Safety Note

Ÿ

Turn off the power before connecting any module or wire. The correct 
power supply voltage (48 – 57 V DC) is listed on the product label. 
Check the voltage of your power source to make sure that you are 
using the correct part. Do NOT use voltage greater than 48 – 57 V 
DC, as specified on the product label. 

Ÿ

Calculate the maximum possible current in each power wire and 
common wire. Observe all electrical codes dictating the maximum 
current allowable for each wire size. If the current surpasses the 
maximum ratings, the wiring could overheat, causing serious 
damage to your equipment.

!

Optional

: The switch chassis can also be connected to a known 

grounding point for additional safety and protection (grounding wire is 
not included)

GND

Содержание TI-PG1284i

Страница 1: ...TI PG1284i Quick Installation Guide...

Страница 2: ...Table of Content 1 English 1 Before You Start 2 Quick Reference 3 Hardware Installation 4 Hardware Configuration 5 Additional Information...

Страница 3: ...s TI PG1284i Quick Installation Guide CD ROM User s Guide Console cable Minimum Requirements Power supply ex model TI S24048 Networked computer RJ 45 Network Cable 1 GND Optional Equipment 35 mm DIN R...

Страница 4: ...will receive the highest priority and port 8 will receive the lowest priority The ports with lower priority will have its PoE function disabled until more than 7 5 watts of power becomes available 2 P...

Страница 5: ...ws Note Polarities must match 2 Attach the terminal block to the unit 3 3 Rotate the TI PG1284i downward towards the rail to lock it into place You will know it is secure when you hear the click 4 To...

Страница 6: ...8 57 V DC as specified on the product label Calculate the maximum possible current in each power wire and common wire Observe all electrical codes dictating the maximum current allowable for each wire...

Страница 7: ...in the subnet of 192 168 10 x e g 192 168 10 25 and a subnet mask of 255 255 255 0 3 Open your web browser type the IP address of the switch in the address bar and then press Enter The default IP add...

Страница 8: ...ngs General Settings 6 Configure the switch to match the requirements of your network Then click Apply Apply 7 Click Save Save 8 Connect a network source and devices to the switch Check the LEDs to co...

Страница 9: ...mary power and Terminal Block RPS for secondary power source to be a redundant power Input 2 DIP Switch 1 2 NO PWR RPS ON Primary power alarm enabled OFF Primary power alarm disabled PWR ON Redundant...

Страница 10: ...linking Data is transmitting receiving LINK ACT Orange Network speed at 10 100 Mbps OFF Port disconnected ON SFP port link up at 1000 Mbps OFF Port disconnected SFP Slots 9 12 ON PoE PoE device is con...

Страница 11: ...ives Product Information Product Name Model Number TI PG1284i Trade Name TRENDnet 12 Port Hardened Industrial Gigabit PoE Layer 2 Managed DIN Rail Switch EMC Person responsible for this declaration Da...

Страница 12: ...que sus productos carecen de defectos en el material y la fabricaci n en condiciones de uso y funcionamiento normales Los periodos espec ficos de garant a figuran en cada unadelasp ginasdeproductodel...

Страница 13: ...using a mains power supply To disconnect devices from the mains supply remove the device itself or its mains plug from the power outlet The power outlet and all connected network devices should be eas...

Страница 14: ...isticas del adaptador de alimentac n necesario para su funcionamiento El uso de un adaptador distinto al mencionado puede producir da os fisicos y o da os al equipo conectado El adaptador de alimentac...

Отзывы: