88
RT-SVX34R-EN
Table 62.
27.5 - 35 Ton horizontal economizer (O/A) -
ultra-low-leak economizer (continued)
Sys-
tem
De-
sign
CFM
Return Air Duct Return Air Damper
Static (in WC)
0.2-
0
0.4-
0
0.6-
0
0.8-
0
1.0-
0
1.2-
0
1.4-
0
stroke limit setting % on OA damper
actuator
11500
100
80
50
45
40
40
40
12000
100
100
60
45
40
40
40
12500
100
100
60
50
45
40
40
13000
100
100
60
50
45
40
40
13500
100
100
70
50
45
45
40
14000
100
100
70
60
50
45
40
14500
100
100
80
60
50
45
45
Table 63.
40 - 50 Ton downflow economizer (O/A) -
ultra-low-leak economizer
Sys-
tem
De-
sign
CFM
Return Air Duct Return Air Damper
Static (in WC)
0.2-
0
0.4-
0
0.6-
0
0.8-
0
1.0-
0
1.2-
0
1.4-
0
stroke limit setting % on OA damper
actuator
12000
100
100
65
60
55
55
55
12500
100
100
65
60
60
55
55
13000
100
100
75
65
60
55
55
13500
100
100
75
65
60
60
55
14000
100
100
75
65
65
60
55
14500
100
100
75
75
65
60
60
15000
100
100
100
75
65
60
60
15500
100
100
100
75
65
60
60
16000
100
100
100
75
65
65
60
16500
100
100
100
75
75
65
60
17000
100
100
100
75
75
65
65
17500
100
100
100
100
75
65
65
18000
100
100
100
100
75
65
65
18500
100
100
100
100
75
75
65
19000
100
100
100
100
75
75
65
19500
100
100
100
100
75
75
75
20000
100
100
100
100
100
75
75
Table 64.
40 - 50 Ton horizontal economizer (O/A) -
ultra-low-leak economizer
Sys-
tem
De-
sign
CFM
Return Air Duct Return Air Damper
Static (in WC)
0.2-
0
0.4-
0
0.6-
0
0.8-
0
1.0-
0
1.2-
0
1.4-
0
stroke limit setting % on OA damper
actuator
12000
100
80
50
45
40
40
40
12500
100
80
60
50
45
40
40
13000
100
100
60
50
45
40
40
13500
100
100
60
50
45
40
40
14000
100
100
70
50
45
45
40
14500
100
100
70
60
50
45
45
15000
100
100
80
60
50
45
45
15500
100
100
80
60
50
50
45
16000
100
100
100
70
60
50
45
16500
100
100
100
70
60
50
45
17000
100
100
100
80
60
50
50
17500
100
100
100
80
60
50
50
18000
100
100
100
80
70
60
50
18500
100
100
100
100
70
60
50
19000
100
100
100
100
80
60
50
19500
100
100
100
100
80
70
50
20000
100
100
100
100
80
70
60
Manual Outside Air Damper
Units ordered with the 25% manual outside air option
have two slidable dampers. By adjusting one or both,
the desired amount of fresh air entering the system can
be obtained.
To adjust the outside air damper;
1. Turn the “System” selection switch to the “Off”
position and the “Fan” selection switch (if
applicable) to the “Auto” position.
2. Close the disconnect switch or circuit protector
switch that provides the supply power to the unit's
power terminal block or the unit factory mounted
disconnect switch.