VI. d - REMOVING THE POWERPACK:
1. Remove the louver panel by first removing the four
(4) black plastic plugs that are located in each corner
of the powerpack louver assembly.  These conceal four
(4) Phillips head screws which hold the louver in place.
Remove these screws as well, and set both them and
the plastic plugs aside (see figure 6).

2. Remove louver assembly (see Figures 7a & 7b).

3. Remove the power cord blank-off cover and retainer.

4. Disconnect power and mullion heater plugs from
chassis.

5. Remove interior plenum on back wall of cabinet in-
terior, air duct transition, supply air duct and return air
grill.

6. Remove the four (4) Phillips head screws securing
the powerpack to the cabinet front (see figure 8).

7. Grasp the condenser fan mounting brace and pull
the powerpack up and out gently.  This allows the unit
to come forward enough so as to enable the powerpack
to be pulled out of the top and bottom lip brackets (see
figure 9).

VI. a - ADJUSTING THE SHELVES (cont

d):

rotating clockwise.  Make sure the pin is securely tight-
ened down.  Do not over tighten.  Slide the shelf into
its new position, and replace the white plastic covers
into the holes vacated by the shelf pins.

VI. b - REHINGING THE DOOR(S):
All UC models are supplied standard with a re-hinging
feature. To begin rehinging the door,  first disconnect
power to the unit.

Lift the door off its hinge cams and place aside.  Next
remove the plugs covering the holes of the re-hinging
feature located on the side opposite of the present
hinge location.

Remove the existing hinge bodies by removing the
three (3) Phillips head screws which secure each to
the cabinet face.  Replace the hinges in their new loca-
tion, and replace the screws.

Remove the hinge cover from the door half of the hinge
by sliding it downwards.  Next remove the hinge hard-
ware from the door by removing the three (3) Phillips
head screws which secure each to the door.

Turn the door around to its new position, and replace
the hinge hardware to the door in the existing screw
holes, but in the opposite position.  Replace the screws
to secure the hinge hardware in place.

Position the door in its new location by lowering the
door hinge hardware into the hinge cams located on
the cabinet face.

VI. c - REMOVING THE DRAWERS:
Each drawer on UL equipment stand models are de-
signed to accommodate two (2) 12

 x 20

 x 4

 deep

pans, front to back.  SBS models can acommodate two
(2) 12

 x 20

 x 4

 deep pans, side by side.

Drawers are supplied standard with divider bars which
allow it be configured for use with half, third  and quar-
ter size pans.  These are shipped along with the cabi-
net, taped together and secured inside of the bottom
drawer.  No bar is required for use with full-size pans.
In all cases, pans are supplied by others.

The drawers can be easily removed by first pulling the
drawer out to its full extension.  Next, lift the drawer
vertically to dis-engage the drawer slide wheel from
the slide frame and remove the entire drawer.  To re-
place the drawer, reverse the process.

VI. d - REMOVING & RELOCATING THE POWERPACK:
To remove the powerpack for maintenance, servicing
or to relocate it to the other side, first disconnect power
to the unit.  If the unit is equipped with an optional
stainless steel top, this will also first have to be re-
moved.   Then follow these directions:

-5-

VI. MISC. OPERATIONS

Fig. 6

Fig. 8

Содержание UC Series

Страница 1: ...er to the model and serial number found on the name tag affixed to the unit Should you need service however call us on our toll free number 800 825 8220 between 7 30 am and 4 30 pm CST Monday thru Friday It is our pleasure to help and assist you in every possible way Traulsen Co Inc OWNER S MANUAL Instructions for the installation operation and maintenance of all Traulsen UC Series Full Size Under...

Страница 2: ... 10 g Customer Service Parameters Page 11 h Adjusting Thermostat Set Point High Page 11 i Adjusting Thermostat Set Point Low Page 12 j Changing The Temperature Scale Page 12 k Setting The 24 Hour Clock Page 13 l Setting The Date Page 14 m Setting Daylight Savings Time Page 14 n Starting A Manual Defrost Page 15 o Setting Defrost Lockouts Page 16 p Adjusting The Dewpoint Compensation Factor Page 17...

Страница 3: ...all surfaces To remove the wooden pallet first if at all possible we suggest that the cabinet remain bolted to the pallet during all transportation to the point of final installa tion The bolts can then be removed with a 3 4 socket wrench Avoid laying the unit on its front side or back for removal of the pallet NOTE Traulsen does not recommend laying the unit down on its front side or back However...

Страница 4: ...uring freezer defrost operation heat is confined to the coil enclosure to prevent any significant rise in temperature within the food zone The fan delay con 3 III INSTALLATION continued III d INSTALLING LEGS OR CASTERS cont d Please note that Traulsen units are not designed to be moved while on legs If the unit requires moving a pallet jack or forklift should be used to prevent dam age For install...

Страница 5: ... warm air into the food storage area Second to prevent any conden sation on the defrost coil from being blown into the food storage area The INTELA TRAUL control is set from the factory to terminate defrost at 20 minutes in the event of a sen sor failure This setting should never be tampered with without first consulting the factory IV c CONDENSATE REMOVAL Both refrigerator and freezer units are s...

Страница 6: ...3 Phillips head screws which secure each to the cabinet face Replace the hinges in their new loca tion and replace the screws Remove the hinge cover from the door half of the hinge by sliding it downwards Next remove the hinge hard ware from the door by removing the three 3 Phillips head screws which secure each to the door Turn the door around to its new position and replace the hinge hardware to...

Страница 7: ...Fig 7b Fig 7a Remove Louver Assembly VI MISC OPERATIONS cont d 6 Fig 9 Removing Power Pack ...

Страница 8: ...with HAACP standards Records alarm events Records diagnostic test of each sensor every 24 hours Records failed security attempts Records door open cycles Records defrost cycles refrigerator and freezer models only Note The 24 hour clock and the date must be set for the above information to be recorded at the correct time and date Communication Ability An RS485 port is available as a means of retri...

Страница 9: ...en the unit regains power after an outage To turn off the audible alarm and or clear the visual text press the alarm cancel button You must reset the clock and date if you are using any defrost lockouts or are retrieving the information from the data storage memory See Setting The 24 Hour Clock page 12 and Setting the Date page 13 System Leak The audible alarm will sound and the display will read ...

Страница 10: ...e order 3 DIGIT RED LED DISPLAY HOLDER CLIP 377 60038 00 EVAP COIL NOT USED CABINET AIR NOT USED TRANSFORMER RS485 DEFROST COMPRESSOR RELAY POWER LINE IN 2 DOOR HEATER EVAP BLOWER RELAY POWER IN LINE 1 INTELA TRAUL HORIZONTAL CONTROLLER 337 60062 00 HOLDER CLIP HORN DISCHARGE LINE COIL SENSOR 337 60071 00 refrigerator freezer only CABINET SENSOR 337 60069 00 DISCHARGE SENSOR 337 60072 00 refrigera...

Страница 11: ...e following instructions Press the set button The display will read Customer Service Access Press the set button The display will show three zeros with the left zero flashing Press the set button The display will show three zeros with the center zero flashing Press the down arrow key to sequence through F E d C b A 9 8 7 etc When you reach A press set The display will show zero A zero with the rig...

Страница 12: ... of the desired cabinet temperature range Typically freezers will range from 3 F to 0 F 19 C to 18 C and refrigerators will range from 36 F to 40 F 2 C to 4 C for this parameter setting This parameter is preset at the factory and does not have to be adjusted unless the customer chooses to do so Note Set Point Low and Set Point High cannot be set to the same temperature There will be at least 1 2 d...

Страница 13: ...n the display shows the temperature you want press the set button The display will then read Thermostat Set Point High You can use the up or down arrow keys to scroll to the next parameter or press the alarm cancel button to exit VII j Changing The Temperature Scale The temperature scale determines if the temperature displayed will be in degrees Fahrenheit or degrees Celsius Follow the instruction...

Страница 14: ... 5 00 a m H11 11 00 a m H17 5 00 p m H23 11 00 p m H06 6 00 a m H12 12 00 p m H18 6 00 p m H24 12 00 a m Follow the instructions to enter the customer access code on page 9 When the control displays Thermostat Set High press the down arrow key until the control display reads Clock Press the set button The display will show Hours The right two numbers will be flashing Use the arrow keys to set the ...

Страница 15: ...ay is displayed press the set button The display will then read Thermostat Set Point High You can use the up or down arrow keys to scroll to the next parameter press the alarm cancel button to exit VII m SETTING DAYLIGHT SAVINGS TIME This parameter is preset at the factory to automatically adjust the 24 hour clock for Daylight Savings Time Follow the instructions to enter the customer access code ...

Страница 16: ...w key YES The display will show Press the set button The display will then read Thermostat Set Point High You can use the up or down arrow keys to scroll to the next parameter or press the alarm cancel button to exit The defrost icon will be lit and the display will read when the unit is in defrost VII INTELA TRAUL continued 15 VII n STARTING A MANUAL DEFROST CYCLE SET SET NOTE Traulsen refrigerat...

Страница 17: ... 6 00 a m 120 12 00 p m 180 6 00 p m 240 12 00 a m 063 6 30 a m 123 12 30 p m 183 6 30 p m 243 12 30 a m 070 7 00 a m 130 1 00 p m 190 7 00 p m 010 1 00 a m 073 7 30 a m 133 1 30 p m 193 7 30 p m 013 1 30 a m 080 8 00 a m 140 2 00 p m 200 8 00 p m 020 2 00 a m Denotes not available A lockout can not be programmed to start at 12 00 am or 12 30 am due to conflicts with other internal programs The de...

Страница 18: ...meter or press the alarm cancel button to exit 17 VII INTELA TRAUL continued SET SET VII q SETTING THE AUDIBLE ALARM STYLE This parameter will allow the customer to turn on off the audible alarm feature on the INTELA TRAUL control The audible alarm is preset from the factory to OFF The customer can choose between an audible alarm that sounds for 3 seconds then automatically turns off or a continuo...

Страница 19: ...s to enter the customer access code on page 9 When the control displays Thermostat Set Point High press the DOWN arrow key unit the display reads Evaporator Coil Sensor or Disharge Line Sensor or press the SET button The display will read Thermostat Set Point High Press the UP or DOWN arrow keys to scroll through the parameters or press the ALARM CANCEL button to exit VII INTELA TRAUL continued 18...

Страница 20: ...antity of warm food has recently been added or the door was kept open for a long period of time in both cases allow adequate time for the cabinet to recover its normal operating temperature c INTELA TRAUL setting too high readjust per instructions on page 11 4 Food compartment is too cold a Perhaps a large quantity of very cold or frozen food has recently been added Allow adequate time for the cab...

Страница 21: ... of said control which proves to be defective Inspection by the TRAULSEN Service Department of parts claimed defective shall be final in determining warranty status The warranty is to include repair or exchange of any defective In Warranty control or part s of said control for Part s Any TRAULSEN INTELA TRAUL supplied part s found to be defective Labor The labor charges from a TRAULSEN Certified S...

Страница 22: ...uver assembly for all UL models Shelf Pin 344 24759 00 Replacement shelf pin Side Panel Exterior Stainless steel exterior side panel X OTHER X a SERVICE INFORMATION Before calling for service please check the following Is the electrical cord plugged in Is the fuse OK or circuit breaker on Is the power switch ON If after checking the above items and the unit is still not operating properly please c...

Страница 23: ...age 6 E F G Gaskets 5 H Hinge 4 5 I Internal Time Clock 6 INTELA TRAUL 3 4 5 6 17 J K L Legs 2 Louver Assembly 4 5 M Manual Defrost Cycle 14 N O P Power Supply 3 R Return Authorization 2 Room Temperature Offset 16 S Serial Tag 1 Shelf Pins 2 Shelves 2 5 Smart Recovery 6 T Thermostat Set Point High 10 Thermostat Set Point Low 11 U V Vinyl Protective Covering 2 W Warranty 19 Warranty Registration 21...

Страница 24: ...Traulsen Co Inc 4401 Blue Mound Road Fort Worth TX 76106 Phone 800 825 8220 Fax Svce 817 740 6757 Website www traulsen com HOURS OF OPERATION Monday thru Friday 7 30 am 4 30 pm CST Quality Refrigeration ...

Отзывы: