Figure 5
Ceiling Hanger Bracket
Installation for Vertical
Air Delivery
Diffuser Options
Optional diffusers lend added air pattern versatility to individual vertical down blown installations as shown in illustrations.
Description
Used On
Model
No.
Max.
Mtg. Ht.
Dim. A
Dim. B
Diffuser Pattern
1. Louver Diffuser
(Standard) Louvers can be
individually adjusted for
rectangular coverage over
doorways as an air curtain
or to meet rectangular floor
pattern heating
requirements.
3.3 & 5.0 KW
7.5 & 10.0 KW
15.0 & 20.0 KW
25.0 & 30.0 KW
40.0 & 50.0 KW
STD
STD
STD
STD
STD
9’ (2.7 M)
12’ (3.7 M)
18’ (5.5 M)
22’ (6.7 M)
24’ (7.3 M)
20’ ( 6.1 M)
40’ (12.2 M)
52’ (15.8 M)
75’ (22.9 M)
84’ (25.6 M)
10’ ( 3.0 M)
22’ ( 6.7 M)
30’ ( 9.1M)
42’ (12.8 M)
47’ (14.3 M)
2. General Distribution
(No Diffuser)
Trane’s Airchute Venturi
permits general downflow
air pattern distribution as
required at a higher
mounting height.
3.3 & 5.0 KW
7.5 & 10.0 KW
15.0 & 20.0 KW
25.0 & 30.0 KW
40.0 & 50.0 KW
N/R
N/R
N/R
N/R
N/R
9’ (2.7 M)
12’ (3.7 M)
18’ (5.5 M)
22’ (6.7 M)
24’ (7.3 M)
15’ ( 4.6 M)
30’ ( 9.1 M)
40’ (12.2 M)
55’ (16.8 M)
64’ (19.5 M)
3. Anemostat Diffuser
(Optional)
For application where draft
restriction is required at
lower unit mounting heights.
3.3 & 5.0 KW
7.5 & 10.0 KW
15.0 & 20.0 KW
25.0 & 30.0 KW
40.0 & 50.0 KW
N/A
AD5120
AD5120
AD5150
AD5150
— —
10’ ( 3.0 M)
15’ (4.6 M)
17’ (5.2 M)
20’ (6.1 M)
— —
30’ ( 9.1 M)
38’ (11.6 M)
50’ (15.2 M)
60’ (18.3 M)
4. Louver Cone Diffuser
(Optional)
Individually adjustable
blades permit increased
floor coverage at 45° open.
Additional throw is
accomplished when blades
are 90° vertical. Allow
higher mounting heights.
3.3 & 5.0 KW
7.5 & 10.0 KW
15.0 & 20.0 KW
25.0 & 30.0 KW
40.0 & 50.0 KW
N/A
RD5120
RD5120
RD5150
RD5150
45° 90°
— U —
10’ 3.0M 14’ 4.3M
14’ 4.3M 21’ 6.4M
20’ 6.1M 30’ 9.1M
18’ 5.5M 28’ 8.5M
45° 90°
— —
36’ 11.0M 30’ 9.1M
42’ 12.8M 35’ 10.7M
62’ 18.9M 44’ 13.4M
68’ 20.7M 54’ 16.5M
STD = Standard N/R = None Required N/A = Not Applicable
A
A
A
A
B
Installation
12
UHEC-IM-7A