RT-SVX34R-EN
87
switch is set back to its original default position - Y
= 0 - same direction as spring return. (See
Figure 59.
Actuator stroke limit adjustment
9
Philips screwdriver
Angle of Rotation
Limiter
Scale Shows % of
Full Stroke
Figure 60.
Actuator for OA damper - Downflow
Actuator for Downflow
OA Damper
Figure 61.
Actuator for OA damper - horizontal
Actuator for Horizontal OA Damper
Figure 62.
Actuator auto-scaling feature details
Control Reversing Switch
Must Be Set to Match Spring
Return Direction
Table 61.
27.5 - 35 Ton downflow economizer (O/A) -
ultra-low leak economizer
Sys-
tem
De-
sign
CFM
Return Air Duct Return Air Damper
Static (in WC)
0.2-
0
0.4-
0
0.6-
0
0.8-
0
1.0-
0
1.2-
0
1.4-
0
stroke limit setting % on OA damper
actuator
8000
75
55
55
55
55
55
55
8500
75
60
55
55
55
55
55
9500
100
65
55
55
55
55
55
10000
100
65
60
55
55
55
55
10500
100
65
60
60
55
55
55
11000
100
75
65
60
55
55
55
11500
100
75
65
60
55
55
55
12000
100
100
65
60
55
55
55
12500
100
100
65
60
60
55
55
13000
100
100
75
75
65
60
55
Table 62.
27.5 - 35 Ton horizontal economizer (O/A) -
ultra-low-leak economizer
Sys-
tem
De-
sign
CFM
Return Air Duct Return Air Damper
Static (in WC)
0.2-
0
0.4-
0
0.6-
0
0.8-
0
1.0-
0
1.2-
0
1.4-
0
stroke limit setting % on OA damper
actuator
8000
100
45
40
40
40
40
40
8500
100
45
40
40
40
40
40
9000
100
50
40
40
40
40
40
9500
100
50
45
40
40
40
40
10000
100
60
50
40
40
40
40
11000
100
60
50
45
40
40
40