: ...ds 1 1 V1 and V2 PA299 and PA399 Boilers There are two different blower venturi arrangements that result in two different required ignition kits The separate blower and venturi V2 configuration ap pli...

Страница 2: ...ed 2 6 PB Sticker S N adaptation not shown 1 7 Combustion Chamber Insulation gasket not shown 1 Fig 1 Prestige Solo Excellence Ignition Kit Gr Br W Bk V 4 5 6 1 2 3 X15 X11 6 7 8 9 10 1 2 3 4 5 3 4 1...

Страница 3: ...ing the power switch 5 Disconnect electrical power at the external electric box Avoid electrical shock by disconnecting the electrical supply prior to performing any operation on the internal parts of...

Страница 4: ...spark generator with bracket B on the blower clamp A aligning bracket hole with blow er clamp hole See Fig 6 6 Reinstall the blower clamp screw A to secure the spark generator bracket to the blower cl...

Страница 5: ...x front cover See Fig 11 13 Connect the brown ionization cable at the front of the control box See Fig 11 14 Reuse the Control Board box to ship the old control board to Triangle Tube and using the pr...

Страница 6: ...Excellence PCB Wiring Pre modification Protect bare pins with Fast on connectors then store connector and wiring at the rear of control box with retaining clips 4 5 6 1 2 3 X15 X11 6 7 8 9 10 1 2 3 4...

Страница 7: ...7 PRESTIGE SOLO EXCELLENCE IGNITION KIT INSTALLATION INSTRUCTIONS A B Fig 15 Prestige Solo Excellence Combustion chamber 2 in 1 Insulation Damages...

Страница 8: ...21 5 22 6 23 8 25 10 11 24 ALARM Pump 3 Flex Relay 3 to be set to MIX OPEN MIX OPEN ON ONLY if no additional pump is con nected to Flex Relay 3 P3 If a pump is connected please con tact your TTP assi...

Страница 9: ...Off DHW ECS SWW Off MIX OPEN Off MIX CLOSE Off ERROR On FLAME Off Save Exit Boiler Settings Boiler Settings Prestige Model Solo Lockout Temp 105 C Modbus Address 1 Pump settings Pump Settings Current...

Отзывы: