background image

10

Resetting The Control

Refers To Older Control Versions Only

If memory reaches capacity during a chill cycle there is potential that some printout data could
be incorrect (date & time).  This will reset on it’s own, however to do so manually...

FACTORY SETTINGS

VERSION 2.0

S/N:T00000A00

 RESET 

    

  

NEXT

 

STEP 6

Serial number will be

displayed.  Press NEXT.

STEP 5

FACTORY SETTINGS
menu.  Press RESET.

STEP 10

Press NEXT.

DEFROST TIME (40)  

DEFR. TEMP (50)

°

   

   

   

   

   

DEFR. INTVL (3) HR 

BACK           

NEXT

STEP 9

Press NEXT.

STEP 13

Press YES.

STEP 11

Press ENTER.

(do not change code)

S E L E C T   S U P E R V I S O R :

PRESET  SUPERVISOR

PASSWORD

 (PIN): 00

CANCEL     ENTER

BLASTING DIFF (4)

°

F

HOLDING DIFF (3)

°

ANTI-SHORT(1)     

  

    

    

BACK          

 NEXT

ENTER SECURITY CODE

FOR NEXT SETTINGS:

     

     

     

     

     

     (000000) 

               

               

               

               

               

 EXIT       

ENTER 

FACTORY SETTINGS

DO YOU WISH TO SAVE

THESE NEW SETTINGS

 NO           

YES 

STEP 1

Main Menu display press MORE

STEP 2

Press SETUP.

STEP 3

Enter PASSWORD/PIN 85.

S E L E C T   S U P E R V I S O R :

TIM SMITH

        

PASSWORD 

(PIN): 85

CANCEL     ENTER

DISPLAY WILL SHOW

SELECT SUPERVISOR screen

MAIN MENU   AIR 35

°

F

BY TEMP    BY PROD
BY TIME

08:05:01

    

MORE

MAIN MENU   08:06:01

HOLD PROD   PRINT
DEFROST        

SETUP

BACK

STEP 4

Press the top left, top

right, and bottom right buttons

at the same time.

FACTORY SETTINGS

VERSION 2.0

S/N:T00000A00

 

RESET     

  NEXT 

LABEL PRINTER (NO)

 RESET       NEXT 

LABEL PRINTER(YES)

 RESET       

NEXT 

STEP 7

Display will ask LABEL

PRINTER (NO), press the UP

arrow to select YES.

STEP 8

Press NEXT.

NEW SOFTWARE

HAS BEEN INSTALLED

SYSTEM PARAMETERS

HAVE BEEN SET!

DISPLAY WILL SHOW

MACH. MODEL (RBC)  

MACHINE SIZE(50)  

   

   

   

   

   

RESET          

EXIT

STEP 12

MACH. MODEL (RBC)  

MACHINE SIZE(50)  

   

   

   

   

   

RESET

          EXIT

14. The display will return to the MAIN

MENU. Repeat steps 1-10

15. Press EXIT.

16. Press YES.

Display will ask MACHINE SIZE.   Press RESET,
then using the UP or DOWN arrow change for
your model. For RBC50 = 50, RBC100 = 100,
RBC200 = 200.   Press EXIT.

Содержание KROGER RBC100

Страница 1: ...ng with any work you should read in its entirety the procedure you wish to perform in order to determine if you have the necessary tools and skill required to perform the procedure Procedures for which you do not have the necessary tools and or skill should not be performed TRAULSEN RBC50 RBC100 RBC200 BLAST CHILLERS service guide basic ...

Страница 2: ... 7 Verifying Control Version 8 Locating Refrigerant Leaks 9 Resetting The Control 10 Parts List 11 Interior air temperature Press to chill BY PRODUCT Press to quickly start a Chill Cycle Press to access additional menus Press to chill BY TEMP Press to start a chill cycle BY TIME Time Main Menu LEGEND Push button to left or right of any feature marked by or to select that feature Push button to lef...

Страница 3: ...c YEAR 2003 2079 d DAY OF WEEK SUNDAY SATURDAY e HOUR 0 23 f MINUTE 0 59 g DLS Daylight Savings TIme ENABLED DISABLED e LOW ALARM 30 0 5 Press the button to the left of ITEM to select between the different items Adjust the VALUE for each ITEM using the UP and DOWN buttons 6 Press ENTER to return to the MAIN MENU 2 Programming the Control How to Set Correct Date Time SYS PAR SET CLOCK ITEM MONTH VA...

Страница 4: ...emp prior to chilling Verify actual product temp with thermometer probed piece PROBLEM Previously observed expected high product temps differ from those shown on cycle data printout a See above for possible causes b Bad food probe Replace probe c Batch started incorrectly Start chill cycle according to owner s manual instructions d Moisture damage to the control Replace control PROBLEM Occasional ...

Страница 5: ... Call service d Failed coil sensor Call service e Other system problem Call service PROBLEM Continuous defrost sensor warning a Failed defrost heater Call service b Failed defrost sensor Call service PROBLEM No data available for printing or later than actual start time or start temperature data appears on cycle data printouts for a given probe a Product probe added to active chill cycle incorrect...

Страница 6: ...emble in reverse order 5 Restore power 6 If previously authorized by Traulsen insert original control in pre addressed mailer and return to Traulsen Replacing The Control Board 5 TRAULSEN RBC50 RBC100 RBC200 BLAST CHILLER BASIC SERVICE GUIDE WARNING DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AND FOLLOW PROPER LOCKOUT TAGOUT PROCEDURES Fig 1 Fig 2 Fig 3 ...

Страница 7: ...d printer 5 Re assemble in reverse order using a new printer 6 Restore power Fig 2 Fig 3 Fig 1 Printer Details LEGEND 1 Printer Power Port Red Harness 2 Printer Data Port White Harness 3 Cutting Wheel Cartridge 4 Paper Folded To Point For Easy Feed 5 Feed Roller 6 Feed Roller Tension Arm 7 Thermal Paper or Label Stock NOTE Order printer supplies from Traulsen or your local Hobart Sales Service Off...

Страница 8: ...nce of grease or water damage indicated by a green color see inset with a commercial contact cleaner This will dislodge the contamination 5 Wipe away any debris or excess contamination using a cotton swab Allow adequate time to dry 6 Reassemble the control in reverse order Repairing Moisture Damage 7 TRAULSEN RBC50 RBC100 RBC200 BLAST CHILLER BASIC SERVICE GUIDE Fig 1 Fig 2 WARNING DISCONNECT THE ...

Страница 9: ...ight and bottom right buttons at the same time 5 The control version will appear on the display SELECT SUPERVISOR PRESET SUPERVISOR PASSWORD PIN 00 CANCEL ENTER SELECT SUPERVISOR TIM SMITH PASSWORD PIN 85 CANCEL ENTER MAIN MENU AIR 35 F BY TEMP BY PROD BY TIME 08 05 01 MORE MAIN MENU 08 06 01 HOLD PROD PRINT DEFROST SETUP BACK FACTORY SETTINGS VERSION 2 0 S N T00000A00 RESET NEXT ...

Страница 10: ...erant at 100 degrees F on the P T chart see system data plate for design refrigerant 8 Open nitrogen bottle and gauge manifold valve low side and allow pressure to equalize 9 Shut off both valves and disconnect the nitrogen bottle 10 Using a leak detector check for leaks at all tubing connections a If any leaks are detected repair leak and recheck for additional leaks b If no leaks are discovered ...

Страница 11: ...EP 1 Main Menu display press MORE STEP 2 Press SETUP STEP 3 Enter PASSWORD PIN 85 SELECT SUPERVISOR TIM SMITH PASSWORD PIN 85 CANCEL ENTER DISPLAY WILL SHOW SELECT SUPERVISOR screen MAIN MENU AIR 35 F BY TEMP BY PROD BY TIME 08 05 01 MORE MAIN MENU 08 06 01 HOLD PROD PRINT DEFROST SETUP BACK STEP 4 Press the top left top right and bottom right buttons at the same time FACTORY SETTINGS VERSION 2 0 ...

Страница 12: ...C100 HORIZONTAL BREAKER CAP 345 60011 04 RBC100 VERTICAL BREAKER CAP 345 60011 05 RBC100 200 400 LOCK KEEPER 346 60018 00 RBC100 200 400 LOCK KEEPER BRACKET 346 60019 00 RBC100 200 400 SMARTCHILL CONTROL KIT SER 60461 00 RBC100 DOOR HINGED RIGHT 200 60059 00 RBC100 TRAY SLIDE 342 60014 00 RBC100 PRINTER COVER 701 60741 00 ALL MODELS STANDARD PRINTER PAPER 400 60003 00 ALL MODELS LABEL PAPER 400 60...

Отзывы: