Trane XR13 Скачать руководство пользователя страница 5

22-1790-08

5

General
Data

Product Specifications

Model No. 

1

4TTR3042A1

4TTR3048A1

4TTR3060B1

Electrical Data V/Ph/Hz 

2

208/230/1/60

208/230/1/60

208/230/1/60

Min Cir Ampacity

25

27

34

Max Fuse Size (Amps)

40

45

60

Compressor

CLIMATUFF

®

 - SCROLL

CLIMATUFF

®

 - SCROLL

CLIMATUFF

®

 - SCROLL

RL Amps - LR Amps

18.6 - 105

20.5 - 109

27.6 - 135

Outdoor Fan FL Amps

1.3

1.3

1.3

Fan HP

1/4

1/4

1/4

Fan Dia (inches)

27.6

27.6

27.6

Coil

Spine Fin™

Spine Fin™

Spine Fin™

Refrigerant R-410A

7/00-LB/OZ

7/04-LB/OZ

8/06-LB/OZ

Line Size - (in.) O.D. Gas 

3

3/4

7/8

7/8

Line Size - (in.) O.D. Liquid 

3

3/8

3/8

3/8

Charge Spec. Subcooling

13°

10°

10°

Dimensions H x W x D (Crated)

38.4 x 35.1 x 38.7

38.4 x 35.1 x 38.7

46.4 x 35.1 x 38.7

Weight - Shipping

258

261

287

Weight - Net

225

227

251

Start Components

NO

NO

YES

Sound Enclosure

NO

NO

NO

Compressor Sump Heat

NO

NO

YES

Optional Accessories:

 

4

Anti-short Cycle Timer

TAYASCT501A

 TAYASCT501A

TAYASCT501A

Evaporator Defrost Control

AY28X079

AY28X079

AY28X079

Rubber Isolator Kit

BAYISLT101

BAYISLT101

BAYISLT101

Extreme Condition Mounting Kit

BAYECMT001

BAYECMT001

BAYECMT001

Start Kit

BAYKSKT260

BAYKSKT260

Crankcase Heater Kit

BAYCCHT301

BAYCCHT301

Seacoast Kit

BAYSEAC001

BAYSEAC001

BAYSEAC001

Low Ambient Kit

BAYLOAM103

BAYLOAM103

BAYLOAM103

Refrigerant Lineset 

5

TAYREFLN7*

TAYREFLN3*

TAYREFLN3*

ARI Standard Capacity Rating Conditions

ARI STANDARD 210/240 RATING CONDITIONS 

(A) Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB

air entering outdoor coil.

(B) High Temperature Heating 47°F DB, 43°F WB air entering

outdoor coil, 70°F DB air entering indoor coil.

(C) Low Temperature Heating 17°F DB, 15°F WB air entering

outdoor coil, 70°F DB air entering indoor coil.

(D) Rated indoor airflow for heating is the same as for cooling.

ARI STANDARD 270 RATING CONDITIONS 

— (Noise rating

numbers are determined with the unit in cooling operation.)
Standard Noise Rating number is at 95°F outdoor air.

Accessory Description and Usage

Anti-Short Cycle Timer

 — Solid state timing device that

prevents compressor recycling until five (5) minutes have
elapsed after satisfying call or power interruptions. Use in area
with questionable power delivery, commercial applications, long
lineset, etc.

Evaporator Defrost Control

 — SPST Temperature actuated

switch that cycles the condenser off as indoor coil reaches
freeze-up conditions. Used for low ambient cooling to 30°F
with TXV.

Rubber Isolators

 — Five (5) large rubber donuts to isolate

condensing unit from transmitting energy into mounting frame
or pad. Use on any application where sound transmission
needs to be minimized.

Hard Start kit

 — Start capacitor and relay to assist compressor

motor startup. Use in areas with marginal power supply, on long
linesets, low ambient conditions, etc.

Extreme Condition Mount Kit

 — Bracket kits to securely

mount condensing unit to a frame or pad without removing any
panels. Use in areas with high winds, or on commercial roof
tops, etc.

Содержание XR13

Страница 1: ...Split System Cooling Product Data XR 13 4TTR3018 060 1 5 Tons PUB NO 22 1790 08...

Страница 2: ...ther proof Comfort R mode approved Glossy corrosion resistant finish Internal high low pressure and temperature protection 018 024 030 and 060 ship with start kit Liquid line filter drier Tarpaulin gr...

Страница 3: ...2 General Data 4 Product Specifications 4 A weighted Sound Power Level dB A 4 Accessory Description and Usage 5 ARI Standard Capacity Rating Conditions 5 Model Nomenclature 6 Electrical Data 7 Dimens...

Страница 4: ...ECMT001 BAYECMT001 BAYECMT001 BAYECMT001 Start Kit Crankcase Heater Kit BAYCCHT300 BAYCCHT300 BAYCCHT300 BAYCCHT300 Seacoast Kit BAYSEAC001 BAYSEAC001 BAYSEAC001 BAYSEAC001 Low Ambient Kit BAYLOAM103...

Страница 5: ...RD 210 240 RATING CONDITIONS A Cooling 80 F DB 67 F WB air entering indoor coil 95 F DB air entering outdoor coil B High Temperature Heating 47 F DB 43 F WB air entering outdoor coil 70 F DB air enter...

Страница 6: ...TU Upflow Horizontal TD Downflow Horizontal Type D 80 Premium X 90 Premium Number of Heating Stages 1 Single Stage 2 Two Stage 3 Three Stage Cabinet Width A 14 5 Cabinet Width B 17 5 Cabinet Width C...

Страница 7: ...22 1790 08 7 4TTR3018 024 030A1 036B1 4TTR3042A1 Electrical Data SCHEMATIC DIAGRAMS SEE LEGEND...

Страница 8: ...8 22 1790 08 4TTR3048A1 4TTR3060B1 Electrical Data SCHEMATIC DIAGRAMS SEE LEGEND PRINTED FROM D155205P01 REV00...

Страница 9: ...22 1790 08 9 Electrical Data SCHEMATIC DIAGRAMS LEGEND SYMBOLS...

Страница 10: ...0 8 1 4 79 3 1 8 508 20 4TTR3030A 3 1 832 32 3 4 829 32 5 8 756 29 3 4 3 4 3 8 143 5 5 8 92 3 5 8 210 8 1 4 79 3 1 8 508 20 4TTR3036B 3 1 933 36 3 4 829 32 5 8 756 29 3 4 3 4 3 8 143 5 5 8 92 3 5 8 21...

Страница 11: ...emperature and pressure protector total dipped hermetic motor and thermostatically controlled sump heater Other features include centrifugal oil pump and low vibration and noise Condenser Coil The Spi...

Страница 12: ...ber Supersedes SS PRC007 EN 2 02 Stocking Location PI Louisville Webb Mason Houston Trane has a policy of continuous product and product data improvement and it reserves the right to change design and...

Отзывы: