Trane TTV Скачать руководство пользователя страница 10

10

TTV-IOM-R410A

Maintenance

WARNING:

  DISCONNECT  ELECTRICAL  PO WER

SOURCE AND SECURE IN DISCONNECTED POSITION
BEFORE SERVICING THE UNIT. FAILURE TO DO SO MAY
RESULT  IN  PERSONAL  INJURY  OR  DEATH  FROM
ELECTRICAL SHOCK.

Monthly Inspection

1. Check condition of air filters and replace them if necessary.

2. Check the drain pan to be sure that it is clean and free to

carry the flow of condensate through the drain line.

3. Check the coil surface for cleanliness. Clean if necessary.

Yearly Inspection

1. Replace filters.

2. Check  coil  surface.  Clean  by  vaccuming  or  flushing  with

cold water. Do not use steam or hot water. High pressure
may damage coil.

3. Carry out checks as detailed in inspection checklist in the

Operation Section.

4. Inspect the condition of the evaporator fan belt and replace

if necessary. The belts fitted to TTV units cannot achieve
design performance without the correct tensioning.

5. Check condition of vibration isolators, replace if there is any

sign of wear, loosening or material deterioration.

6. Check  fan  bearings  for  noisy  operation  and  excessive

lubricant leakage. Replace if necessary.

7. Inspect the condensate drain pan and condensate piping

to make sure they are clear and will carry away all water.

8. Inspect the control panel wiring to make sure connections

are tight and insulation is intact.

Change / Clean Filters

Change  or  clean  air  filters  at  least  twice  a  year.  Filters  will
require more frequent care under high load conditions or dirty
air. A clogged air filters reduces airflow, cooling capacity and
increases energy usage.

To clean permanent filters, remove the filter media and wash it
in water to remove dust, dirt and lint; allow to dry thoroughly
before re-installing in the units. Do not rub or wring.

Permanent  filters  can  also  be  cleaned  by  blowing  with
compressed air in opposite direction of filter airflow.

Belt Maintenance

Clean fan belts and pullies with a dry cloth. Oil and grease
must  be  kept  off  belts. The  use  of  a  belt  dressing  is  not
recommended. When replacing belts, use a matched set.

Do not force belts onto pullies, but adjust motor position to
allow mounting and then re-tighten.

Figure 3 : Belt Tension Measurement

To  measure  belt  tension,  use  a  belt  tensioner  as  shown  in
Figure 3. Determine actual deflection by depressing one belt
with the belt tensioner and then adjust the belt tension to the
correct pounds force and tighten all setscrews to the proper
torques.

Deflection

Force

na

p

S

Содержание TTV

Страница 1: ...s and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe...

Страница 2: ...ly Fan Motor kW 5 15 Supply Fan Motor kW Digit 11 Minor Design Sequence Digit 12 0 No Discharge Plenum A 1st Minor Design Sequence Digit 13 A Internal Filter Rack 1 Filter B External Filter Rack 2 Fil...

Страница 3: ...TTV IOM R410A 3 Contents Model Nomenclature System Precaution General Information General Data Installation Operation Start Up Maintenance Dimensional Data Electrical Wiring 2 4 5 6 8 9 10 12 23...

Страница 4: ...ing leakage of water etc Be sure to cut off the main power in case of setting up the indoor electronic control P C board or wiring works It could cause an electri shock Any presence of foreign substan...

Страница 5: ...d mail Notify the local Trane Sales Office Concealed damage must be reported within 15 days delivery Check the unit nameplate to confirm that the proper unit was shipped Available power supply must be...

Страница 6: ...6 TTV IOM R410A General Data TTV250 400...

Страница 7: ...TTV IOM R410A 7 General Data TTV500 800...

Страница 8: ...d on a sub base so that adequate height can be provided for a condensate drain trap However if adequate drainage can be provided the unit may be mounted directly on the floor It is recommended that ei...

Страница 9: ...connections completed Wiring is correct and in accordance with the wiring diagram with all connections secure Ground connection completed Check and retighten if necessary set screws on the drive fan p...

Страница 10: ...ondensate drain pan and condensate piping to make sure they are clear and will carry away all water 8 Inspect the control panel wiring to make sure connections are tight and insulation is intact Chang...

Страница 11: ...is 2 5 Voltage imbalance is defined as the sum of the deviation of the three voltages from the average without regard to sign divided by twice the average voltage e g if the three measured voltages ar...

Страница 12: ...RECOMMENDED 750 RECOMMENDED CLEARANCE 750 CLEARANCE RECOMMENDED 750 RECOMMENDED CLEARANCE 750 TOP VIEW SIDE VIEW 16 X 20 16 X 20 16 X 20 16 X 20 16 X 20 16 X 20 16 X 20 16 X 20 1219 13 1008 1040 COIL...

Страница 13: ...ECOMMENDED CLEARANCE 750 CLEARANCE RECOMMENDED RECOMMENDED CLEARANCE 38 DIA KNOCKOUT FOR POWER SUPPLY AND CONTROL 750 REAR VIEW REAR FRONT SIDE VIEW 16 X 20 16 X 20 16 X 20 16 X 20 16 X 20 16 X 20 16...

Страница 14: ...RECOMMENDED CLEARANCE RECOMMENDED 750 RECOMMENDED CLEARANCE 38 DIA KNOCKOUT FOR POWER SUPPLY AND CONTROL 750 TOP VIEW REAR VIEW REAR FRONT SIDE VIEW 16 X 20 16 X 20 16 X 25 15 X 25 15 X 20 15 X 20 137...

Страница 15: ...EARANCE RECOMMENDED RECOMMENDED CLEARANCE 38 DIA KNOCKOUT FOR POWER SUPPLY AND CONTROL 750 COIL TOP VIEW REAR VIEW REAR FRONT SIDE VIEW 16 X 20 16 X 20 16 X 25 15 X 25 15 X 20 15 X 20 1372 13 1008 104...

Страница 16: ...EARANCE RECOMMENDED 750 750 CLEARANCE RECOMMENDED RECOMMENDED CLEARANCE 750 RECOMMENDED CLEARANCE 750 38 DIA KNOCKOUT FOR POWER SUPPLY AND CONTROL SIDE VIEW REAR VIEW 20 X 25 16 X 25 1520 481 1008 104...

Страница 17: ...46 361 361 67 CLEARANCE RECOMMENDED 750 750 CLEARANCE RECOMMENDED RECOMMENDED CLEARANCE 750 38 DIA KNOCKOUT FOR POWER SUPPLY AND CONTROL SIDE VIEW REAR VIEW 20 X 25 16 X 25 1520 1008 1040 COIL FRONT...

Страница 18: ...ARANCE RECOMMENDED 750 750 CLEARANCE RECOMMENDED RECOMMENDED CLEARANCE 750 RECOMMENDED CLEARANCE 750 38 DIA KNOCKOUT FOR POWER SUPPLY AND CONTROL SIDE VIEW REAR VIEW 25 X 25 16 X 25 1653 569 1241 1275...

Страница 19: ...ISOMETRIC VIEW CLEARANCE RECOMMENDED 750 750 CLEARANCE RECOMMENDED RECOMMENDED CLEARANCE 750 38 DIA KNOCKOUT FOR POWER SUPPLY AND CONTROL SIDE VIEW REAR VIEW 25 X 25 16 X 25 1653 1241 1275 COIL REAR...

Страница 20: ...OMMENDED 750 CLEARANCE RECOMMENDED 750 RECOMMENDED CLEARANCE 750 RECOMMENDED CLEARANCE 750 38 DIA KNOCKOUT FOR POWER SUPPLY AND CONTROL SIDE VIEW REAR VIEW 20 X 25 1777 1241 1275 COIL REAR TOP VIEW TO...

Страница 21: ...569 452 51 486 486 CLEARANCE RECOMMENDED 750 CLEARANCE RECOMMENDED 750 RECOMMENDED CLEARANCE 750 38 DIA KNOCKOUT FOR POWER SUPPLY AND CONTROL SIDE VIEW REAR VIEW 20 X 25 1777 1241 1275 COIL REAR TOP V...

Страница 22: ...22 TTV IOM R410A Dimensional Data TTV 800 FAN ARRANGEMENT 1...

Страница 23: ...T ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH USE COPPER CONDUCTORS ONLY TO PREVENT EQUIPMEN...

Страница 24: ...ations without notice We are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor env...

Отзывы: