Installation - Electrical
80
UNT-SVX07E-EN
Refer to
Table 26
for the wire size range and maximum
wiring distance for each device.
Recommendation: Do not bundle or run interconnection
wiring in parallel with or in the same conduit with any
high-voltage wires (110 V or greater). Exposure of
interconnection wiring to high voltage wiring, inductive
loads, or RF transmitters may cause radio frequency
interference (RFI). In addition, improper separation may
cause electrical noise problems. Therefore, use shielded
wire (Belden 83559/83562 or equivalent) in applications
that require a high degree of noise immunity. Connect the
shield to the chassis ground and tape at the other end.
Note:
Do not connect any sensor or input circuit to an
external ground connection.
Table 26. Maximum wiring distances for low voltage
controls (ft)
Device
Wire Size
Range
Fan Speed Switch
14–22 AWG
500
Zone Sensor
16–22 AWG
200
Table 27.
Free discharge and high static ECMs
programmed to standard ECM mode
Unit
Size
115 Volt
208–230 Volt
277 Volt
FLA
HP
FLA
HP
FLA
HP
1
2
1
2
1
2
1
2
1
2
1
2
2
3.1
0.22
1.8
0.22
1.6
0.24
3
3.1
0.22
1.8
0.22
1.6
0.24
4
3.1
0.22
1.8
0.22
1.6
0.24
6
3.1
0.22
1.8
0.22
1.6
0.24
8
3.1
0.22
1.8
0.22
1.6
0.24
10
3.1 3.1 0.22 0.22 1.8 1.8 0.22 0.22 1.6 1.6 0.24 0.24
12
3.1 3.1 0.22 0.22 1.8 1.8 0.22 0.22 1.6 1.6 0.24 0.24
Table 28. Free discharge ECMs programmed to reduced
FLA mode
Unit
Size
115 Volt
208–230 Volt
277 Volt
FLA
HP
FLA
HP
FLA
HP
1
2
1
2
1
2
1
2
1
2
1
2
2
0.6
0.22
0.4
0.22
0.3
0.24
3
0.6
0.22
0.4
0.22
0.3
0.24
4
0.8
0.22
0.6
0.22
0.4
0.24
6
1.1
0.22
0.8
0.22
0.6
0.24
8
1.6
0.22
1.1
0.22
0.8
0.24
10
0.7 1.2 0.22 0.22 0.5 0.8 0.22 0.22 0.4 0.6 0.24 0.24
12
0.7 1.3 0.22 0.22 0.5 0.9 0.22 0.22 0.4 0.7 0.24 0.24
Table 29. High static ECMs programmed to reduced FLA
mode
Unit
Size
115 Volt
208–230 Volt
277 Volt
FLA
HP
FLA
HP
FLA
HP
1
2
1
2
1
2
1
2
1
2
1
2
2
1.3
0.22
0.9
0.22
0.7
0.24
3
1.3
0.22
0.9
0.22
0.7
0.24
4
1.7
0.22
1.2
0.22
0.9
0.24
6
2.3
0.22
1.6
0.22
1.2
0.24
8
3.1
0.22
1.8
0.22
1.5
0.24
10
1.4
2
0.22 0.22 1 1.4 0.22 0.22 0.7 1.1 0.24 0.24
12
1.5 2.8 0.22 0.22 1.1 1.8 0.22 0.22 0.8 1.4 0.24 0.24
Table 30. Low vertical free discharge ECMs
Unit Size
115 Volt
RPM
FLA
HP
H
M
L
3
3.1
0.22 1090
770
560
4
3.1
0.22
1090
750
560
6
3.1
0.22
1115
760
560
Note:
Actual rpm will vary with application and configuration.
Table 31.
Lowboy vertical free discharge ECMs
programmed with reduced FLA mode
Unit Size
115 Volt
RPM
FLA
HP
H
M
L
3
0.5
0.22
1090
770
560
4
0.8
0.22
1090
750
560
6
1
0.22
1115
760
560
Note:
Actual rpm will vary with application and configuration.
Table 32. Unit RPM
Unit
Size
Free Discharge—Units
with 2-Row Coils
Free Discharge—Units with
3- and 4-Row Coils
H
M
L
H
M
L
2
980
840
655
980
840
655
3
980
780
580
1080
800
600
4
1050
780
580
1080
800
600
6
1030
780
580
1080
800
600
8
1080
800
600
1080
800
600
10
1050
780
580
1080
800
600
1030
780
580
1080
800
600
12
1050
780
580
1080
800
600
1080
800
600
1080
800
600
Unit
Size
High Static—Units with
2-Row Coils
High Static—Units with 3-
and 4-Row Coils
H
M
L
H
M
L
2
1480
1110
865
1480
1110
865
3
1400
1175
860
1500
1355
1110
4
1475
1315
1070
1580
1375
1240
6
1400
1070
855
1475
1285
975
8
1475
1285
975
1475
1285
975
10
1475
1315
1070
1580
1375
1240
1400
1070
855
1475
1285
975
12
1475
1315
1070
1580
1375
1240
1475
1285
975
1475
1285
975
Note:
Actual rpm will vary with application and configuration.