System Evacuation and Purge

1. The outdoor unit is supplied with

refrigerant pre-loaded in factory . The
load indicated on the nameplate is
the total amount required by a system
with a refrigerant line lenght of up to
7.5 meters (295.3”). Considering that
the outdoor unit does not require
evacuation,  except in cases of
refrigerant leakage, the suction and
liquid valves should remain closed.

2. After installation is finished, apply

vacuum in refrigerant lines and indoor
unit.

3. The system should be evacuated until

the vacuum gauge shows a reading
of  350 microns (5.9 x 10

-2

 inHg).

4. Close the vacuum pump valve, and

observe the vacuum gauge. If the
reading is more than 500 microns
(8.3 x 10

-2

 inHg) in an interval of one

minute, the evacuation is not
complete, or there is a system
leakage.

5. If the vaccum gauge does not pass

500 microns (8.3 x 10

-2

 inHg) within

the interval of one minute, the vaccum
is finished.

6. With the vacuum pump off and the

manifold closed, open the service
valves in the liquid and suction lines.

System
Evacuation

7. Replace the register and valve caps

to prevent leakages.

Table 02 - Additional refrigerant load

The refrigerant load will have to be
completed when the distance between
internal and external units is more than
7.5 meters (295.3”). Use table 2 for
recommended additional loads.

Obturator
Cap

Service

Valve

Flange Nut

Thread

Threaded

Cap

Service hose for

Schrader-type valve

Outdoor
Unit

Suction

Pressure

Liquid

Pressure

Electronic

Vacuum

Gauge

Vacuum

Pump

Suction Line

Liquid

Line

Electric

Connection

Figure 03 - Service Valve

Figure 04 - Evacuation System

Obs: Notice that the position of suction and liquid lines is different for some models, refer to page 06 - fig. 02

Tubing Sizes

Liquid - Suction

1/4" - 1/2"

26 g/m

17.5x10

-3

lbs/ft

1/4" - 5/8"

30 g/m

20.2x10

-3

lbs/ft

3/8" - 5/8"

59 g/m

39.6x10

-3

lbs/ft

3/8" - 3/4"

60 g/m

40.3x10

-3

lbs/ft

3/8" - 7/8"

62 g/m

41.7x10

-3

lbs/ft

3/8" - 1 1/8"

68 g/m

45.7x10

-3

lbs/ft

Additional Load

Содержание TTK 509 E

Страница 1: ...allation Manual Mini Split System Condensing Units TTK Horizontal Air Discharge 9 000 to 36 000 BTU h 50 60 Hz SS SVN03B EN September 2003 Models TTK 509 E TTK 518 E TTK 512 E TTK 524 E TTK 530 E TTK 536 E ...

Страница 2: ...igning the delivery note Specify any damage of the unit on the delivery note and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery Notify the dealer at the same time The unit should be totally inspected within 7 days of delivery If any concealed dam age is discovered send a registered letter of protest to the carrier within 7 days of delivery and noti...

Страница 3: ...ection using Flange Thread Type Valve System Evacuation 7 System Evacuation and Purge Service Valve 8 Multi Function Liquid Line Electric Connections 9 Electric Connection System Start Up 10 System checking before start up Dimensional Data 11 TTK 509E TTK 512E TTK 518E TTK 524E TTK 530E TTK 536E Typical Wiring Diagram 13 Wiring Interconnection 14 ...

Страница 4: ...y Characteristics 5 1 Phase 60 Hz 208 230 VAC B 1 Phase 50 Hz 208 230 VAC Digit 7 Development Sequence E Sequence Brazil Digits 5 6 Nominal Capacity Class BTU H 09 9 000 BTU h 12 12 000 BTU h 18 18 000 BTU h 24 24 000 BTU h 30 30 000 BTU h 36 36 000 BTU h Digit 4 Refrigerant and Connection Types 5 Refrigerant R 22 Service Valve Digit 3 Quantity of Refrigerating Circuits K 1 Refrigerating Circuit D...

Страница 5: ...stalled on a leveled and reinforced concrete foundation The minimum height of the concrete foundation should be 50 mm 1 97 Unit shall be fixed to the foundation with bolts not supplied 2 The concrete foundation must be positioned at least 250 mm 9 84 away from any existing wall or shrubbery 3 The minimum clearance on the air inlet sides of the unit should be 250 mm 9 84 and on the air discharge si...

Страница 6: ...n the tube WARNING Liquid line Suction line TTK 518E 524E 530E 536E TTK 509E 512E Figure 02 System detail Service access Register cap Line connection Flange Suction line Liquid line 4 Make the flange of the tube as perfect as possible 5 Apply refrigerant oil on coupling surfaces of the union of the valve with the flanged tube end before coupling them 6 Align the union center formed by the tube and...

