background image

TB/TS/KO, /OS, /KOS, /KOF, /KOSF Installation Instructions TG200606 Issue 3, 26-Aug-2014 3

Installation Instructions 

TB/TS/KO, /OS, /KOS, /KOF, /KOSF

9

Set up strategies 

8

assemble unit

3 InSTallaTIOn 

(continued)

Wire to controller

7

*** 

Note that /KO, /OS, /KOS, /KOF, /KOSF cannot 

be used by IQ211 (although they can be used by 

IQ212

)

TB/TS Data Sheet (TA200603)

or

For  /KO,  /OS,  /KOS,  /KOF,  /KOSF  options  configure  the 

controller strategy using the pre-configured strategy in SET’s 

Strategy  Library  (TB  TS  KOSF),  and  only  use  the  options 

required.. If this is not used write your own strategy, see data 

sheet for suggested strategy.

1    2   3   4   5   6

Note that these options (TB/TS/KO, /OS, 

/KOF, /KOSF) cannot be used with IQLs; 

use options TB/TS, TB/TS/K, /KE, or /KEF 

with IQLs.

OPTIOn

COnneCT 

TeRMInalS

TB/TS

1, 2

TB/TS/K

1, 2, 3

TB/TS/KO***

1, 2, 3, 4**

TB/TS/OS***

1, 2, 3*, 4**

TB/TS/KOS***

1, 2, 3, 4**

TB/TS/KOF***

1, 2, 3, 4**, 5, 6

TB/TS/KOSF***

1, 2, 3, 4, 5, 6

Terminal size 0.5 to 2.5 mm

2

 (20 to 14 AWG)

Note that the IQ recommended limits may need to be changed 

to suit mains supply voltage and auxiliary supply loading, or a 

24  Vdc regulated supply can be used.

‘click’

4

3

5

6

OUT

0 V

IN

COM (0 V)

+24 V

IN

COM (0 V)

SENSOR

/K, /O

/S

/F

analogue input
(thermistor T)

auxiliary supply

analogue output
(voltage V)

analogue input
(voltage V)

see note ** below

Knob/Override

Status/Power

+24 V

Fan

IQ

1

2

IN

TB/TS

analogue input
(thermistor T)

COM (0V)

0V

Temperature

1

1

* Note that the override function operates via the knob connection so 

that for the /OS option, the Knob connection must be made.

**Note that the override function takes its power from the Status/

Power connection so the Status/Power connection (terminal 4) must 

also be made for /KO and /KOF versions. For these /KO and /KOF 

versions, connect the Status/Power to 10 Vdc or 24 Vdc. If status 

indication is fitted but not used (i.e. /OS, /KOS, /KOSF used as /O, 

/KO, or /KOF), 10 Vdc must be used  e.g. from dummy analogue 

output.

IQecos  with  fixed  strategies  must  be 

connected  as  described  in  the  relevant 

strategy data sheet.

For IQecos with fixed strategies ignore steps 9 and 10 and proceed to step 11

Отзывы: