IQXIO I/O Expansion Module Installation Instructions TG201447 Issue 1, 24-Mar-2020 5

Installation Instructions IQXIO

7

Connect Universal Inputs / Outputs 

(if required)

IO/20

3 INSTALLATION 

(continued)

Terminal size:  

2.0 to 1.0 mm

2

 (14 to 18 AWG). 

Terminal screw torque: 0.4 to 0.5 Nm (3.5 to 4.4 lbf-in).

Caution

: Do not connect ‘C’ (0V) terminals to earth (ground).

Thermistor / Resistive input

Current input

Voltage input

Volt-free / Digital input

n

n

n

n

n

n

ensure correct 

polarity

S

+

-

n

n

n

0 to 10 Vdc

S

n

n

n

Externally powered

External 

Power 

Supply

ensure correct 

polarity

S

n

n

n

Loop powered (using 20 Vdc AUX output supply, 100mA maximum)

ensure correct 

polarity

Common C terminal is linked 

internally to AUX supply common - 

no additional connection is required

volt free 

contact

open 

collector

n

n

n

ensure correct 

polarity

logic

circuit

330 μA

TTL / 

CMOS

0V

3

1

1

5

4

2

2

IN 0V

IN 0V

IN 0V

IN 0V

0V IN

0V IN

0V IN

29

13

30

14

31

15

32

33

34

35

36

C

14

5

13

4

C

12

3

11

5

2

2

C

C

10

4

1

1

1

2

3

4

5

8

6

9

7

10

11

12

13

14

15

16

C

C

1

2

3

C

4

5

20V

AUX

20V

AUX

C

C

6

7

8

9

Input Connection Examples

Output Connection Example

Universal Inputs (UI)

I/O signal types are defined in controller configuration

0 to

300k

W

e.g.

20kNTC

PT1000

Output Type

Load

0 to 10 Vdc, 10 mA max.

≥1k

W

4 to 20 mA

≤550

W

X

IO/7

IQXIO/20 (9 channels)

1

2

3

4

5

6

C

C

1

2

3

20V

AUX

IQXIO/7 (3 channels)

Universal Input/

Output (UIO)

IQXIO/20 (5 channels)

IQXIO/7 (2 channels)

Содержание IQXIO

Страница 1: ...lation practices e g HSE Memorandum of Guidance on Electricity at Work Regulations 1989 USA National Electric Code CONTENTS 1 Box Contents 1 2 Storing 1 3 Installation 1 4 Field Maintenance 8 5 Dispos...

Страница 2: ...Do not mount in areas where acid fumes or other deteriorating vapours can attack the metal parts of the controller or in areas where escaping gas or other explosive vapours are present IO 20 Note For...

Страница 3: ...if using direct connection 67 mm 2 64 click Remote Connection Additional or remote modules require a separate power supply see step 6 and be interconnected via an I O Data Bus cable see step 5 All sup...

Страница 4: ...necting device for the unit Do not position the equipment so that the disconnecting device is difficult to operate Terminal size 2 0 to 1 0 mm2 14 to 18 AWG Terminal screw torque 0 4 to 0 5 Nm 3 5 to...

Страница 5: ...100mA maximum ensure correct polarity Common C terminal is linked internally to AUX supply common no additional connection is required volt free contact open collector n n n ensure correct polarity l...

Страница 6: ...B on IQXIO 20 module Voltage Range As supply source see below A1 A3 B5 A2 A4 B6 17 18 19 20 21 22 23 24 25 26 27 28 0V 0V 0V 1 2 3 4 5 6 A B 24V AUX n n n n n n Or from an additional external source s...

Страница 7: ...ules must be given a unique address between 1 and 8 before applying power Set switches 1 2 4 and 8 to be ON h or OFF i as shown in the table below Module Address 1 2 4 8 Module Address 1 2 4 8 0 off i...

Страница 8: ...e maintenance 6 CHINA HAZARDOUS SUBSTANCE TABLE Component Name Hazardous Substances Pb Lead Pb Hg Mercury Hg Cd Cadmium Cd Cr6 Chromium VI Compounds Cr6 PBB Polybrominated Biphenyls PBB PBDE Polybromi...

Отзывы: