Installation Procedure
SAFETY
INSTRUCT! ONS
.&WARNING
The entire machine safety system
must be tested at the start of every shift. Machine testing
should include: (1) proper machine operation and stopping
capability; and (2) verification of proper installation and
settings of all point of operation guards and devices before
the operation is released for production.
ACAUTION
Pylons should be mounted in a
manner so that any authorized personnel can change
the mounting or location.
A CAUTION
Additional guards may be required
to prevent the operator from standing between the light
curtain and the point of operation.
1)
Locate pylons so the working zone is guarded from
reaching around, over, and under the PPG Series system
to the point of operation or hazard zone. Mounting of
pylons should be shock mounted (see Safeguarding with
Mechanical Guards, Appendix A).
Receiver Pylon
ACAUTION
Current Boards (Rev 3 and newer):
Kl, K2 use only Safety Relays PN# 32-101.
Setup and Installation
Superlight VI Safety Light Curtain
;
For location of pylons in
re atIon to t e azard area, refer to the Federal
Register 1910.217 (c) (3) (iii) (e) and Table 0-10
(both available in Appendix A).
2) Determine the safety distance of the light curtain
from the point of operation using the
ANSI
Standard B11.19-2003 (see Appendix A).
3) Refer to the Dimensional Information section
(Page 4) for the mechanical layout of the pylons.
4) Refer to the Wiring Diagram section (Page 3)
for electrical connections.
5) Power is brought to both pylons 120VAC or
24VDC (depending on the model)@60Hz. The
Ground Terminal must be connected to a good
ground connection, not conduit. A bad ground
may keep the light curtain from going GREEN
in an electrically noisy environment.
6) Refer to the Light Curtain Test Procedure
section (Page M-2) to ensure the light curtain
is functioning properly.
Terminal
Description
Aux relay N.C. (closed when RED) (optional)
2
Aux relay common
3
Aux relay N.O. (close when Green) (optional)
Machinery with a
single STOP
circuit:
.,�
.....
4
Cincinnati Interface (Ground or Float = Normal
Operation, 24vdc = Guard RED)
5
External relay checking input
Wire STOP circuit into and out of Kl Terminals
Machinery with
dual STOP
circuits:
Wire STOP circuit #1 into and out of Kl Terminals
Wire STOP circuit #2 into and out of K2 Terminals
ACAUTION
Older Boards (Rev 2 and older):
Kl, K2 use only Safety Relays PN# 32-001
Machinery with a
single STOP
circuit:
Wire STOP circuit into Kl, Install a jumper wire
between Kl and K2 Terminals, out of K2 Terminal
If there is no Terminals between Kl & K2, the
jumper is under the PCB already
Machinery with
dual STOP
circuits:
Wire STOP circuit #1 into and out of Kl Terminals
Wire STOP circuit #2 into and out of K2 Terminals
If there is no Terminals between Kl & K2, you
must call the factory to get Terminals, and cut the
jumper under the PCB.
Ill I
lii1 •
aJ
.
,
Tl
"
"L i
�
• • • • •
• • • • •
I
····· ·I •• · ••
1
.
4. 5
6
8
..
.
ACAUTION
All Board Versions:
K3 use only Relay
PN# 32-001 for auxiliary
ur oses onl
3
(must tie to terminal #6 when not in use)
6
External relay checking power
L,N,G
Line, Neutral, Ground
K1
Safety relay (closed when Green)
K2
Safety relay (closed when Green)
NOTICE
Ground Terminal must be
connected to a good ground connection, not con
duit. A bad ground may keep the light curtain from
going GREEN in an electrically noisy environment.
Emitter Pylon
(120vac)
(24 vdc optional)
Input Power
1010
1
0
1
• • •
L N G