Series 91000

•••   Self-Operating Regulators

Operation, Installation & Maintenance Manual

Page 5

INSTALLATION

Deciding the LOCATION for the Regulator

The regulator should be installed in an accessible location on horizontal piping.  Possible damage from moving
parts, splashing of corrosive liquids, vibration, heat, fluid pulsations, etc., should be considered in deciding the
location.  Similar consideration should also be given to the connecting tubing and bulb.  The tubing for the
special purpose “Small Bulb” option (9” long) should be located where the temperature is at least 20°F cooler
than the control point.

REGULATOR Installation

A strainer should be installed just ahead of the regulator to protect the valve from dirt, scale or foreign
matter which could interfere with the seating  of the valve.  A three valve by-pass installed around the
regulator will facilitate removal for service.

Blow out all pipe lines thoroughly to eliminate all foreign material from the system.  Pipe thread compound
should be applied only on external or male pipe threads (not on the union nut threads).  Install the regulator
in a vertical position with the flow direction through the valve corresponding to the flow arrow cast on the
valve body.  Tighten tailpieces of unions on piping first and then tighten both valve union nuts
simultaneously.

Positioning the Indicator

The Model 91400 Self-Operating Regulator contains an integral dial thermometer that can be rotated 330°
about the vertical axis for best readability.  To prevent thermal system damage, a rotation stop is built in. 
If the stop prevents a proper viewing angle from being achieved, rotate the thermometer in the opposite
direction.  This thermometer can also be tilted up or down for maximum readability.  To tilt, loosen the 
clevis screw/nut, tilt thermometer to desired angle and re-tighten the clevis screw/nut combination.

NOTE:  ACTUAL BYPASS
LINE SHOULD BE LEVEL
WITH OR ABOVE 
PROCESS LINE.

Содержание 91000 Series

Страница 1: ...Series 91000 Self Operating Temperature Regulators Operation Installation Maintenance Manual Indicating and Non indicating Model 91400 Shown Instruction Manual IH 2...

Страница 2: ...Action 10 11 Valve Body Assembly 12 13 Reversing the Valve Action 14 15 3 Way Regulator Installation Maintenance 16 Model 91600 Safety Type Installation Maintenance 17 Typical Applications 18 19 Typic...

Страница 3: ...65 F 5 to 20 C N A 30 to 115 F C R02 40 to 90 F 5 to 30 C 65 to 85 F 20 to 30 C N A 50 to 140 F C R03 30 to 115 F 0 to 45 C 85 to 110 F 30 to 45 C 50 to 80 F 10 to 25 C 30 to 115 F C R04 50 to 140 F...

Страница 4: ...ture sensing bulbs on a regulator are not recommended for direct insertion into any pressurized system The use of a Thermowell is strongly encouraged Brass and Steel Thermowells are rated to 500 PSIG...

Страница 5: ...moval for service Blow out all pipe lines thoroughly to eliminate all foreign material from the system Pipe thread compound should be applied only on external or male pipe threads not on the union nut...

Страница 6: ...s this may require a small by pass flow line around the valve to maintain representative system temperatures at the sensing bulb SENSING BULB INSTALLATION To install a union connected sensing bulb rem...

Страница 7: ...HE SMALL HEX STEM JAM NUTS THIS IS A CRITICAL SETTING FOR THE PROPER SEATING STROKE OF THE REGULATOR PLACING THE REGULATOR INTO OPERATION AND SETTING THE CONTROL POINT Figure 1 Model 91000 shown CAUTI...

Страница 8: ...nal drop of oil on the stem will aid in eliminating mineral deposits and maintaining a free running stem for accurate regulation See Figure Figure 2 Removing any sharp mineral crystals from the stem w...

Страница 9: ...Remove all accumulations of mineral deposits or other debris before re building A 4375 diameter reamer is ideal to remove deposits from the bonnet if the bonnet is removed from the body A 45 diameter...

Страница 10: ...completely off of and below the scale then the thermal system is most likely dead and needs to be replaced On all other model of actuators 1 Record the current adjusting screw setting relative to the...

Страница 11: ...up There should be at least 1 4 of motion 3 If no motion is seen the valve is jammed A Remove valve from line and inspect for debris caught between the valve seat and the valve plug preventing the val...

Страница 12: ...D POLISHED PORTION OF THE VALVE STEM 5 Remove the Bonnet Nut holding the actuator to the valve with a 11 2 wrench 6 Unscrew the valve stem from the actuator stem by turning the entire valve body If th...

Страница 13: ...screw in up to reference number 8 5 Place valve stem up through the Yoke and Bonnet Nut 6 Thread the valve stem into the actuator stem A Use a 5 16 wrench to hold or turn the actuator stem B Use a 3...

Страница 14: ...gulator these valves are used for HEATING Stem Out To Close valves close with temperature decrease and outward stem motion On a regulator these valves are used for COOLING 1 2 through 2 Bronze Body va...

Страница 15: ...Thread the stem in until the cross pin holes in the stem and the valve plug are centered upon each other B Check the centering by making an extra 1 2 turn to see if this improves the centering If not...

Страница 16: ...ses as temperature increases Port A is the common port and remains open G LOWER PORT B UPPER PORT C COMMON PORT A F E for Mixing or Diverting MIXING FLOW DIAGRAM DIVERTING FLOW DIAGRAM TEMPERATURE COL...

Страница 17: ...Report basis and the regulator will be thoroughly inspected and tested Model 91600 SPECIAL INSTRUCTIONS 91600 Stem The actuator stem in a Model 91600 actuator does not turn When removing or attaching...

Страница 18: ...on Using a Self Op 3 Way Diverting Valve Typical Plumbing for a Self Op 3 Way Mixing Valve HEATING Connect Upper Port C to Water Glycol Return and Lower Port B to Heat Exchanger COOLING Connect Upper...

Страница 19: ...UEL OIL STORAGE TANK PUMP Teflon covered sensor and tubing Sensor attached into tank with pipe hangers STEAM COILS HEAT EXCHANGER Influence Side Process Side STEAM RETURN TO TRAP THEN BOILER STEAM RET...

Страница 20: ...e average temperature location or add agitation 3 Tube system assembly has lost 3 Replace the thermal actuator pressure fill 4 Stem adjustment too short 4 Readjust See Figure 6 Closes with temperature...

Страница 21: ...sure too low 5 Increase supply pressure 6 Heat exchanger not large enough 6 Replace with proper capacity 7 Faulty or undersized steam trap 7 Install trap of proper capacity 8 Stem moves into body to o...

Страница 22: ...Page 22 Notes Adjustments Stem Dimensions Maintenance Logs...

Страница 23: ...Page 23 Notes Adjustments Stem Dimensions Maintenance Logs...

Страница 24: ...ustomer Service and International Sales 12950 W Eight Mile Road Oak Park Michigan 48237 Toll Free 1 888 873 7423 Fax 1 248 399 7246 www TRERICE com Regional Sales Offices Northeast Central East Midwes...

Отзывы: