IQView4 Installation Instructions TG201038 Issue 4, 25/11/2009
IQView4
Installation Instructions
Read licence
Read and agree to End User
Licence Agreement
(see Section 4)
close panel
Switch on
1
3
2
IQ1xx with 25 Way D type female
IQ3, IQ2xx, (some IQ1xx with RJ11)
IQ1xx with 5 way in line plug
SERVICE
24V
SERVICE
24V
SERVICE
24V
IQ3, IQ2xx, IQ1xx
IQ1xx,
IQ1xx
IQView4
IQView4
IQView4
RJ11
RD/SDU-IQ2COMMS CABLE/3M
EJ105046 (supplied with IQView4)
RD/SDU-IQ2COMMS CABLE/3M
EJ105046 (supplied with IQView4)
RD/SDU-IQ2COMMS CABLE/3M
EJ105046 (supplied with IQView4)
RJ11
RJ11
25 way D male
RJ11
RD/SDU-ADAPTOR IQ1xx+ (additional)
RD/SDU-ADAPTOR IQ1xx (additional)
5 in line socket
connect RS232
9
SERVICE
24V
3.1 Installation - Mounting
(continued)
Note that IQView4 cannot be connected to a controller with local supervisor port already used (e.g. wireless sensor reciever
XW/RIQ, NDP, IQView (RS232), or local PC) or to /ADL, ATM or XNC220 controllers.
Note that Supervisor Port Address should be set to zero (default).
Note that for IQ1xx controllers with a separate CNC board, the Address module Local address parameter, R(L), must be set
up correctly so that the IQView4 can identify the controller.
3.2 Installation - Configuration
24 V AUX
24 V AUX
RS232
RS232
RS232
Do not
connect
Do not
connect
Note that the RD/SDU-IQ2COMMS CABLE/10M, EJ105047, 10 m
cable, may be used instead of the RD/SDU-IQ2COMMS CABLE/3M,
EJ105046, 3 m cable, but it is not UL listed, and is not supplied with
the IQView4.