Wireless Zone Sensor •
BAS-SVX04A-EN
Setting the Address, Mounting, Wiring, and Associating the
Receiver and Sensor
Radio transmission considerations
•
Avoid metal barriers between the receiver and the sensor; they decrease
radio signal quality significantly (for example, plastered walls with metal
lathe or metal roof decks).
•
Avoid placing the receiver inside metal enclosures.
•
Avoid radio transmissions through thick, solid concrete walls.
•
Conduct rooftop mounting and operation of the receiver only after careful
site evaluation and confirmation.
Location Considerations for the Sensor
When selecting a location for the sensor, consider both thermal and radio
transmission characteristics of the location.
Thermal considerations
•
Avoid areas of direct sunlight.
•
Avoid areas in the direct airstream of air diffusers.
•
Avoid exterior walls and other walls that have a temperature differential
between their two sides.
•
Avoid areas close to sources of heat such as sunlight, appliances, or other
equipment.
•
Avoid drafty areas.
•
Avoid dead spots behind doors, projection screens, or corners.
Radio transmission considerations
•
Avoid metal barriers between the sensor and receiver, such as plastered walls
with metal lathe. They will decrease radio signal quality.
•
Avoid placing the sensor inside metal enclosures.
•
Avoid radio transmissions through thick, solid concrete walls.