4.3 Storage
During storage, the drive must remain inside its original packaging which complies with the ESD
standard.
The storage conditions must respect the IEC 61800-1 standard.
TSD80/TSD130
Temperature
-25°C (-13°F) and +55°C (+131°F), max. rate of change 20K / hour
Humidity
between 5 and 95% without condensation
Storage duration
Less than 2 years:
without restriction.
More than 2 years:
capacitors must be reformed before setting up
and operating the drive. To do this, remove
all electrical connections and apply DC for
about 30 minutes to the DC-Bus terminals (J1).
Table 7: Conditions during Storage.
4.4 Packaging
Triamec drives come in a recyclable cardboard box with the following content
TSD80/TSD130
Dimensions
W x D x H
343 x 228 x 58mm
3
Labeling
label on box
Delivery content
Servo drive
TSD80or TSD130
Online documentation and setup software 'TAM System Explorer'
on CD-ROM
Mating connectors X1, X2, X3, X4, X30, X31, X40, X41
Table 8: Packaging.
Accessories
must be ordered separately. A list of accessories and options can be found in chapter 3.2.
4.5 Disassembling
Observe the sequence below, if a servo drive has to be disassembled (e.g. for replacement).
Action
DANGER
1. Switch off the power supply that supplies the drive. Wait at least ten minutes after switching
off the power supply before touching potentially live sections of the equipment (e.g. contacts).
To be sure, measure the voltage in the DC Bus link and wait until it has fallen below 40V.
Remove the wiring. Disconnect the earth (ground) connection at last.
CAUTION
2. During operation the heat sink of the servo drive may reach high temperatures. Before
touching the device, check the temperature and wait until it has cooled down below 40°C
(104°F).