Страница 7: ... interval of one minute the vaccum is finished 6 With the vacuum pump off and the manifold closed open the service valves in the liquid and suction lines System Evacuation 7 Replace the register and valve caps to prevent leakages Table 02 Additional refrigerant load The refrigerant load will have to be completed when the distance between internal and external units is more than 7 5 meters 295 3 Us...

Страница 8: ...n the orifice and the flare nut Step 4 The new restrictor should be appropriately lubricated and have an o ring on the perimeter The orifice and the o ring should be encapsulated in the valve body seat and for that a small crack should be heard in order to assure that the orifice was properly installed The assembly of these parts is shown in the figure below Step 5 The liquid line tube should be f...

Страница 9: ...omply with the specification in the equipment nameplate 4 Install an exclusive overcurrent protection circuit breaker for the outdoor unit It can also be used for system protection 5 Use flexible electric conduits in cases where vibrations can introduce noises inside the structure 6 Appropriate color electric wires should be used for command to allow easier connections between indoor and outdoor u...

Страница 10: ... or on the equipment Check for possible leaks at connections Check that lines are well isolated Check that passages through piping structure are well insulated Check that water drains are free Insufflation and return grids are free and unobstructed Air filters are installed and clean Use an inpected thermometer to check if the thermostat is accurate Check grounding Check for power voltage fuse cir...

Страница 11: ...id Suction Kg Lbs A B C D TTK 509E 1 4 6 35 3 8 9 5 27 60 102 4 1 60 2 4 29 1 2 31 1 22 TTK 512E 1 4 6 35 1 2 13 32 70 5 102 4 1 60 2 4 29 1 2 31 1 22 Note Diameter of Liquid and Suction Lines are in inches mm LIQUID CONNECTION SUCTION CONNECTION 700 27 6 40 1 6 4 x 12 0 5 WIRING IN 2 X 22 0 86 472 18 6 AIR FLOW 250 9 8 500 19 7 32 5 1 3 235 9 3 296 11 7 264 10 4 22 0 86 A C D B 112 4 4 5 ...

Страница 12: ... 2 12 7 48 106 30 1 2 25 0 98 20 0 78 50 1 96 71 2 8 87 5 3 5 70 2 8 TTK 524E 3 8 9 5 5 8 15 8 57 126 30 1 2 25 0 98 20 0 78 50 1 96 71 2 8 87 5 3 5 70 2 8 TTK 530E 3 8 9 5 5 8 15 8 67 148 30 1 2 25 0 98 20 0 78 50 1 96 71 2 8 87 5 3 5 70 2 8 TTK 536E 3 8 9 5 3 4 19 05 69 153 30 1 2 25 0 98 20 0 78 50 1 96 71 2 8 87 5 3 5 70 2 8 LIQUID CONNECTION SUCTION CONNECTION 830 32 7 D 4 x 12 0 5 554 21 8 A...

Страница 13: ...SS SVN03B EN 13 Typical Wiring Diagram Figure 9 Wiring Diagram TTK 509E 512E 518E 524E 530E 536E 220 240V 1PH 50 60Hz ...

Страница 14: ...units TTK Figure 11 Wiring Interconnection MCW K and L models with condensing units TTK NOTES 1 Single power supply point for each unit indoor unit and outdoor unit NOTES 1 Single power supply point for both units indoor unit and outdoor unit 208 230V 1PH 50 60 Hz 208 230V 1PH 50 60 Hz 208 230V 1PH 50 60 Hz ...

Страница 15: ...units TTK Figure 13 Wiring Interconnection MCW A model with condensing units TTK NOTES 1 Single power supply point for each unit indoor unit and outdoor unit NOTES 1 Single power supply point for both units indoor unit and outdoor unit 208 230V 1PH 50 60 Hz 208 230V 1PH 50 60 Hz 208 230V 1PH 50 60 Hz ...

Страница 16: ...units TTK Figure 15 Wiring Interconnection MCX with condensing units TTK NOTES 1 Single power supply point for each unit indoor unit and outdoor unit NOTES 1 Single power supply point for both units indoor unit and outdoor unit 208 230V 1PH 50 60 Hz 208 230V 1PH 50 60 Hz 208 230V 1PH 50 60 Hz ...

Страница 17: ...units TTK Figure 17 Wiring Interconnection MCD with condensing units TTK NOTES 1 Single power supply point for each unit indoor unit and outdoor unit NOTES 1 Single power supply point for both units indoor unit and outdoor unit 208 230V 1PH 50 60 Hz 208 230V 1PH 50 60 Hz 208 230V 1PH 50 60 Hz ...

Страница 18: ...umber Supersedes Stocking Location Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice Only qualified technicians should perform installation and servicing of equipment referred to in this publication SS SVN03B EN SL UN 000 SS SVN03B EN 0903 SS SVN03A EN 0703 Houston TX Code X39150103 01 ...

Отзывы: