Trerice TA901 I/P Transducer

Page 2

DANGER, WARNING, CAUTION and NOTE statements

Refers to conditions or hazards which could result in serious personal injury or death.

Refers to conditions or hazards which could result in personal injury.

Refers to conditions or hazards which could result in equipment or property damage.

Alerts you to facts or special instructions.

ALL DANGER, WARNING, AND CAUTION NOTICES MUST BE COMPLIED WITH IN FULL

SPECIFICATIONS

Min./Max. Supply Pressure

Minimum - 3 psig (

0.21 BAR

)

 

Above maximum output

 

Maximum 

- 100 psig (7

 BAR

)

Supply Pressure Sensitivity

 

0.1% of span per psig

 

(<±

 

0.15% of span per 1

 BAR

)

Linearity

<± 0.75% of span

Repeatability

< 0.5% of span

Hysteresis

< 1.0% of span

Flow Rate

4.5 scfm (

127 Nl/min

) at

 

25 

psig (1

.7 BAR

) supply

12.0 scfm (

340 Nl/min

) at

 

100 

psig (

6.8 BAR

) supply

Maximum Air Consumption

.05 scfm (

1.4 Nl/min

) midrange typical

Port Sizes

1/4 NPT (Pneumatic)
1/2 NPT (Electric)

1. DESCRIPTION and INSTALLATION

1.1 Description

1.1.1

 

This 

I/P Current to Pressure Transducer converts a current or voltage input signal to a linearly proportional

pneumatic output pressure. This versatile instrument is designed for control applications that require a high
degree of reliability and repeatability at an economical cost.

1.2 Principle of Operation

1.2.1

 

Th

is

 I/P Transducer is a force balance device in which a coil is suspended in the field of a magnet by a flex-

ure. Current flowing through the coil generates axial movement of the coil and flexure. The flexure moves towards

 

the nozzle and creates back pressure which acts as a pilot pressure to an integral booster relay. Input signal

 

increases cause proportional output pressure increases.

Zero and Span are calibrated by turning adjust screws on the front face of the unit. Adjustment of the zero screw 
repositions the nozzle relative to the flexure. The span adjustment is a potentiometer that controls the amount of 
current through the coil.

.

1.3 Mounting

1.3.1

Unit may be pipe, panel, or bracket mounted. Mounting may be at any angle, though may require field 

adjustment. High external vibration may cause output fluctuations. Mounting in a vibration-free area is recommended.

NOTE

CAUTION

WARNING

DANGER