TriangleTube CCRKIT32 Скачать руководство пользователя страница 4

Challenger Blower 

Replacement Kit

4

6.  With the gas orifice in place, reconnect the gas pipe 

brass nut to the gas valve. See Fig. 2.

7.  If previously removed, reinstall the vent pipe.

WARNING

!

When reassembling the vent pipe, ensure all gaskets 
are in place and correctly installed. Ensure all associat-
ed internal joints are complete, tight and secure. Fail-
ure to comply can result in flue gas leakage resulting 
in severe personal injury.

8.  Reattach the wire harness plugs to the blower mo-

tor.

9.  Replace the front jacket panel and secure with the 

two Phillips head mounting screws at the control 

panel. 

10. Open the main shutoff valve to the gas supply pip-

ing. Before placing the Challenger back into service 

check and test all gas piping connections for leaks. 

Repair leaks if found. 

WARNING

!

If any gas leaks are found or suspected, shut down the 
appliance immediately. Use a gas detection device or 
bubble test to locate the source of the gas leak and 
repair at once. Do not operate the appliance until the 
leak is corrected. Failure to comply with this proce-
dure can result in substantial property damage, seri-
ous injury, or death. 

11. Turn on power at the main service switch and re-

turn to service. 

12. Perform a combustion analysis by measuring CO2 

or O2 and CO during both low and high firing rates. 

The combustion readings must be within the range 

listed in Table 1. The CO level must not exceed 100 

ppm for natural gas and 150 ppm for propane gas 

when combustion is correct.

Perform the following procedure to manually place 

the burner into high fire.  Press both the “

” and 

“+” buttons simultaneously once until the operating 

display shows “h” or twice until the operating dis-

play shows “H” for high fire.

Perform the following procedure to manually place 

the burner into low fire.  Press both the “

” and 

“-” buttons simultaneously until operating display 

shows “L”.

Table 1:  Acceptable Combustion levels

Combustion Levels  Natural Gas 

Propane Gas

H

igh F

ire 

DOOR OFF*

CO2 Range 

9% - 10.1% 

10.5% - 11.1%

CO2 Target 

9.0%

10.8%

O2 Range 

3.0% - 5% 

4.1% - 5.0%

O2 Target 

5.0%

4.5%

Lo

w F

ire

CO2 Range

0% - 0.4% <H.F. 

9%

0% - 0.4% <H.F. 

10.5% min.

O2 Range

0% - 0.6% > H.F. 

5.0% max.

0% - 0.6% > H.F. 

5.0% max.

CO Max.

100 ppm

150 ppm

* Door On can raise the maximum allowable CO2 by 0.4 

or lower the minimum O2 by 0.6

WARNING

!

If the combustion levels are not within the range giv-
en in Table 1, shut the appliance down and contact Tri-
angle Tube Technical Support. Failure to comply with 
this requirement can result in substantial property 
damage, serious injury, or death.

2019-05 Challenger Blower Replacement Instructions 

Revised 02/27/2019

Содержание CCRKIT32

Страница 1: ... injury or death WARNING For your safety the boiler may be extremely hot Ensure the boiler has properly cooled prior to ser vicing Failure to do so can cause severe personal injury WARNING Failure to follow instructions below can result in severe personal injury or damage if ignored Instructions are for a qualified installer ser vice technician only Read all instructions before proceeding Follow i...

Страница 2: ...retaining ring attaching it to the condensate pan then slide the pipe up and out of the condensate pan Pull the vent pipe out and down to remove 5 Loosen the gas pipe brass nut at the gas valve Set aside the orifice and o ring for reinstallation See Fig 2 Fig 2 Gas Orifice location NOTICE Do not discard the gas orifice and gasket as they will be re used 6 Remove the 2 M5 flange nuts attaching the ...

Страница 3: ...the venturi and gas pipe are properly seated 3 Insert the venturi clip into the blower housing En sure the venturi clip is holding the venturi and gas pipe in place by lightly pulling on the gas pipe NOTICE Do NOT force the clip into a flush fit with the blower surface Fig 4 Venturi assembly installation 4 Seat the blower orifice if required and blower outlet gasket onto the blower flange Position...

Страница 4: ... turn to service 12 Perform a combustion analysis by measuring CO2 or O2 and CO during both low and high firing rates The combustion readings must be within the range listed in Table 1 The CO level must not exceed 100 ppm for natural gas and 150 ppm for propane gas when combustion is correct Perform the following procedure to manually place the burner into high fire Press both the and buttons simu...

Отзывы: