IQ422, IQ4NC/00, IQ4NC/12 Controllers Installation Instructions - Configuring TG201265 Issue 12, 24-Jul-2018
11
InstallationInstructions-Configuring
IQ422, IQ4NC/00, IQ4NC/12
3
Make Connection
(continued)
3
CONNECT TO IQ4XX
(continued)
RJ11
RJ11
24 Vdc
Supply
XW/R/IQ
Must use external 24 V supply
Connect Directly to Controller
RD-IQ, SDU-xcite, IQView4 via Local Supervisor Port
(RS232)
Connect via Ethernet Network
▪
Ensure the IQ4xx is connected to the Ethernet network.
▪
Connect the other device (e.g. network display or PC) to
same Ethernet network and ensure an IP connection is
available between it and the IQ4xx.
▪
To make a connection with SET, a supervisor or display
ensure a vCNC is available in a Trend device on the same
Ethernet Trend network and connect to the vCNC as
described in the supplied documentation.
Note: If connecting with IP Tool, the PC should be on the
same Ethernet segment as the IQ4xx.
▪
To make a connection with a web browser run a web
browser on the PC and access the IQ4xx IP address or
host name.
XW/R/IQ wireless sensor receiver via Local Supervisor Port
(RS232)
PC Connection use
Notes
IPTool
ü
SET
ü
Requires vCNC
Web Browser
ü
Supervisor
ü
Requires vCNC
Note: Set local supervisor port address to ‘0’ (default) as
communication is limited to the IQ422, IQ4NC/00, IQ4NC/12.
IQView4 requires its own power
supply.
RJ11
RJ11
RD/SDU-
IQ2COMMSCABLE3M
RJ11
RJ11
IQView4
RD-IQ
SDU-xcite
Standard Ethernet cable
(Cat 5e twisted pair)
max 100 m (109 yds)
Hub / Switch
Router
RJ45
RD-WMB via Wallbus Port
RD-WMB
Twisted Pair Cable
maximum length 60 m (200 ft)
IQView8
PC