RT-SVX34R-EN
89
W
WA
AR
RN
NIIN
NG
G
L
Liiv
ve
e E
Elle
eccttrriicca
all C
Co
om
mp
po
on
ne
en
nttss!!
F
Fa
aiillu
urre
e tto
o ffo
ollllo
ow
w a
allll e
elle
eccttrriicca
all ssa
affe
etty
y p
prre
ecca
au
uttiio
on
nss
w
wh
he
en
n e
ex
xp
po
osse
ed
d tto
o lliiv
ve
e e
elle
eccttrriicca
all cco
om
mp
po
on
ne
en
nttss cco
ou
ulld
d
rre
essu
ulltt iin
n d
de
ea
atth
h o
orr sse
erriio
ou
uss iin
njju
urry
y..
W
Wh
he
en
n iitt iiss n
ne
ecce
essssa
arry
y tto
o w
wo
orrkk w
wiitth
h lliiv
ve
e e
elle
eccttrriicca
all
cco
om
mp
po
on
ne
en
nttss,, h
ha
av
ve
e a
a q
qu
ua
alliiffiie
ed
d lliicce
en
nsse
ed
d e
elle
eccttrriicciia
an
n
o
orr o
otth
he
err iin
nd
diiv
viid
du
ua
all w
wh
ho
o h
ha
ass b
be
ee
en
n p
prro
op
pe
errlly
y ttrra
aiin
ne
ed
d
iin
n h
ha
an
nd
dlliin
ng
g lliiv
ve
e e
elle
eccttrriicca
all cco
om
mp
po
on
ne
en
nttss p
pe
errffo
orrm
m
tth
he
esse
e tta
asskkss..
H
HIIG
GH
H V
VO
OL
LT
TA
AG
GE
E IIS
S P
PR
RE
ES
SE
EN
NT
T A
AT
T T
TE
ER
RM
MIIN
NA
AL
L
B
BL
LO
OC
CK
K H
HT
TB
B1
1 O
OR
R U
UN
NIIT
T D
DIIS
SC
CO
ON
NN
NE
EC
CT
T S
SW
WIIT
TC
CH
H..
3. Remove the mist eliminator retainer bracket and the
mist eliminators from the fresh air hood.
4. Remove the five (5) screws in the top and bottom of
each fresh air damper located inside the hood area.
5. Using the Service Test guide in
—
, momentarily jump across the test terminals
one time for constant volume applications, or three
consecutive times for a variable air volume
application, to start the Minimum Ventilation Test.
6. With the supply fan “On” and rotating in the proper
direction, measure the return duct static pressure.
7. Using
, enter the desired amount of
fresh air and the return air static pressure reading to
obtain the proper damper opening dimension.
8. Loosen the adjustment screws on each side of the
damper and slide it downward to the required
opening.
9. Tighten the adjustment screws and re-install the
mist eliminators and the mist eliminator retainer
bracket.
10. Open the main power disconnect or the unit
mounted disconnect switch to shut the unit off and
to reset the RTRM.
11. Before closing the disconnect switch, ensure that
the compressor discharge service valve(s) and
suction service valve(s) are backseated.
Table 65.
Damper adjustment
Damper Opening (in.)
Return Air Static Pressure - Inches w.c.
Damper #1
Damper #2
-0.20
-0.40
-0.60
-0.80
-1.00
-1.20
-1.40
-1.60
2
0
430
590
725
840
950
1040
1120
740
4
0
780
1080
1330
1545
1730
1890
2035
2170
6
0
1185
1620
1990
2300
2575
2815
3030
3240
8
0
1530
2110
2600
3025
3390
3705
3985
4240
10
0
1930
2655
3270
3800
4250
4650
5005
5345
10
2
2295
3165
3910
4545
5095
5575
6010
6415
10
4
2660
3650
4510
5255
5905
6480
6995
7470
10
6
3010
4150
5130
5965
6690
7330
7900
8440
10
8
3345
4600
5680
6610
7410
8120
8765
9365
10
10
3690
5125
6350
7395
8295
9075
9775
10420
Starting the Compressor
Optional service valves must be fully opened before
startup (suction and discharge line).
N
No
otte
e:: Suction and discharge service valves are
standard on high efficiency units and 40-50T
standard efficiency constant volume units.
N
NO
OT
TIIC
CE
E
C
Co
om
mp
prre
esssso
orr F
Fa
aiillu
urre
e!!
F
Fa
aiillu
urre
e tto
o ffo
ollllo
ow
w iin
nssttrru
uccttiio
on
n b
be
ello
ow
w cco
ou
ulld
d rre
essu
ulltt iin
n
cco
om
mp
prre
esssso
orr ffa
aiillu
urre
e..
U
Un
niitt m
mu
usstt b
be
e p
po
ow
we
erre
ed
d a
an
nd
d ccrra
an
nkkcca
asse
e h
he
ea
atte
errss
e
en
ne
errg
giizze
ed
d a
att lle
ea
asstt 8
8 h
ho
ou
urrss B
BE
EF
FO
OR
RE
E cco
om
mp
prre
esssso
orrss
a
arre
e sstta
arrtte
ed
d..
Starting 27.5 to 35 Ton Standard
Efficiency Units
Install a set of service gauges onto the suction and
discharge service ports. To start the compressor test,
close the main power disconnect switch or the unit
mounted disconnect switch.
Jump across the “Test terminals” on LTB1 or toggle
the test switch three consecutive times if it is a constant
volume application, or five times if it is a variable air
volume application for two to three seconds per jump.
Refer to
-
for the Cooling Test
sequence.
Содержание Voyager Commercial