TREND TBTS Скачать руководство пользователя страница 4

TB/TS Thermistor Room Temperature Sensors Installation Instructions TG200604 Issue 2, 08/03/2011

TB/TS 

Installation Instructions

Please send any comments about this or any other Trend technical publication to [email protected]

© 2011 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division 

of Honeywell Technologies Sàrl, Ecublens, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation 

to notify any person of such revisions or changes.

Trend control Systems limited

Albery House, Springfield Road, Horsham, West Sussex,  RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com

Trend control System uSa

6670 185

th

  Avenue  NE,  Redmond,  Washington  98052,  USA.  Tel:(425)  869-3900  Fax:(425)  869-8445  www.trendcontrols.com

 

 T 

WEEE Directive :

At the end of their useful life the 

packaging and product should be 

disposed of by a suitable recycling 

centre.

Do not dispose of with normal household waste.

Do not burn.

Test system

InSTallaTIon 

(continued)

Set up IQ Sensor types

9

If IQl

10

If IQ

IQL Strategy Installation 

Instructions

It is recommended to use SET (software tool) for the setting of sensor type modules. For all 

IQ2 series controllers with firmware version 2.1 or greater, or IQ3 series controllers, select the 

appropriate SET Unique Sensor Reference from the following:

Thermistor:

 

Thermistor TBTS

 (°C)

  

Thermistor TBTS F

 (°F)

  

Alternatively, set scaling mode to 5 (characters) and enter scaling manually, as defined in the 

table below.

Note that for IQ3 the scaling mode and exponent (E) do not need to be set up. 

For all other IQ controllers see Sensor Scaling Reference Card TB100521A

DISpoSal

units

°c

°F

Y

Input type

1 (thermistor volts)

E

Exponent

3

u

Upper

50

122

l

Lower

-5

23

p

Points

6

x

Ix

ox (°c)

ox (°F)

1

2.641

50

122

2

3.47

40

104

3

4.46

30

86

4

6.663

10

50

5

7.668

0

32

6

8.102

-5

23

Отзывы: