Section IV -  Refrigerant Piping
A. Purpose

1. Liquid line - The purpose of the liquid refrigerant line is to convey refrigerant, in the liquid state, from
the outdoor unit to the indoor unit in the cooling mode and from the indoor unit to the outdoor unit in the
heating mode.
2. Gas line - The purpose of the gas line is to convey refrigerant in the gas state and oil from the indoor unit
to the outdoor unit in the cooling mode and from the outdoor unit to the indoor unit in the heating mode.

B. Limitations:

1. The XL19i contains two compressors that share the same refrigeration circuit, however, do not operate
simultaneously. Therefore, it is crucial that refrigerant lines are properly sized and do not exceed the length
set forth in the unit’s installation manual.
2. Line length limits:

A. Gas line = 80 feet linear length / of the linear length, 25 feet may be installed vertical.
B. Liquid line = 80 feet linear length / of the linear length, 25 feet may be installed vertical.

3. No exceptions shall be allowed to these piping limitations.

C. Explanation:

1. Refrigerant lines shall not exceed 80 feet total line length. / 25 feet of the 80 feet may be vertical. .
2. Liquid subcooling may not be achieved on first stage if the liquid line exceeds 80 feet.
3. Oil return may be sacrificed during first stage operation if the gas line exceeds 80 feet.

25 Ft. Max

55 Ft. Max

80 Feet Max.

55 Ft. Max

25 Ft. Max

vertical

Pg. 18

Содержание XL19i-APG02-EN

Страница 1: ...Application Guide XL19i APG02 EN Low Outdoor Operating Temperature Unit Mounting Minimum Clearances Refrigerant Piping Limitations Trane XL19i heat pumps and cooling units...

Страница 2: ...riteriaasrelatedtotheTraneXL19i coolingunitsandheatpumps Thisbulletindiscusses I OffSeasonCoolingOperation II UnitMounting III MinimumOperatingClearances IV RefrigerantPipingLimitations ISSUEDBY Produ...

Страница 3: ...ning if the XL19i will operate at the specified conditions as well as required accessories E R U T A R E P M E T D O S E I R O S S E C C A D E R I U Q E R l e d o M 5 4 0 F 0 4 0 3 0 F 0 0 F i 9 1 L X...

Страница 4: ...e W3 Blue B Orange O R Y2 Y1 G W1 X2 B O EDR 1 EDC EDR Y1 Red R Ylow Green G White W1 White W2 White W3 Blue B EDC Heat Pump Split System andAY28X084 Evaporator Defrost Control 2TTZ9 TWE E Thermostat...

Страница 5: ...aseobservethefollowing 1 Anytimetheunitistobesupportedfromtheedge thesupportingmaterialshallextendminimumtwo inches under the perimeter of the unit s base 2 Themountingholelocationsaremoldedinthebasep...

Страница 6: ...drilled support must extend 2 from the basepan perimeter support center of unit If supporting the base pan from the perimeter the support must extend under the base pan at least 2 Trane recom mends su...

Страница 7: ...more walls of an adjacent building 3 Fences or barriers provided to reduce sound transmission or visually screen the equipment 4 Otheroutdoorunitsinamulti unitinstallation 5 A combination of the above...

Страница 8: ...ice clearance for personnel safety This distance may be increased under certain conditions Please refer to the most current edition of the National Electric Code for more information Page15ofthisdocum...

Страница 9: ...m overhang from side of unit to deck 3 minimum from top of unit to deck Outdoor Unit SIDE VIEW FrontView 3 minimum from side of unit to wall of home Outdoor Unit 2 maximum deck overhang to side of uni...

Страница 10: ...of deck 3 Minimum Clearance from side of unit to wall of structure Outdoor Unit Outdoor wall of home Deck Edge TOPVIEW ISOMETRIC VIEW Pg 10 Illustrations provided to designate required clearances Tran...

Страница 11: ...it shall have1 5 feet clearance from both walls 2 3 0 feet clearance in between units if service panels face each other this clearance may be increased to 4 0 feet per NEC 3 2 0 feet clearance from ot...

Страница 12: ...feet Consult the National Electric Code for more informationregardingminimumclearancesforworkingspaces Service Panel Service Panel 1 5 min 1 5 m i n 1 5 m i n 1 5 min 12345 12345 12345 12345 123 123 1...

Страница 13: ...elocity B For locations where the design ambient temperature exceeds 105F 1 Corner unit shall have 2 0 feet clearance from one wall and 2 5 feet clearance from the other wall 2 3 5 feet clearance in b...

Страница 14: ...be increased to 3 5 feet Please consult the 2002 or current Edition of the National Electric Code Article 110 for the most up to date information D Fence construction 1 Height shall not exceed the top...

Страница 15: ...M 3 5FT 1 2 mm 4FT Note Where the conditions are as follows Condition 1 Exposed live parts on one side and no live or grounded parts on the other side of the working space or exposed live parts on bo...

Страница 16: ...5 7 0 4 A 0 0 0 1 A 0 6 0 9 Z T T 2 5 7 0 4 A 0 0 0 1 A 0 6 0 9 Z W T 2 5 7 0 4 Required Opening CFM 300 FPM Example Given Qty of 2 units in an area surrounded by a fence on two sides and solid walls...

Страница 17: ...9 Z W T 2 4 8 7 9 4 4 1 7 3 4 1 4 3 A 0 0 0 1 A 6 3 0 9 Z T T 2 4 8 7 9 4 4 1 7 3 4 1 4 3 A 0 0 0 1 A 6 3 0 9 Z W T 2 4 8 7 9 4 4 1 7 3 4 1 4 3 A 0 0 0 1 A 8 4 0 9 Z T T 2 4 8 7 9 4 4 1 7 3 4 1 4 3 A...

Страница 18: ...however do not operate simultaneously Therefore itiscrucialthatrefrigerantlinesareproperlysizedanddonotexceedthelength setforthintheunit sinstallationmanual 2 Linelengthlimits A Gas line 80 feet linea...

Страница 19: ...Pg 19 NOTES...

Страница 20: ...trane com Literature Order Number File Number XL19i APG02 EN 03 04 Supersedes XL19i APG01 EN 01 03 Stocking Location Since Trane has a policy of continuous product improvement it reserves the right to...

Отзывы: